• Title/Summary/Keyword: Power distribution lines

Search Result 306, Processing Time 0.03 seconds

Switching Surge Analysis of Vacuum Circuit breaker at the Power Plant distribution lines (발전소 비전계통 진공차단기의 스위칭 써지 해석)

  • Kim, Ik-Mo;Kim, Ji-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.305-308
    • /
    • 2001
  • The first objective of this study is to set up the switching surge analysis method in motor driving distribution system. The simplified model which can simulate the motor energization and circuit breaker re-ignitions, and each circuit element model is presented in this paper. The second objective is to calculate the quantify of surge over-voltage in real nuclear power station. And the surge suppressing measures are verified on the simulation basis. It is clarified that most cases are not satisfactory to meet the IEEE standard 522-1992 without using surge suppressing measures. In cases that the surge arrester are installed in distribution board at the load side of circuit breaker. The IEEE specification is fully met.

  • PDF

Fuzzy Estimation for Fault Location

  • Tipsuwanporn, V.;Tuppadung, Y.;Suesut, T.;Rukkaphan, S.;Junkrob, N.
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2000.10a
    • /
    • pp.453-453
    • /
    • 2000
  • This paper presented Fuzzy logic application to Electrical power system analysis for fault location estimation in distribution lines and apply the Power system theory to be fuzzy logic database. The case study referred to the Overhead distribution line of the Provincial Electricity Authority (PEA.), Thailand which mostly the distribution line of PEA. are Radial schemes. These benefits include reduced outage time, help in locating momentary faults, enhance safety to the line crews and provide notification of an outage without receiving calls from the consumer, Which these benefits also increase Reliability, Stability and Efficiency.

  • PDF

Analysis of the lightning characteristics by the LPATS in KOREA (낙뢰위치 표정시스템(LPATS)에 의한 2004넌 한반도 낙뢰통계 분석결과)

  • Kwak, J.S.;Woo, J.W.;Kweon, D.J.;Kang, Y.W.;Moon, J.D.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.606-608
    • /
    • 2005
  • As the overhead transmission lines are exposed to the outdoor weather, the causes of the transmission lines faults are from natural conditions, and among these faults, the outage rate due to lightning is more than 60%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the statistical distribution of lightning current parameters and the IKL map.

  • PDF

Analysis of the lightning characteristics by the Lightning DB in KOREA (낙뢰위치표정시스템의 낙뢰 DB를 이용한 한반도 뇌격 특이특성 분석)

  • Woo, J.W.;Kwak, J.S.;Shim, E.B.;Lee, G.W.;Kim, K.W.;Kim, B.S.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1658-1660
    • /
    • 2001
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the statistical distribution of lightning current parameters and the IKL map.

  • PDF

Analysis of LPATS-III Error Level and the lightning characteristics in KOREA (LPATS-III의 오차검토 및 한반도 낙뢰발생빈도 분석결과)

  • Woo, J.W.;Shim, E.B.;Kwon, D.J.;Choi, Y.M.;Lee, S.J.;Kim, K.W.;Lee, B.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1772-1774
    • /
    • 2002
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. To study the basic research of the lightning parameters for power system operation, LPATS-III (Lightning Positioning and Tracking System) has been introduced since 1995 in Korea. This paper describes the inspection result about location information error and the statistical distribution of lightning current.

  • PDF

Analysis of the lightning characteristics by LPATS Data during 7 year (LPATS에 의한 7년간의 한반도 뇌격특성분석)

  • Woo, J.W.;Shim, E.B.;Kwak, J.S.;Kweon, D.J.;Moon, J.D.;Han, S.O.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.509-511
    • /
    • 2003
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the statistical distribution of lightning current parameters and the IKL map.

  • PDF

Development of the equipment for detecting the poor power facilities by receiving electric noises (전자파 잡음을 이용한 전기설비 불량 검출장치 개발)

  • 이복규;강성철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1997.10a
    • /
    • pp.1356-1359
    • /
    • 1997
  • There are various methods to detect the faulty electric facilities(esp, insulator) indirectly on power distribution lines at a certain distance apart. This paper describes the proto type equipment to detect a faulty insulator by receiving a electric discharge noises, which are generated with a periodicity of 120Hz.

  • PDF

Load Shedding Algorithm Using Linear Programming for Congestion Problems by a Major Contingency

  • Shin Ho-Sung;Song Kyung-Bin
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.4
    • /
    • pp.371-377
    • /
    • 2005
  • Congestion problems of transmission lines are very important research issues in power system operations. Load curtailment is one of the ways to solve congestion problems by a major contingency. A systematic and effective mechanism for load shedding has been developed by investigating congestion distribution factors and the direct load control program. In this paper, a load shedding algorithm using linear programming for congestion problems by a major contingency is presented. In order to show the effectiveness of the proposed algorithm, it has been tested on the 6-bus sample system and the power system of Korea, and their results are presented.

A New Algorithm to Reduce the Mal-Operation of DOCR in Bi-directional Power Distribution Systems

  • Jang, Su-Hyeong;Oh, Joon-Seok;Jeong, Ui-Yong;Kim, Jae-Eon
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.3
    • /
    • pp.585-591
    • /
    • 2016
  • DOCR can be used to efficiently increase the reliability and to protect the bi-directional D/L(Distribution Lines). As more DG(Distributed Generation)s attempt to connect the bi-directional D/L, there is an increasing need for studies of how to use DOCR installed in the D/L. This paper investigates the operating principles of DOCR and presents the results an effect of sequence and fault impedance in L-L(Line to Line) fault. An advanced DOCR operating algorithm is proposed to reduce the mal-operation of conventional DOCR. The proposed algorithm is applied to the bi-directional power flow system and shows that it decreases the mal-operation of DOCR through the computer simulation.

Application of Wireless Sensor for Diagnostics of Electric Equipments (전력 설비 진단을 위한 무선 센서의 응용)

  • Yun, Ju-Ho;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2112-2113
    • /
    • 2008
  • The concept is based on distributed wireless sensors that are attached to the incoming and outgoing power lines of secondary substations. A sensor measures only phase current characteristics of the wire it is attached to, is not synchronized to other sensors and does not need configuration of triggering levels. The main novelty of the concept is in detecting and locating faults by combining power distribution network characteristics on system level with low power sampling methods for individual sensors. This concept enables the sensor design to be simple, energy efficient and thus applicable in new installations and for retrofit purposes in both overhead and underground electrical distribution systems.

  • PDF