• Title/Summary/Keyword: Partial discharge tests

Search Result 100, Processing Time 0.025 seconds

Assessment of 23 kV Capacitive Coupler for On-line Partial Discharge Measurements

  • Jeong, J.Y.;Kang, D.S.;Sun, J.H.;Heo, J.C.;Park, C.H.
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.123-130
    • /
    • 2009
  • The partial discharge (PD) measurement is a very effective method to assess the winding insulation condition of high-voltage machines, since most of the insulation failure processes are directly or indirectly caused by PD. On-line PD measurements, which can detect insulation defects of winding in the early stages on rotating machines in operation, have been accepted as the most important technique. The epoxy mica capacitive coupler is currently and extensively used for on-line detection of PD pulses of high-voltage rotating machines. To evaluate the feasibility of developing a capacitive coupler that is easier to manufacture at a lower cost compared to epoxy mica couplers, a 100pF capacitive coupler made of ceramic material is designed, fabricated and tested for on-line PD measurements of 23 kV electrical machines. A series of electrical tests and accelerated aging tests are performed on the ceramic coupler to evaluate the performance requirements, long-term reliability and thermal stability for in field application. The test results show that the newly developed ceramic coupler provides equal and improved performance at a lower cost compared to epoxy mica couplers, and estimated voltage life is anticipated to surpass 100 years.

Partial Discharge Pattern Recognition of Cast Resin Current Transformers Using Radial Basis Function Neural Network

  • Chang, Wen-Yeau
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.1
    • /
    • pp.293-300
    • /
    • 2014
  • This paper proposes a novel pattern recognition approach based on the radial basis function (RBF) neural network for identifying insulation defects of high-voltage electrical apparatus arising from partial discharge (PD). Pattern recognition of PD is used for identifying defects causing the PD, such as internal discharge, external discharge, corona, etc. This information is vital for estimating the harmfulness of the discharge in the insulation. Since an insulation defect, such as one resulting from PD, would have a corresponding particular pattern, pattern recognition of PD is significant means to discriminate insulation conditions of high-voltage electrical apparatus. To verify the proposed approach, experiments were conducted to demonstrate the field-test PD pattern recognition of cast resin current transformer (CRCT) models. These tests used artificial defects created in order to produce the common PD activities of CRCTs by using feature vectors of field-test PD patterns. The significant features are extracted by using nonlinear principal component analysis (NLPCA) method. The experimental data are found to be in close agreement with the recognized data. The test results show that the proposed approach is efficient and reliable.

Implementation of an Inductively Coupled EM Probe System for PD Diagnosis

  • Kim, Hee-Dong;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.1
    • /
    • pp.111-118
    • /
    • 2011
  • In recent years, various types of partial discharge (PD) methods such as capacitive, inductive, electromagnetic, and acoustic coupling techniques have been developed for diagnosing rotating machines. An electromagnetic (EM) probe, which is an inductively coupled type of sensor, is required for detecting corona and internal discharges during off-line tests. In this study, a new technique for enhancing the measurement sensitivities for corona and internal discharge based on an EM inductive position sensor is proposed. An EM probe that winds wires around horseshoe-shaped and cylindershaped ferrites as helices is designed and optimized for the implementation of off-line PD monitoring of the stator winding of a rotating machine. The measurement system based on this design is implemented, and it is verified from the results of the experiment performed in this study that the probe provides similar performance as existing commercial products.

A Study on the PD Measurement System for Estimating Reliabilities of Low-voltage Electrical and Electronic Components (저압용 전기전자부품의 신뢰성 평가를 위한 부분방전 측정시스템에 관한 연구)

  • Seo, Hwang-Dong;Snog, Jae-Yong;Moon, Seung-Bo;Kil, Gyung-Suk;Kang, Dong-Sik;Hwang, Don-Ha
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.321-322
    • /
    • 2005
  • In this paper, we dealt with a partial discharge(PD) measurement system that has been accepted as an effective and non-destructive technique for estimating reliabilities of low-voltage electrical and electronic components. Calibration tests on laboratory set-up have shown that the PD measurement system has a stable sensitivity of 37.6 mv/pC. In an application test on photo coupler, we could detect 0.1 pC level of partial discharge at the applied voltage of AC 520 $V_{peak}$.

  • PDF

Considerations on the Long-term Reliability of On-line Partial Discharge Ceramic Sensor for Thermal Power Generators and its Demonstration in the Field

  • Sun, Jong-Ho;Youn, Young-Woo;Hwang, Don-Ha;Kang, Dong-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.1
    • /
    • pp.103-108
    • /
    • 2012
  • The present study describes the considerations on the long-term reliability of the on-line partial discharge (PD) ceramic sensor for thermal power generators. Voltage acceleration aging tests were carried out under continuous and impulsive thermal aging at more than $100^{\circ}C$, considering the practical service environment. Experimental results show that the sensors have a life that could last for more than 100 years, excellent dielectric characteristics, and insulation strength. In addition, the ceramic on-line PD sensors were installed in a thermal power generator in Korea for demonstration. The results of the PD calibration and test voltage application prove that the on-line ceramic sensors have satisfactory performances for on-line PD measurement.

The Application Technique on AI and Statistical Analysis of 3d-PD (3d-PD의 통계적 고찰과 신경망 응용기술)

  • Lim, Jang-Seob;Park, Yong-Sik;Choi, Byoung-Ha;Han, Sok-Kyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05a
    • /
    • pp.66-70
    • /
    • 2001
  • The partial discharge testing is widely used in diagnostic measuring technology because it gives low stress to power equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power system that requires on-line/on-site diagnosis. But partial discharges have very complex characteristics of discharge pattern, so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated system is manufactured and HFPD occurred from those simulator is measured with broad-band antenna in real time, the degradation grade of system is analyzed through produced patterns in simulated target according to the AI/statistics processing.

  • PDF

Design and Fabrication of an Ultra-low Partial Discharge Measurement System (극미소 부분방전 측정시스템의 설계 및 제작)

  • Seo, Hwang-Dong;Song, Jae-Yong;Moon, Seung-Bo;Kil, Gyung-Suk;Kwon, Jang-Woo
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • v.9 no.2
    • /
    • pp.208-211
    • /
    • 2005
  • This paper presents an ultra-low partial discharge(PD) measurement system that has been accepted as a non-destructive method to estimate electrical insulation of low-voltage electric devices. The PD measurement system is composed of a coupling network, a low noise amplifier, and associated electronics. A shielding box is used to make a better condition against electromagnetic interference. A low cut-off frequency of the coupling network was 1MHz(-3 dB). Calibration tests on laboratory set-up have shown that the PD measurement system has a stable sensitivity of 11.4mV/pC. In an application experiment on a low-voltage induction motor(5HP), we could detect 0.77pC level of partial discharge pulse at the applied voltage of AC 664 V$_{peak}$.

  • PDF

Analysis of Insulation Characteristics of Low-Voltage Induction Motors Fed by Pulse-Controlled Inverters (인버터 구동형 저압 유동전동기의 절연특성 분석)

  • 박도영
    • Proceedings of the KIPE Conference
    • /
    • 2000.07a
    • /
    • pp.195-198
    • /
    • 2000
  • In this paper the insulation characteristics test results of 25 low-voltage induction motors($3\phi$, 5HP, 380V) are presented. Five different types of insulation techniques are applied to 25 motors. The maximum partial discharge (PD) magnitude ($\textrm{Q}_{m}$) discharge inception voltage (DIV) dissipation factor tip-up ($\Delta$tan$\delta$) and rate of change in AC current($\Delta$I) are measured by PD and AC current tests. Also the insulation breakdown tests by high voltage pulse are performed and the corresponding breakdown voltage are obtained.

  • PDF

Partial Discharge Phenomena with $SF_{6}$ Gas Pressures in Insulation Consisted of Insulation Paper and $SF_{6}$ Gas(II) ($SF_{6}$가스와 절연지의 절연계에서 가스압력에 따른 부분방전 현상(II))

  • Seon, Jong-Ho;Kim, Gwang-Hwa;Park, Jeong-Hu;Jo, Jeong-Su
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.9
    • /
    • pp.430-435
    • /
    • 2002
  • The $SF_{6}$ gas insulated power equipments have the insulation systems which are composed of $SF_{6}$ gas and insulation paper. It is repored that their insulation abilities are influenced by the $SF_{6}$ gas gaps in those insulation systems and gas pressures. This paper describes partial discharge phenomena with $SF_{6}$ gas pressures in insulation system of $SF_{6}$ gas-insulation paper Specimens of $SF_{6}$ gas-insulation paper were prepared and aramid paper was used as insulation paper. Partial discharge inception voltages(PDIV) and breakdown voltages for the existence of $SF_{6}$ gas gaps were measured by short term tests with gas pressures. Also, average PD quantities and pulse counts, life times of each specimens were calculated from the results of long term aging tests with gas pressures. It was found that the $SF_{6}$ gas gaps decrease increasing rates of PDIV and brealdown voltages according to gas pressure increase and the insulation breakdown caused by the smaller PD quantities than 1[pC] at the high gas pressure of 300kPa is due to the increase of energy density with increase of gas pressure.

A Study on the Partial Discharge Wave Propagation along Stator Winding (회전기 권선의 펄스 전송특성 연구)

  • Kang, Dong-Sik;Sim, Woo-Yong;Hwang, Don-Ha;Kim, Yong-Joo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07b
    • /
    • pp.738-740
    • /
    • 2003
  • A lot of R&D on the diagnosis of stator winding insulation for large rotating machines has been carried out since the 1970s. The on-line partial discharge measurement has proved to be an effective technique in the evaluation of the state of stator insulation in high voltage rotating machines. It is well known that if the discharge pulses propagate through the winding conductor, they are attenuated and delayed. In the present study, to investigate the attenuation and the time delay of discharge pulses through the winding conductor, a series of tests were conducted using a model coils and slot. Thus it could be concluded that while the high frequency pulse propagates in radiation or end-winding coupling modes, the low frequency one does in a series mode through the coil conductor.

  • PDF