• Title/Summary/Keyword: Rod-ground system

Search Result 63, Processing Time 0.019 seconds

Analysis of the Frequency Dependent Characteristics of Ground Impedance of a Ground Rod (봉상접지전극의 접지임피던스의 주파수의존성의 분석)

  • 이복희;엄주홍
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.8
    • /
    • pp.426-432
    • /
    • 2004
  • This paper presents a systematic approach of measurement, modeling and analysis of grounding system impedance in the field of lightning protection system and intelligent power equipments. The measurement and analysis system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 50 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. Although the steady-state ground resistance of the ground rod of 50 m was less than that of the ground rod of 10 m, the ground impedances of the ground rod of 50 m over the frequency range of more than 60 kHz were much greater than those of the ground rod of 10 m. Furthermore, the equivalent circuit model based on the measured data was proposed. and the calculated results were in approximately agreement with the measured data.

A Study on the Optimal Divergence Spacing of the Connecting Grounding Rod to the Dangerous Voltage in the Global Earthing Network of Urban Rail Transit (도시철도 통합접지망에서의 위험전압에 따른 연접접지봉의 최적 분기간격에 관한 연구)

  • Jung, Ho-Sung;Park, Young;Kim, Hyeng-Chul;Kim, Jin-Hee;Kim, Jae-Moon;Cho, Dae-Hoon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.9
    • /
    • pp.1374-1379
    • /
    • 2012
  • Urban rail transit tends to global grounding system in order to control ground potential rise and potential differences between electric equipments. In addition, global grounding system can discharge the large capacity surge current to the ground safely. Since some railway electric equipments are installed all section of line, the global grounding system connected with the connecting grounding wire is more effectively. However, if the fault occurred in the connecting grounding wire area, some dangerous voltage is generated. So, the installation of additional grounding rod will be required. In this study, the global grounding system is simulated using CDEGS program to analyze the divergence spacing of additional ground rod depending on dangerous electric potential characteristics. Grounding net of the each station is modelled in depending on the size of the platform, and the spacing of the connecting grounding rod are compared 50m, 100m, 250m and 400m. Simulation results considering of earth resistivity and underground condition of the connecting grounding wire, spacing of the connecting grounding rod is that less than 250m to spacing of the ground rod was appropriately confirmed.

Potential Reduction and Energy Dispersion Due to Ionization Around the Submerged Ground Rod (수중에 잠긴 접지전극 주변에서의 이온화에 의한 전위저감 및 에너지방출)

  • Choi, Jong-Hyuk;Ahn, Sang-Duk;Yang, Soon-Man;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.1
    • /
    • pp.92-99
    • /
    • 2009
  • Deeply-driven ground rod in the rainy season may contact with rainwater and ground water. When surge voltages are applied to the submerged ground rods, the ionization around the ground rods are occurred. Ionization in soil and/or water is affected in dynamic performance of ground rod systems. This work aims at studying the transient performance of ground rod system under impulse voltage using scale model in an electrolytic tank. The potential reduction and energy dispersion caused by ionization were treasured and quantitatively analyzed using the Matlab Program. As a result, the peak voltage at the terminal of ground rod was varied with water resistivity and charging voltage of Marx generator. The potential at the terminal of the ground rod was approximately reduced to a half of the applied voltage just below breakdown voltage. Also the energy more than half of the applied energy was dispersed through the ground rod due to ionization just below breakdown voltage.

A Study on Transient Grounding Performance of Ground Rods

  • Yun Dong-Hyeon;Lee Hyeong-Su;Lee Gwan Hyeong
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.11a
    • /
    • pp.281-285
    • /
    • 2002
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod using HIFREQ[1], which is an engineering electro-magnetic code based on MoM (Method of Moment).

  • PDF

An Analysis on Resultant Ground Impedance Based on the Potential Interference Of Parallel Ground Rods (전위간섭을 기초로 한 병렬 접지봉의 합성접지임피던스의 분석)

  • Lee, Bok-Hee;Seong, Chang-Hoon;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.12
    • /
    • pp.107-112
    • /
    • 2011
  • Multiple ground rods are commonly used to obtain the low ground impedance, but they will not reduce the ground impedance unless the spacings between the ground rods are sufficient. This paper presents the experimental results of frequency-dependent resultant ground impedance of two ground rods in parallel. The resultant ground impedance of two ground rods in parallel were measured as functions of the spacing and length of ground rods and the frequency of test currents and were discussed based on the potential interferences. As a consequence, the frequency-dependent ground impedance of single ground rod and two combined ground rods give capacitive. It was found that the effect of potential interference on the ground impedance is directly associated with the frequency-dependent ground impedance and is strong in low frequency. Also, in order to reduce the increasing rate of resultant ground impedance of two ground rods due to potential interference to within 10(%), two ground rods in parallel will be placed over one rod length apart.

Transient Ground Impedances According to Shapes of Grounding Electrodes (접지전극의 형상에 따른 과도접지임피던스)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Jeong, Dong-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.1
    • /
    • pp.65-70
    • /
    • 2006
  • This paper presents the transient behaviors of grounding system impedance against lightning impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current were investigated. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system Also, the deeply-driven ground rod was effective to reduce the transient ground impedance in time domain of miceroseconds.

High Frequency Grounding Impedances of Vertically-Driven Ground Rods

  • Kim, Tae-Ki;Lee, Bok-Hee;Jeon, Duk-Kyu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.7
    • /
    • pp.41-48
    • /
    • 2009
  • Grounding impedance depends on the frequency of current flowing into a grounding system lightning in particular has a broad frequency spectrum from some tens of Hz to a few MHz. So the grounding impedance related to transient currents such as lightning should be measured. In this paper, the grounding impedances of vertically-driven ground rods of 10, 30 and 48[m] long are measured and analyzed as functions of the frequency of injected current and the feeding point. As a result, the longer the ground rod is, the lower the steady-state ground resistance is. However the grounding impedance of a vertically-driven ground rod at a high frequency is significantly increased. It is not always true that low grounding impedance follows from a low steady-state ground resistance. It is important to evaluate the high frequency performance of grounding systems for protection against lightning.

Grounding Resistance and Current Characteristics of the Planar Earth Structure using Multiple Discharge Paths (다중방전 경로를 이용한 편상접지체의 접지저항 및 전류특성)

  • Kim, Young-Sun;Kim, Dong-Min;Lee, Ki-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.9
    • /
    • pp.1564-1570
    • /
    • 2016
  • This study proposes a newly modified form of existing ground electrodes in order to secure trust of grounding system for large current caused by a stroke of lightning. Proposed planar earth structure has a several needle electrodes around a circular rod and 4 plane electrodes in all directions. The plane electrodes are fused with the insulator on the linear rod, so that they're electrically isolated. The concept is to increase the discharge amount of earth structure using multiple discharge paths like needle and plane electrodes. To check the discharge efficiency of the suggested scheme, the discharge currents are compared with typically used two kinds of ground rods. To ensure accuracy in the measurement of the discharge current, the same material was used for the comparison model. Also, the ground resistance are simulated by CDEGS commercial software and the results are compared with measured data. Based on this kind of experimental study, the suggested ground rod can be used when designing a ground system or when constructing a ground system at the site.

Property of Long vertical rod according to the different injection point with impulse current (대형 봉상 접지전극의 임펄스 인가위치에 따른 특성)

  • 이복희;장근철;엄주홍;김병근;오성균;길형준
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.369-372
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil or in insufficient place such as downtown, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flows into the grounding system, the ground impedance is remarkedly increased. This paper presents how the impulse and fault current works on the long. vertical ground rods associated with incoming points. When the test current was injected at the bottom of ground rod, the potential waveform of ground rod includes the oscillation with high frequency.

  • PDF

Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents (임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선)

  • Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jeon, Byung-Wook;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.62-68
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of deeply-driven ground rods associated with the injection point of impulse currents. The transient grounding impedance strongly depends on the length of deeply-driven ground rod and the rise time and injection point of impulse currents, and the intrinsic inductance of ground rod has a significant affect on the transient grounding impedance of grounding system in fast rise time ranges. The reduction of inductance is decisive to improve the impulse impedance behaviors of deeply-driven ground rods. It is effective that grounding conductor is connected to the top of the ground rod as short as possible.