• Title/Summary/Keyword: Porcelain Insulator

Search Result 140, Processing Time 0.024 seconds

The Inner Defect Detection of Suspension Insulators by Lightning Impulse (뇌 임펄스를 이용한 현수애자의 내부결함 검출)

  • 송일근;곽희로
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.9 no.6
    • /
    • pp.83-90
    • /
    • 1995
  • This paper analyzed the electrical field strength of porcelain suspension insulator used various testing methods in order to present the causes and countermeasure for the puncture failure by the inner minute defect. A power frequency puncture test and a step-front-of-wave flashover voltage test were conducted. The failed specimen of these samples was analyzed material characteric observed the cross-sectional picture by the scanning electron microscope, and tested the autoclave expansion for the portland cement using the metal bond agent. The porcelain made a progress the failure by the thermal expansion coefficient of the different material. The inner detecting technique on behalf of the puncture failure protection is presented such as the steep-front-of-wave flashover voltage test.

  • PDF

Various Factors Influencing the Lifetime of Suspension-Type Porcelain Insulators for 154 kV Power Transmission Lines

  • Choi, In Hyuk;Park, Joon Young;Kim, Tae Gyun;Yoon, Yong Beum;Yi, Junsin
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.3
    • /
    • pp.151-154
    • /
    • 2017
  • In this article, we investigated the various influencing factors that degraded the lifetime of suspension insulators in 154 kV transmission lines, and showed the possible solutions to avoid such breakdowns. With respect to achieve safety, reliability and aesthetical considerations, the characteristics of transmission and distribution network power cables should be improved. Suspension insulators are particularly important to study, as they have developed to be the main component of transmission lines due to their ability to withstand the electrical conductivity of high-voltage power transmission. Suspension insulators are mostly made from glass, rubber and ceramic material due to their high resistivity. In Korea, porcelain suspension insulators are typically used in the transmission line system, as they are cheaper and more flexible compared to other types of insulators. This is effective from preventing very high and steep lightening impulse voltages from causing the breakdown of suspension insulators used in power lines. Other influential factors affect the lifetime of suspension insulators that we studied include temperature, water moisture, contamination, mechanical vibration and electrical stress.

Development of Image Process for Crack Identification on Porcelain Insulators (자기애자의 자기부 균열 식별을 위한 이미지 처리기법 개발)

  • Choi, In-Hyuk;Shin, Koo-Yong;An, Ho-Song;Koo, Ja-Bin;Son, Ju-Am;Lim, Dae-Yeon;Oh, Tae-Keun;Yoon, Young-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.33 no.4
    • /
    • pp.303-309
    • /
    • 2020
  • This study proposes a crack identification algorithm to analyze the surface condition of porcelain insulators and to efficiently visualize cracks. The proposed image processing algorithm for crack identification consists of two primary steps. In the first step, the brightness is eliminated by converting the image to the lab color space. Then, the background is removed by the K-means clustering method. After that, the optimum image treatment is applied using morphological image processing and median filtering to remove unnecessary noise, such as blobs. In the second step, the preprocessed image is converted to grayscale, and any cracks present in the image are identified. Next, the region properties, such as the number of pixels and the ratio of the major to the minor axis, are used to separate the cracks from the noise. Using this image processing algorithm, the precision of crack identification for all the sample images was approximately 80%, and the F1 score was approximately 70. Thus, this method can be helpful for efficient crack monitoring.

A study on the Unbalanced Insulation of the Double Circuit 154 kV Transmission Lines to Reduce Lightning Failure Rate (뇌사고율 저감을 위한 154 kV 송전선의 차등절연 적용 방안 연구)

  • Kwak, J.S.;Kang, Y.W.;Woo, J.W.;Shim, E.B.;Kim, W.G.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.151-159
    • /
    • 2003
  • According to the records, approximately 50 percent of power failure were caused by lightning. Conventional fault preventive measures against lightning include reduction of the footing resistance of the tower, multiplication of overhead ground wires and unbalanced insulation of the double circuit transmission tower. In addition to these, transmission line arresters have been recently appeared as an alternatives. In this paper an unbalanced insulation method with transmission line arrester was assumed as another countermeasure against simultaneous double circuit trip of 154 kV transmission line by lightning strike. The lightning performance of line arrester was compared with conventional insulation concept using different numbers of porcelain and glass insulator. Larger numbers of insulator simply increase flashover current level by lightning but the lightning performance doesn't proportional to it. EMTP simulation and predictive calculation of lightning failure rate were carried out to evaluate the performance.

  • PDF

Reliability Assessment of Forest Fire on EHV Polymer Insulator Strings (송전용 폴리머애자의 산불 영향 신뢰성 평가)

  • Min, Byeong-Wook;Shin, Tai-Woo;Choi, In-Hyuk;Choi, Han-Yeol;Park, Jae-Ung;Yu, Kun-Yang
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.436-437
    • /
    • 2006
  • Porcelain insulators have generally been used in Korea but polymer insulators which are superior in that they are light weight, explosion proof, impact proof, economical with construction characteristics, have been in use for the 154kV transmission line since 1999 following a worldwide trend towards the reduced weight, simplification and compact usage of new material insulators. However there have been approximately 500 cases of forest fires in Korea, so the transmission lines that for the most part pass through mountainous areas have been highly effected and the highly polymerized compound polymer insulator has raised concern about reliability in cases of exposure to forest fires. Therefore for the reliability assessment of the effect of forest fires on polymer insulators, mechanical and electrical characteristics are analyzed by an artificial flare test device and transmission facility surrounding conditions along with forest fire characteristics are surveyed. In addition to this, actual 90kV energized transmission line was tested with an artificial forest fire and the expanded usage of polymer insulators is presented through the analysis of mechanical and electrical characteristics and physical properties, and a study on the influence of forest fires on polymer insulators.

  • PDF

Improvement of surface insulation properties of engineering thermoplastics by using nano/micro composite (나노/마이크로 컴포지트를 이용한 엔지니어링 열가소성 플라스틱의 표면 절연 개선)

  • Jung, Eui-Hwan;Lim, Kee-Joe;Hur, Jun;Jeong, Jong-Hun;Kim, Pyung-Jung;Jeong, Su-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.29-29
    • /
    • 2010
  • Engineering plastics have excellent electrical properties, mechanical strength and various characteristic which include chemical resistance, environmental resistance, weatherability at a wide temperature range. It has good characteristic(light weight, good productivity) as compare with epoxy or porcelain insulators. However, engineering plastics not suited to outdoor insulator because it isn't hydrophobic. Therefore, to over come these critical problems, we improve the surface insulation characteristics of engineering plastic by coating micro-, nano- size inorganic fillers added to RTV-SIR(Room temperature vulcanized-silicone rubber) at this plastic surface. The effect is analyzed through salt-fog test, tracking test. In conclusion, the engineering plastic coated RTV with micro-$Al_2O_3$20[phr], nano-Al(OH)3 1 ~ 3[phr] improved much better than the others.

  • PDF

Properties of PD Pulses accompanying with propagation of Bush-type tree in LDPE (LDPE에서 부시형 전기트리의 성장에 수반되는 부분방전 펄스의 특성)

  • 박영국;강성화;정수현;박철현;임기조
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.06a
    • /
    • pp.293-296
    • /
    • 1998
  • Surface electrical conduction in insulator is most important factor to assess the insulation performances of outdoor insulating materials. In this paper, contamination performance of the widely used materials for outdoor insulator - porcelain, EPDM, Silicone rubber - were discussed by measuring properties of average leakage current and scintillation discharge pulses under artificial contamination conditions. The artificial contaminations used were deionized distilled water fog, 0.5wt% NaCl salt fog of light pollution and 2wt% NaCl salt fog of medium pollution. The average leakage current was appeared linearly with applied voltage at dry and clean surface condition. The magnitude of leakage current was almost same at different kinds of samples. In case of deionized distilled water fog, the characteristics of leakage current and applied voltage was most different to that in case of dry and clean condition. In case of salt fog pollution condition, The leakage current was increased above critical voltage. The scintillation discharges were also activated at the level. the leakage current and scintillation discharges were increased with increasing pollution degree. The resistance to pollution properties of silicone rubber appeared excellent among them.

  • PDF

A Random Forest Model Based Pollution Severity Classification Scheme of High Voltage Transmission Line Insulators

  • Kannan, K.;Shivakumar, R.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.4
    • /
    • pp.951-960
    • /
    • 2016
  • Tower insulators in electric power transmission network play a crucial role in preserving the reliability of the system. Electrical utilities frequently face the problem of flashover of insulators due to pollution deposition on their surface. Several research works based on leakage current (LC) measurement has been already carried out in developing diagnostic techniques for these insulators. Since the LC signal is highly intermittent in nature, estimation of pollution severity based on LC signal measurement over a short period of time will not produce accurate results. Reports on the measurement and analysis of LC signals over a long period of time is scanty. This paper attempts to use Random Forest (RF) classifier, which produces accurate results on large data bases, to analyze the pollution severity of high voltage tower insulators. Leakage current characteristics over a long period of time were measured in the laboratory on porcelain insulator. Pollution experiments were conducted at 11 kV AC voltage. Time domain analysis and wavelet transform technique were used to extract both basic features and histogram features of the LC signal. RF model was trained and tested with a variety of LC signals measured over a lengthy period of time and it is noticed that the proposed RF model based pollution severity classifier is efficient and will be helpful to electrical utilities for real time implementation.

Effects of Non-uniform Pollution on the AC Flashover Performance of Suspension Insulators

  • Zhijin, Zhang;Jiayao, Zhao;Donghong, Wei;Xingliang, Jiang
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.4
    • /
    • pp.961-968
    • /
    • 2016
  • The non-uniform distribution of contamination on insulator surface has appreciable effects on flashover voltage, and corresponding researches are valuable for the better selection of outdoor insulation. In this paper, two typical types of porcelain and glass insulators which are widely used in ac lines were taken as the research subjects, and their corrections of AC flashover voltage under non-uniform pollution were studied. Besides, their flashover characteristics under different ratio (T/B) of top to bottom surface salt deposit density (SDD) were investigated, including the analysis of flashover voltage, surface pollution layer conductivity and critical leakage current. Test results gave the modified formulas for predicting flashover voltage of the two samples, which can be directly applied in the transmission line design. Also, the analysis delivered that, the basic reason why the flashover voltage increases with the decrease of T/B, is due to the decrease of equivalent surface conductivity of the whole surface and the decrease of critical leakage current. This research will be of certain value in providing references for outdoor insulation selection, as well as in proposing more information for revealing pollution flashover mechanism.

Bending strength of GFRP for Insulator according to Winding Angle (전기절연물용 GFRP의 winding 각도에 따른 굽힘강도)

  • Park, Hoy-Yul;Kang, Dong-Pil;Ahn, Myeong-Sang;Lee, Tae-Joo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07a
    • /
    • pp.429-432
    • /
    • 2004
  • The demand for electric power keeps growing, and tends to be more effective. Polymer insulators have been manufactured for almost twenty years and the excellent insulation performance of polymer insulators is attractive. Polymeric materials are now widely used as a replacement for inorganic materials such as porcelain or glass for the outdoor insulation of high voltage insulation. GFRP has been used widely as a core materials for polymer insulators. This paper reports the mechanical properties of GFRP for insulators. The bending strength was simulated and evaluated according to the winding angle. The fiber orientation in GFRP has a great effect on the strength of GFRP because the strength of GFRP mainly depends on the strength of fiber. Results of simulated and evaluated strength of GFRP were compared each other. The simulated strength of GFRP rod was different from the evaluated strength. It was caused that the shear stress had a great effect on the strength of GFRP although the stress of parallel direction of GFRP was much higher.

  • PDF