• Title/Summary/Keyword: Polymer surge arrester

Search Result 16, Processing Time 0.021 seconds

Temperature and Leakage Current Characteristics with Structure of Polymeric Surge Arresters (폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성)

  • Cho, Han-Goo;Lee, Un-Yong;Kim, Ha-Na
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.513-514
    • /
    • 2006
  • This paper presents the temperature characteristics with the structure of 18 kV surge arresters for distribution system. Three types of polymer arrester were fabricated and a ceramic arrester was also prepared to investigate. Below $100^{\circ}C$, three types of polymeric arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, the polymeric arresters whose module was injected into polymeric housing with the grease exhibited the highest leakage current. In contrary, the arresters being manufactured by directly injecting silicone rubber onto arrester module exhibited the lowest leakage current. The rapid rising of leakage current of the polymeric arresters with the grease at $120^{\circ}C$ was because of the deterioration of the insulation characteristics of the grease between the FRP module and the silicone housing. All polymeric arresters exhibited the same surface temperature characteristics but the ceramic arresters was slower than the polymer arrester in heat emission despite the lowest leakage current. It was thought that the air layer between ZnO varistor blocks and the ceramic housing prevented the heat emission.

  • PDF

Characteristic Analysis of Gapped Surge Arresters for D.C. Railway Line (직류 전차선로용 공극형 피뢰기의 특성 분석)

  • 조한구;한세원;윤한수;천종욱
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.07a
    • /
    • pp.485-488
    • /
    • 2001
  • This paper provides the result of analysis of the structure and I-V characteristics of D.C. 1500 V surge arresters which were installed in railway line currently. As Porcelain housed surge arresters have unstable elements such as exploding and dispersion, so it is thought that the system is protected more stably with replacement of polymer housing. The adoption of gap mitigates the voltage stress which is degradation factor of surge arresters and the research is needed to enhance the life characteristic in additive and manufacturing process. Therefore, it is thought that the research should be continued to develop homemade the surge arresters for D.C. railway line as well as transmission line.

  • PDF

Sealing Integrity of polymeric ZnO Surge Arresters (고분자 피뢰기의 기밀특성에 관한 연구)

  • Liang, He-Jin;Han, Se-Won;Cho, Han-Goo;Kim, In-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1997.11a
    • /
    • pp.258-261
    • /
    • 1997
  • The sealing integrity is related to the safe operation of arrester the prime failure reason of porcelain housed arresters is moisture ingress. To be a meaningful tests a polymer arrester sealing test must be a realistic acceleration of field service. We think the test should be an accelerating course of actual temperatures, the enduring property to mechanical load and temperatures should be considered together. A union test method consisting of the thermal mechanical test and thermal cycling test is proposed to test the sealing integrity of polymeric arresters, which uses dielectric loss, leakage current 1mA DC voltage and partial discharge as the diagnostic techniques, and the test results were presented. The comparison states that the TMTCUT method is suitable fur the test of sealing integrity of polymeric arresters. .

  • PDF

Development of Longtime Reliability Assessment Method of Polymer Housed Distribution Surge Arresters using Accelerated Aging Test (가속열화시험을 이용한 배전용 폴리머피뢰기의 장기신뢰성 평가기법 개발)

  • Kim, Ju-Yong;Song, Il-Keun;Moon, Jae-Duk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.10
    • /
    • pp.141-150
    • /
    • 2006
  • In this study we developed accelerated aging test cycle and equipment which can simulate domestic weather condition. And we proposed long term reliability assessment method for polymer housed distribution surge arresters. We carried out electrical and chemical analysis of the arresters which are used for accelerated aging test and outdoor exposure test. Through the analysis we verified the capability of the proposed method and we presented characteristic data for maintenance of domestic arresters.

The Effect of Contaminants on Tracking Aging in Polymer Insulating Materials (고분자 절연재료의 트랙킹 열화에 미치는 오손액의 영향)

  • 조한구;박용관
    • Electrical & Electronic Materials
    • /
    • v.10 no.8
    • /
    • pp.770-777
    • /
    • 1997
  • Some polymer materials including epoxy resin are being instead of porcelain for outdoor insulating materials such as insulators bushings cable terminators and surge arrester housing. And the largest problem to be overcomed is the tracking and erosion of the outdoor polymer material brought about by dry band arcing during prolonged exposure to contaminations. In this paper the effect of surface tension wettability flow rate of contaminants with varying surfactant content and frequency of applied voltage on the tracking breakdown of epoxy insulating materials were investigated. As the flow rate of contaminant is increased the surface resistivity is decreased and the leakage current is increased the time to tracking breakdown is decreased. It is found that time to tracking breakdown depends on the surface tension of contaminant that is difference of wettability. And as the frequency of applied voltage is increased time to tracking breakdown decreased.

  • PDF

A Study on the Submergence Test of the Distribution Polymer Surge Arrester (침수시험에 의한 비전용 폴리머피뢰기의 특성연구)

  • Kim, Ju-Yong;Kwon, Tae-Ho;Song, Il-Keun;Lee, Jae-Bong;Kim, Dong-Myung;Jeong, Yeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.104-106
    • /
    • 2003
  • 본 논문은 이상전압으로부터 배전선로 및 전력기기를 보호하기 위해 사용되는 폴리머피뢰기에 대해 침수 시험을 실시하여 침수 전후 폴리머피뢰기의 특성변화를 평가하였다. 침수 시험은 수온 95[$^{\circ}C$]에서 20일 동안 실시하였다. 침수 시험 전후 폴리머피뢰기의 특성분석은 푸리에변환 적외선분광기(FTR : fourier transform infrared spectrophotometer), 유전열분석(DETA : dielectric thermal analyzer), 발수성 측정, 절연저항 측정, 누설전류 측정, 동작개시전압 측정 둥으로 연구 하였다. 이를 통해 침수시험의 열화 효과에 대해 검토하였다.

  • PDF