• Title/Summary/Keyword: Series Active Compensator

Search Result 22, Processing Time 0.022 seconds

A Study on the Over-Current Protection Method of A Series Active Compensator (직렬 능동 보상기의 과전류 보호방법에 관한 연구)

  • Chae, Beom-Seok;Lee, U-Cheol;Lee, Taek-Gi;Hyeon, Dong-Seok
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.51 no.6
    • /
    • pp.321-329
    • /
    • 2002
  • A protection scheme for series active compensator is presented and analyzed in this paper. The proposed series active compensator operated as a high impedance K($\Omega$) to the fundamentals when short-circuit faults occur in the power distribution system, and two control strategies are proposed in this paper The first is the method by detecting the fundamental source current through the p-q theory, the second is the method by detecting the fundamental component of load current in Synchronous Reference Frame(SRF). When the short-circuit faults occur in the power distribution system, the proposed scheme can protect the series active compensator without additional protection circuits. The validity of the Proposed Protection scheme was investigated through experimental results.

A New Control Scheme of the Line-Interactive UPS Using the Series Active Compensator (직렬 능동 보상기를 이용한 Line-Interactive UPS의 새로운 제어 기법)

  • Jang, Hoon;Lee, Woo-Cheol;Hyun, Dong-Seok
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.8
    • /
    • pp.405-412
    • /
    • 2003
  • This paper presents a three-phase Line-Interactive uninterruptible power supply (UPS) system with series-parallel active power-line conditioning capabilities, using synchronous reference frame (SRF) based controller, which allows an effective power factor correction, source harmonic voltage compensation, load harmonic current suppression, and output voltage regulation. The three-phase UPS system consists of two active power compensator topologies. One is a series active compensator, which works as a voltage source in phase with the source voltage to have the sinusoidal source current and high power factor under the deviation and distortion of the source voltage. The other is a parallel active compensator which works as a conventional sinusoidal voltage source in phase with the source voltage, providing to the load a regulated and sinusoidal voltage with low THD (total harmonic distortion). The control algorithm using SRF method and the active power flow through the Line-interactive UPS systems are described and studied. The simulation and experimental results are depicted in this paper to show the effect of the proposed algorithm.

Over Current Protection Schemes for Active Filters with Series Compensators

  • Lee, Woo-Cheol;Lee, Taeck-Kie
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.4B no.3
    • /
    • pp.134-145
    • /
    • 2004
  • This paper presents and analyses protection schemes for a series active compensator, which consists of a Unified Power Quality Conditioner (UPQC) or a hybrid active power filter. The proposed series active compensator operates as a high impedance "k(D)" for the fundamental components of the power frequency during over current conditions in the distribution system. Two control strategies are proposed in this paper. The first strategy detects the fundamental source current using the p-q theory. The second strategy detects the fundamental component of the load current in the Synchronous Reference Frame (SRF). When over currents occur in the power distribution system momentarily, the proposed schemes protect the series active compensator without the need for additional protection circuits, and achieves excellent transient response. The validity of the proposed protection schemes is investigated through simulation and compared with experimental results using a hybrid active power filter systems.

A New Control Scheme for Unified Power Quality Compensator-Q with Minimum Power Injection

  • Lee, Woo-Cheol
    • Journal of Power Electronics
    • /
    • v.7 no.1
    • /
    • pp.72-80
    • /
    • 2007
  • Voltage sags are one of the most frequently occurring power quality problems challenging power systems today. The Unified Power Quality Conditioner (UPQC) is one of the major custom power solutions that are capable of mitigating the effect of supply voltage sags at the load or Point of Common Coupling (PCC). A UPQC-Q employs a control method in which the series compensator injects a voltage that leads the supply current by $90^{\circ}C$ so that the series compensator at steady state consumes no active power. However, the UPQC-Q has the disadvantage that its series compensator needs to be overrated. Thus it cannot offer effective compensation. This paper proposes a new control scheme for the UPQC-Q that offers minimum power injection. The proposed minimum power injection method takes into consideration the limits on the rated voltage capacity of the series compensator and its control scheme. The validity of the proposed control scheme is investigated through simulation and experimental results.

A Study on DC Changing Algorithm of the Line-Interactive UPS with Dual Converter Structure (2중 컨버터 구조를 갖는 계통 연계형 UPS의 DC 충전 알고리듬에 관한 연구)

  • Lee, Woo-Cheol;Yoo, Dong-Sang
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.3
    • /
    • pp.27-34
    • /
    • 2005
  • This paper presents a three phase Line-Interactive uninterruptible power supply(UPS) system with dual converter structure. The three phase UPS system consists of two active power compensator topologies. One is a series active compensator, which works as a voltage source in phase with the source voltage to have the sinusoidal source current and high power factor under the deviation and distortion of the source voltage. The other is a parallel active compensator, which works as a conventional sinusoidal voltage source in phase with the source voltage, providing to the load a regulated and sinusoidal voltage with low total harmonic distortion(THD). This paper presents in the series and parallel active compensator charging method depending on the amplitude of the source voltage. The conventional Line-Interactive UPS system is responsible for the DC charging and output voltage regulation at the same time, but UPS system with dual converter structure, a series active compensator can also charge the DC link. Therefore the charging algorithm using the series and parallel compensator needs to be researched. Therefore, by making the DC link voltage stable it can contribute the stability of series and parallel compensator. The simulation and experimental result are depicted in this paper to show the effect of the proposed algorithm.

A Study on the Line-Interactive UPS with Power Factor correction (Line - Interactive UPS의 역률 개선 방안에 관한 연구)

  • Jang Hoon;Lee Woo-Cheol;Lee Taeck-Kie;Hyun Dong-Seok
    • Proceedings of the KIPE Conference
    • /
    • 2001.12a
    • /
    • pp.93-96
    • /
    • 2001
  • This paper proposed on the Line-Interactive UPS with power factor correction. The paper Line-Interactive UPS topology with its advantages is reviewed. Next introduces Line -Interactive UPS of the series active compensator. The series active compensator controls input currents and power factor.

  • PDF

A Study on Control and Compensating Characteristics of Active Series Voltage Compensator with Harmonic Current Compensating Capability (고조파전류 보상 기능을 갖는 능동 직렬 전압보상기의 제어 및 보상특성에 관한 연구)

  • 이승요;김홍성;최규하;신우석;김홍근
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.5 no.5
    • /
    • pp.484-492
    • /
    • 2000
  • In this paper, a voltage compensator with harmonic current compensating capability is studied and its compensating characteristics are analyzed. Like the hybrid active power filter, the proposed system is composed of parallel LC passive filter and series PWM converter connected to power line through series transformer. It is shown that the compensation of harmonic current generated due to nonlinear loads such as diode rectifier and instantaneous voltage compensation of the source are performed through the proposed compensating system. The operating principle of the proposed system is described through a single-phase equivalent circuit and the control strategy is suggested on the d-q rotating reference frame of the 3-phase system. Also, experiment is carried out to verify compensating characteristics of the proposed system.

  • PDF

A NEW INSTANTANEOUS VOLTAGE COMPENSATOR WITH FUNCTION OF ACTIVE POWER FILTERING

  • Lee, Seung-Yo;Lee, Jeong-Min;Lee, Sang-Yong;Mok, Hyung-Soo;Choe, Gyu-Ha
    • Proceedings of the KIPE Conference
    • /
    • 1998.10a
    • /
    • pp.780-784
    • /
    • 1998
  • A novel active input unbalance voltage compensator with harmonic current compensating capability is proposed and the operating principle of the proposed system is presented in the 3-phase power system. The proposed system performs both the voltage regulation of the load and the compensation of the harmonic currents generated due to nonlinear load such as diode rectifier. The system to compensate unbalanced voltage and hramonic currents is composed of a 3-phase voltage source inverter, LC filter, series transformer and passive devices at the load side of the line. The compensating voltage to regulate the load voltage and to remove the harmonic current components is transmitted to the line by the series transformer. The validity of the line by the series transformer. The validity of the proposed system is proved by the results of computer simulation.

  • PDF

Hybrid Series Active Power filter Based on Performance Function Theory for 3-Phase 4-wire System (성능함수제어 알고리즘을 이용한 3상 4선식 하이브리드형 직렬능동전력필터)

  • Kim, Jin-Sun;Shin, Jae-Hwa;Kim, Young-Seok
    • Proceedings of the KIEE Conference
    • /
    • 2003.07b
    • /
    • pp.1096-1098
    • /
    • 2003
  • In this paper, the control algorithm and control methods for a combined system of shunt passive filter and series active filter in 3-phase 4-wire system are discussed. Moreover, the 3-phase 4-wire system is widely employed in distributing electric energy to several office building and manufacturing plants. In such systems, the third harmonic and odd multiples of $3^{rd}$($9^{th}$, $15^{th}$, etc.) are termed as triple and zero sequence components that do not cancel each other in the system neutral. As a result, the triple harmonics add together creating a primary source of excessive neutral current. Regarding this concern, this paper presents a new control scheme for a series hybrid active system. This series active power filter acts not only as a harmonic compensator but also as a harmonic isolator. Hence the required rating of the series active filter is much smaller than that of a conventional shunt active filter. However, the performance of the combined system is greatly influenced by the filtering algorithm employed in the active power filter. This paper proposes a series active power filter scheme based on performance function. Some experiments was executed and experimental results from a prototype active power filter confirm the suitability of the proposed approach.

  • PDF

Stand-Alone Type Single-Phase Fuel Cells Micro-Source with ac Voltage Compensation Capability (교류전압 보상 기능을 갖는 독립형 단상 연료전지 마이크로 소스)

  • Jung, Young-Gook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.1
    • /
    • pp.35-41
    • /
    • 2009
  • This paper proposes a stand alone type single-phase fuel cells micro-source with a voltage sag compensator for compensating the ac output voltage variations (sag or swell) of micro-source. The proposed micro-source is consist of a PEM(polymer electrolyte membrane) fuel cells simulator, a full bridge de converter, a 60Hz PWM(pulse width modulation) VSI(voltage source inverter), and a voltage sag compensator. Voltage sag compensator is similar to the configuration of hybrid series active power filter, and it is directly connected to micro-source through the injection transformer. Compensation algorithm of a voltage sag compensator adopts a single phase p-q theory. Effectiveness of the proposed the system is verified by the PSIM(power electronics simulation tool) simulation in the steady state and transient state which the proposed system is able to simultaneously compensate the harmonic current and source voltage sag or swell.