• 제목/요약/키워드: Power transformer diagnosis

검색결과 113건 처리시간 0.023초

전력용 변압기 온라인 유중가스 진단기준치 및 알고리즘에 관한 연구 (Study on the Criterion and Algorithm for On-line Dissolved Gas of a Power Transformer)

  • 권동진;곽주식;곽희로;김재철;진상범
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권5호
    • /
    • pp.206-212
    • /
    • 2005
  • In this paper, criterion and algorithm for on-line dissolved gas of a Power transformer are studied. For the initial diagnosis of a power transformer, the on-line dissolved gas analysis is one of the most important and acceptable item to preventively diagnose a power transformer. But the criterion and algorithm of this item are not established yet in korea. In this paper, criterion and alarm level of the on-line dissolved gas analysis are based on the analysis of on-line data of operating transformers, Korea industrial standard and operation manual for a power transformer as well as accumulated data of the preventive diagnosis systems which have been operated at nine substations of Korea Electric Power Co.(KEPCO) since 1997, Therefore, the criterion and alarm level proposed in this paper are to be well suitable and are adaptable for the domestic operational environments and conditions of the power transformer. Considering that the conventional diagnosis system is capable only of accumulating and monitoring data of the power transformer operation, the criteria and the algorithms make it possible to accomplish an ultimate goal of the preventive diagnosis system. It is expected, therefore, that they will have a beneficial effect on broad applications of the preventive diagnosis system and the achievement of manless substation system in the future.

Intuitionistic Fuzzy Expert System based Fault Diagnosis using Dissolved Gas Analysis for Power Transformer

  • Mani, Geetha;Jerome, Jovitha
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권6호
    • /
    • pp.2058-2064
    • /
    • 2014
  • In transformer fault diagnosis, dissolved gas analysis (DGA) is been widely employed for a long period and numerous methods have been innovated to interpret its results. Still in some cases it fails to identify the corresponding faults. Due to the limitation of training data and non-linearity, the estimation of key-gas ratio in the transformer oil becomes more complicated. This paper presents Intuitionistic Fuzzy expert System (IFS) to diagnose several faults in a transformer. This revised approach is well suitable to diagnosis the transformer faults and the corresponding action to be taken. The proposed method is applied to an independent data of different power transformers and various case studies of historic trends of transformer units. It has been proved to be a very advantageous tool for transformer diagnosis and upkeep planning. This method has been successfully used to identify the type of fault developing within a transformer even if there is conflict in the results of AI technique applied to DGA data.

Expert System for Fault Diagnosis of Transformer

  • Kim, Jae-Chul;Jeon, Hee-Jong;Kong, Seong-Gon;Yoon, Yong-Han;Choi, Do-Hyuk;Jeon, Young-Jae
    • 한국지능시스템학회논문지
    • /
    • 제7권1호
    • /
    • pp.45-53
    • /
    • 1997
  • This paper presents hybrid expert system for diagnosis of electric power transformer faults. The expert system diagnose and detect faults in oil-filled power transformers based on dissolved gas analysis. As the preprocessing stage, fuzzy information theory is used to manage the uncertainty in transformer fault diagnosis using dissolved gas analysis. The Kohonen neural network takes the interim results by applying fuzzy informations theory as inputs, and performs the transformer fault diagnosis. The Proposed system tested gas records of power transformers from Korea Electric Power Corporation to verify the diagnosis performance of transformer faults.

  • PDF

유입변압기 고장분류를 위한 PNN 기반 Rogers 진단기법 개발 (PNN based Rogers Diagnosis Method for Fault Classification of Oil-filled Power Transformer)

  • 임재윤;이대종;지평식
    • 전기학회논문지P
    • /
    • 제65권4호
    • /
    • pp.280-284
    • /
    • 2016
  • Stability and reliability of a power system in many respects depend on the condition of power transformers. Essential devices as power transformers are in a transmission and distribution system. Being one of the most expensive and important elements, a power transformer is a highly essential element, whose failures and damage may cause the outage of a power system. To detect the power transformer faults, dissolved gas analysis (DGA) is a widely-used method because of its high sensitivity to small amount of electrical faults. Among the various diagnosis methods, Rogers diagonsis method has been widely used in transformer in service. But this method cannot offer accurate diagnosis for all the faults. This paper proposes a fault diagnosis method of oil-filled power transformers using PNN(Probability Neural Network) based Rogers diagnosis method. The test result show better performance than conventional Rogers diagnosis method.

전력용 변압기의 유중가스 분석을 위한 LVQ3의 적용 (Application of LVQ3 for Dissolved Gas Analysis for Power Transformer)

  • 전영재;김재철
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권1호
    • /
    • pp.31-36
    • /
    • 2000
  • To enhance the fault diagnosis ability for the dissolved gas analysis(DGA) of the power transformer, this paper proposes a learning vector quantization(LVQ) for the incipient fault recognition. LVQ is suitable expecially for pattern recognition such as fault diagnosis of power transformer using DGA because it improves the performance of Kohonen neural network by placing emphasis on the classification around the decision boundary. The capabilities of the proposed diagnosis system for the transformer DGA decision support have been extensively verified through the practical test data collected from Korea Electrical Power Corporation.

  • PDF

FCM과 ELM을 이용한 전력용 변압기의 모니터링 알고리즘 (A Monitoring Algorithm using FCM and ELM for Power Transformer)

  • 지평식;임재윤
    • 전기학회논문지P
    • /
    • 제61권4호
    • /
    • pp.228-233
    • /
    • 2012
  • In power system, substation facilities have become too complex and larger according to an extended power system. Also, customers require the high quality of electrical power system. However, some facilities become old and often break down unexpectedly. The unexpected failure may cause a break in power system and loss of profits. Therefore it is important to prevent abrupt faults by monitoring the condition of power systems. Among the various power facilities, power transformers play an important role in the transmission and distribution systems. In this research, we develop intelligent diagnosis technique for monitoring of power transformer by FCM(Fuzzy c-means) and ELM(Extreme Learning Machine). The proposed technique make it possible to diagnosis the faults occurred in transformer. To demonstrate the validity of proposed method, various experiments are performed and their results are presented.

FCM과 SOM을 이용한 전력용 변압기 고장진단 기법 (Fault Diagnosis Method of Power Transformer Using FCM and SOM)

  • 한운동;이대종;지평식
    • 한국콘텐츠학회논문지
    • /
    • 제7권3호
    • /
    • pp.25-33
    • /
    • 2007
  • 전력계통의 갑작스런 고장은 막대한 경제적 손실을 초래함으로 이를 방지하기 위한 전력계통의 상태를 진단하는 모니터링은 무엇보다도 중요하다. 본 논문에서는 FCM과 SOM을 이용하여 다양한 전력설비 중에서 가장 중요한 역할을 담당하는 전력용 변압기의 고장진단 알고리즘을 개발한다. 즉, FCM은 효과적인 특징점을 선택과 학습시간을 줄이기 위해 수행하고, SOM에 의해 변압기의 고장진단이 이루어진다. 제안된 방법은 변압기의 고장진단 뿐만 아니라 열화진행추이 특성까지 분석한다. 제안된 방법은 다양한 사례 연구를 통해 우수성을 입증하였다.

퍼지 패턴 분류와 뉴럴 네트워크를 이용한 지능형 유중가스 판정 시스템 (Intelligent Diagnosis System for DGA Using Fuzzy Pattern Classification and Neural Network)

  • 조성민;권동진;남창현;김재철
    • 전기학회논문지
    • /
    • 제56권12호
    • /
    • pp.2084-2090
    • /
    • 2007
  • The DGA (Dissolved Gases Analysis) technique has been widely using for fault diagnosis of the power transformers. Some electric power utility company establishes the criteria of DGA to improve reliability, because of difference of operation environment and design of power transformer. In this paper, we introduce intelligent diagnosis system for DGA result of KEPCO (Korea Electric Power Cooperation). This system can classify patterns type of gases ratio that frequently occurs in recent result of gases analysis using Fuzzy Inference. The classification of Patterns let us know that major causes of gases generation based on type of patterns. Finally, Neural Network based on patterns diagnose transformer. NN was trained using result data of DGA of actually faulted transformers recently. Result of intelligent diagnosis system is right well in comparison with actual inner inspection of transformers.

차량탑재형 HFPD의 개발 (The Development of HFPD System for Mibile-loading Vehicles)

  • 김덕근;임장섭;여인선
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.33-37
    • /
    • 2001
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

인가 스트레스에 따른 HFPD의 통계적 패턴해석 (Statistic Pattern Analysis of HFPD According to Applied Stress)

  • 김덕근;이은석;정영일;임장섭;김태성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.18-22
    • /
    • 2000
  • The partial discharge testing is widely used in insulation property measurement because it gives low stress to high voltage equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF