Abstract
In this study, a shaking table test was performed for the evaluation of water extinguishing facilities. Water extinguishing facilities, such as a general pipe, a seismic pipe (Loof type) and a pump, were used in the experiment. This captured the dynamic characteristics of water extinguishing systems by earthquake records at El-Centro with a 50%, 70%, 100%, 120% level. As a result, seismic type facilities have excellent seismic performance compared to general facilities. By using the acceleration response spectrum, not only is the performance evaluation of water extinguishing facilities able to be determined, but also the deformation of facilities in low earthquake levels can be known. This proposed approach can determine the seismic performance evaluation of water extinguishing facilities and verify seismic performance criteria.
본 연구에서는 진동대 실험을 통한 수계형 소화설비의 내진성능평가를 실시하였다. 실험에 사용된 수계형 소화설비 시설에는 일반 배관, 내진형 배관, 펌프 등 이다. 그리고 수계형 소화설비 시설의 동적거통특성을 파악하기 위하여 El-Centro 지진파 50%, 70%, 100%, 120% 수준의 가진을 가하였다. 그 결과, 내진형 설비보다 일반형 설비에서 변위 응답과 가속도 응답이 큰 것으로 보아 내진형 설비가 일반설비에 비해 내진성능이 우수하다는 것을 알 수 있었다. 또한, 가진 수준별 가속도 응답스펙트럼을 통하여 일반형 시설과 내진형 시설의 성능 평가뿐만 아니라 작은 규모의 지진에서도 일반형 설비의 파괴가 일어날 수 있다는 것을 알 수 있었다. 본 연구를 통해 수계 소화설비의 내진성능을 평가 할 수 있었고 수계 소화설비의 내진성능 기준을 검증할 수 있었다.