• Title/Summary/Keyword: Seismic performace evaluation

Search Result 1, Processing Time 0.014 seconds

Seismic Response Estimation of Water Extinguishing Facilities using Shaking Table Tests (진동대 실험을 통한 수계 소화설비의 지진응답평가에 관한 연구)

  • Nam, Min-Jun;Park, Seung-Hee;Kim, Dong-Joon;Choi, Jun-Sung
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.16 no.4
    • /
    • pp.9-18
    • /
    • 2012
  • In this study, a shaking table test was performed for the evaluation of water extinguishing facilities. Water extinguishing facilities, such as a general pipe, a seismic pipe (Loof type) and a pump, were used in the experiment. This captured the dynamic characteristics of water extinguishing systems by earthquake records at El-Centro with a 50%, 70%, 100%, 120% level. As a result, seismic type facilities have excellent seismic performance compared to general facilities. By using the acceleration response spectrum, not only is the performance evaluation of water extinguishing facilities able to be determined, but also the deformation of facilities in low earthquake levels can be known. This proposed approach can determine the seismic performance evaluation of water extinguishing facilities and verify seismic performance criteria.