DOI QR코드

DOI QR Code

Seismic Response Estimation of Water Extinguishing Facilities using Shaking Table Tests

진동대 실험을 통한 수계 소화설비의 지진응답평가에 관한 연구

  • 남민준 (성균관대학교 u-City 공학과) ;
  • 박승희 (성균관대학교 사회환경시스템공학과) ;
  • 김동준 (파라다이스산업 기술연구소) ;
  • 최준성 (한국유지관리(주))
  • Received : 2012.02.13
  • Accepted : 2012.06.07
  • Published : 2012.08.31

Abstract

In this study, a shaking table test was performed for the evaluation of water extinguishing facilities. Water extinguishing facilities, such as a general pipe, a seismic pipe (Loof type) and a pump, were used in the experiment. This captured the dynamic characteristics of water extinguishing systems by earthquake records at El-Centro with a 50%, 70%, 100%, 120% level. As a result, seismic type facilities have excellent seismic performance compared to general facilities. By using the acceleration response spectrum, not only is the performance evaluation of water extinguishing facilities able to be determined, but also the deformation of facilities in low earthquake levels can be known. This proposed approach can determine the seismic performance evaluation of water extinguishing facilities and verify seismic performance criteria.

본 연구에서는 진동대 실험을 통한 수계형 소화설비의 내진성능평가를 실시하였다. 실험에 사용된 수계형 소화설비 시설에는 일반 배관, 내진형 배관, 펌프 등 이다. 그리고 수계형 소화설비 시설의 동적거통특성을 파악하기 위하여 El-Centro 지진파 50%, 70%, 100%, 120% 수준의 가진을 가하였다. 그 결과, 내진형 설비보다 일반형 설비에서 변위 응답과 가속도 응답이 큰 것으로 보아 내진형 설비가 일반설비에 비해 내진성능이 우수하다는 것을 알 수 있었다. 또한, 가진 수준별 가속도 응답스펙트럼을 통하여 일반형 시설과 내진형 시설의 성능 평가뿐만 아니라 작은 규모의 지진에서도 일반형 설비의 파괴가 일어날 수 있다는 것을 알 수 있었다. 본 연구를 통해 수계 소화설비의 내진성능을 평가 할 수 있었고 수계 소화설비의 내진성능 기준을 검증할 수 있었다.

Keywords

References

  1. 소방방재청 재난안전기술연구개발 "한반도 활성단층과 연구 현황," 한국방재학회지, Vol. 11, No. 1, 117-123, 2011.
  2. 신이철, 한병찬, 박선규, 이현진, 권영진 "소방시설 내진설계의 필요성과 기준정비에 관한 연구," 한국 화재소방학회지 논문집, Vol. 23, No. 2, 6-12, 2009.
  3. 정진환, 김남식, 김인태, 최형석, 박찬영, "KOCED 지진실험 센터," 대한토목학회지, Vol. 57, No. 8, 43-49, 2009.
  4. 건설교통부, 내진설계기준연구(II), 1997.
  5. 대한건축학회, Korea Building Code, 국토해양부, 2009.
  6. MATLAB, The Language of Technical Computing, Mathworks, 2011.
  7. Roberto Villaverde "Simple method to estimate the seismic nonlinear response of nonstructural components in buildings," Engineering Structures, Vol. 28, No. 8, 1209-1221, 2006. https://doi.org/10.1016/j.engstruct.2005.11.016
  8. Elliott GOODWIN, Emmanuel MARAGAKIS, Ahmad ITANI "Seismic evaluation of hospital piping systems," Earthquake Engineering, 13th World Conference on Earthquake Engineering, Paper No. 1081, 2004.
  9. ICC, International building code (IBC), International Code Council, INC, 2012.
  10. Farzad Naeim, The Seismic Design Handbook Second Edition, Kluwer Academic Publishers, 681-722, 2001.
  11. 윤종구, 김동수 "국내 지반특성에 적합한 설계지반운동 결정 방법에 대한 연구," 한국지진공학회 논문집, Vol. 8, No. 3, 23-32, 2004.
  12. 김장훈 "비구조요소의 내진설계," 대한건축학회 논문집, Vol. 48, No. 8, 53-56, 2004.
  13. 남민준, 박승희, 윤종구, 서춘교, "진동대 실험을 통한 수계형 소화설비의 내진성능 평가," 2012년 학술발표회 논문집, 한국지진공학회, 121-124, 2012.
  14. 김두기, 구조동역학, 구미서관, 서울, 474-504, 2009.
  15. 이현진, 신이철, 이재영, 서동구, 한병찬, 김재환, 권영진 "소방 설비 내진설계에 관한 각국 기준 비교 연구," 2008년 춘계학술발표회 눈문집, 한국화재소방학회, 238-241, 2008.
  16. 김종부, 스프링클러 설비의 내진 설계 방법론 연구, 석사학위논문, 서울시립대학교, 2011.

Cited by

  1. Design Optimization of Valve Support with Enhanced Seismic Performance vol.32, pp.11, 2015, https://doi.org/10.7736/KSPE.2015.32.11.997