• Title/Summary/Keyword: Partial insulation

Search Result 462, Processing Time 0.024 seconds

Partial Discharge Properties of High Voltage Motor Stator Insulation using Partial Discharge Analyzer (PDA를 이용한 고압전동기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong;Lee, Sang-Kil
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05c
    • /
    • pp.225-228
    • /
    • 2001
  • Partial discharge(PD) testing for different capacitive couplers was performed on a 6.6kV, 448kW pulverizer motor. The motor has been in service for twenty years. PD tests were measured using digital partial discharge detector(DPDD) and partial discharge analyzer(PDA), respectively. PDA is used to in the motor stator insulation, which three 80pF or three 500pF epoxy-mica couplers were installed, one per phase. The 500pF couplers did detect more normalized quantity number(NQN) than the 80pF couplers. DPDD and PDA showed that PD and NQN magnitudes increased with increase of ac voltage. Internal discharge was discovered in the motor stator insulation. DPDD and PDA test results are in accordance with the pattern and magnitude of PD.

  • PDF

Development of On-Line Partial Discharge Monitoring Techniques for Stator Winding of High-Voltage Motors (고압 전동기 고정자 권선의 활선 부분방전 모니터링 기술개발)

  • Hwang, Don-Ha;Lee, Joo-Hoon;Kang, Dong-Sik;Kim, Yong-Joo;Lee, Jae-Young;Shin, Byoung-Chol
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.43-46
    • /
    • 2004
  • Recently many research activities on the diagnosis of stator winding insulation of high-voltage motors have been reported. Most of them utilize a trend analysis of partial discharges. In this paper, a novel on-line monitoring system for an insulation diagnosis is proposed. This system displays magnitude and phase angle distribution of partial discharge. The partial discharge activities can be interpreted more precisely by these techniques.

  • PDF

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

A Study on the Insulation Characteristics for Stator Windings of IGBT PWM Inverter-Fed Induction Motors

  • Hwang, Don-Ha;Kang, Dong-Sik;Kim, Yong-Joo;Lim, Tae-Hoon;Bae Sung-Woo;Kim Dong-Hee;Ro Chae-Gyun
    • Journal of Power Electronics
    • /
    • v.3 no.3
    • /
    • pp.159-166
    • /
    • 2003
  • The winding insulation of low-voltage induction motors in adjustable-speed drive system with voltage-fed Inverters is substantially stressed due to the uneven voltage distribution and excessive voltage stress (dv/dt), which result in the premature insulation breakdown In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, discharge inception voltage, AC current, and dissipation factor tests Also, insulation breakdown tests by high voltage pulses are performed, and the corresponding breakdown voltages obtained.

A Study on the Insulation Diagnosis to measure Radiated Electromagnetic Waves with Partial Discharge Propagation at being of Conductive Particle in model GIS (모의 GIS 내부에 도전성 이물질 존재시 부분방전 진전에 따른 전자파 측정에 의한 절연진단연구)

  • Park, Kwang-Seo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.1
    • /
    • pp.157-164
    • /
    • 2008
  • Partial discharge were simulated by conductive particle which could be easy accumulated charge and concentrated electric field in the model GIS. Radiated electromagnetic waves were measured and analyzed by using spectrum analyzer and antenna ($30{\sim}2000[MHz]$) for measurement of EMI EMC in accordance with occurrence and propagation of partial discharge. This paper suggested the other method of detecting and estimating of partial discharge for insulation diagnosis of GIS being conductive particle by measurement and analysis of radiated electromagnetic waves. From results of this study, it was confirmed that if the suggested method should be used for the diagnosis of insulation in the model GIS being conductive particle, detecting partial discharge and estimating discharge propagation will be possible.

Characteristics of Radiated Electromagnetic Waves with Partial Discharge Propagation in Model GIS Being Insulation Particle (모의 GIS 내부에 유전체 파티클 존재시 부분방전 진전에 따른 방사전자파의 특성)

  • Park, Kwang-Seo;Kim, Lee-Kook;Kim, Jong-Wan;Ju, Je-Hyun;Song, Hyun-Jig;Lee, Kwang-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.2
    • /
    • pp.69-76
    • /
    • 2005
  • In this paper partial discharge were simulated by insulation particle which could be easy accumulated charge and concentrated electric field in the model GIS. In this times this paper measured and analyzed the radiated electromagnetic waves by using spectrum analyzer and antenna$(30\~2000(MHz))$ for measurement of$ EMI{\cdot}EMC$ in accordance with occurrence and propagation of partial discharge. This paper suggested the other method of detecting and estimating of partial discharge for insulation diagnosis of GIS being insulation particle by measurement and analysis of radiated electromagnetic waves. From results of this study, it was confirmed that if the suggested method should be used for the diagnosis of insulation in the model GIS being insulation particle, detecting partial discharge and estimating discharge propagation will be possible.

Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings (13[kV]급 수력발전기 고정자 권선의 운전 및 정지 중 진단시험 현장적용 평가 및 분석)

  • Chang, Jeong-Ho;Lee, Dong-Keun;Lee, Heung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.11
    • /
    • pp.73-82
    • /
    • 2011
  • The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line). The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, ${\Delta}tan{\delta}$ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings.

Analysis of Parameters on Partial Discharges from Insulation Defects of used Hydro Generator Stator Windings (수력발전기 고정자 노후권선의 모의결함 시편에 대한 부분방전 파라미터 변화 분석)

  • Oh, Bong-Keun;Kim, Hyun-Il;Kang, Seong-Hwa;Lim, Kee-Joe
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.7
    • /
    • pp.645-649
    • /
    • 2007
  • Partial discharge(PD) test for simulated insulation defects of used hydro generator stator winding was conducted to analyze the PD Parameters. Simulated insulation defects are classified by 5 types corona, slot, internal, multi and aging defect. Phase resolved partial discharge, statistical parameter (skewness, kurtosis), PD magnitude as a function of the test voltage(Q-V curve) and PD magnitude change under test voltage for 2 minutes are used as PD parameters. The analysis of PD parameters by 4 types are proved to be useful methods. In particular, PD parameter characteristics of aging defect could help to assess the aging condition of stator winding because aging defect has more weak insulation strength than other insulation defects : PD distribution is wide and flat, PD rises rapidly near $0^{\circ}\;and\;180^{\circ}$ and Q-V curve rises sharply and then gently drops.

Characteristics of Insulation Aging in Large Generator Stator Windings (대용량 발전기 고정자 권선의 절연열화 특성)

  • Kim, Hee-Dong;Lee, Young-Jun;Ju, Young-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.7
    • /
    • pp.1375-1379
    • /
    • 2009
  • Insulation tests have been performed on two generator stator bars under accelerated aging under a laboratory environment. Electrical stress was applied to stator bar No.1, and electrical and thermal stresses were applied to stator bar No.2. Nondestructive stator insulation tests including the ac current, dissipation factor($tan{\delta}$), and partial discharge tests have been performed on both bars as the bars were aged for 11460 hours. Experimental test results show that ${\Delta}I$, ${\Delta}tan{\delta}$, and partial discharge of No. 1 and No.2 stator bars increased with increased in aging time. It has been concluded from the test that the stator insulation of the two generators are in good condition.

Propagation Characteristics of Acoustic Signals Produced by Partial Discharges in an Insulation Oil (유중 부분방전 음향신호의 전달특성)

  • Park, Dae-Won;Cha, Sang-Wook;Cho, Hyang-Eun;Kim, Dong-Geon;Kil, Gyung-Suk
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2011.06a
    • /
    • pp.188-188
    • /
    • 2011
  • This paper describes the propagation characteristics of acoustic signals as a function of distance from the location of partial discharge(PD) occurrence to analyze correlation between discharge magnitude and acoustic signal in insulation oil. We fabricated a decoupler and an amplifier to measure acoustic signals produced by PD. The amplifier has the gain of 40 dB and the frequency bandwidth of 1.6 kHz~1.6 MHz. After a comparative calibration by a standard pulse generator and a coupling capacitor, we analyzed the propagation characteristics of acoustic signals in insulation oil as a function of distance.

  • PDF