• Title/Summary/Keyword: Partial discharge tests

Search Result 100, Processing Time 0.026 seconds

Analysis of the Temperature Influence on Insulation Characteristics in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 온도변화에 따른 절연특성 분석)

  • Kong, Tae-Sik;Ju, Young-Ho;Kim, Hee-Dong;Park, Tae-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.10
    • /
    • pp.786-790
    • /
    • 2012
  • A variety of diagnostic tests are widely applied in the field in industry to evaluate the condition of high voltage (HV) motor stator insulation. In this paper, the influence of temperature on the stator insulation diagnostic tests such as the insulation resistance, AC current, dissipation factor, and partial discharge measurements are studied and reported. The tests are performed with the HV motor stator winding temperature set between $40^{\circ}C$ to $80^{\circ}C$ in $10^{\circ}C$ intervals. It is shown that the AC current, dissipation factor, and partial discharge magnitude steadily increase with temperature, which suggests that temperature must be taken into account in the interpretation of the test results.

Partial Discharge Measurements of High Voltage Rotating Machine Stator Windings (고압회전기 고정자 권선의 부분방전 측정)

  • Kim, Hee-Dong;Lee, Young-Jun;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1828-1830
    • /
    • 2003
  • Partial discharge(PD) tests are used to evaluate the insulation condition of stator windings in two 4.16kV and three 6.6kV motors. These tests were conducted using a conventional partial discharge detector(PDD) and turbine generator analyzer(TGA). Off-line PD measurements were performed on five high voltage motors. PD magnitudes ranged from 1000 pC to 5400 pC at the normal line-to-ground voltage. Five high voltage motors have been equipped with 80pF epoxy-mica coupler on the motor terminal box. The PD pulse from sensors were measured with the TGA instrument. TGA summarizes each plot with two Quantities such as the peak PD magnitude(Qm) and the total PD activity(NQN). The defect mechanisms of high voltage motor can be associated with PD patterns such as internal, slot and conductor surface discharges. The PDD and TGA test results of No. 4 motor showed that internal discharge was detected in voids of the groundwall insulation.

  • PDF

Characteristics of Insulation Failure in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 절연파괴 특성)

  • Kim, Hee-Dong;Kim, Kyeong-Yeol;Park, Deok-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.124-124
    • /
    • 2010
  • Diagnostic tests were performed on six high voltage motors. These tests included ac current, dissipation factor(tan6) and partial discharge(PD) magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 and No.2 motors(4.16 kV) failed near rated voltage of 12.3 kV and 14.2 kV, respectively. The breakdown voltage of No.3 and No.4 motors(6.6 kV) was 17.6 kV and 17.8 kV, respectively. These motors are higher that expected for good quality coils in 6.6 kV class motors.

  • PDF

Application of the Ultrasonic Detection System for the Power Transformer (전력용 변압기 초음파 측정시스템 적용)

  • Kweon, Dong-Jin;Koo, Kyo-Sun;Kim, Jae-Chul
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.12
    • /
    • pp.553-557
    • /
    • 2005
  • This paper describes the application results of an ultrasonic detection system for the power transformer. The ultrasonic detection system with 6 sensors was applied to detect partial discharge in a 154kV transformer with a dangerous levels of $C_{2}H_{2},\;C_{2}H_4$ and $CH_{4}$ gases. The ultrasonic detection tests were carried out 2 times, respectively, to confirm the existence and location of the partial discharge in the transformer. As a result of internal inspection, the arc trace between the pressure ring and core due to the partial discharge was found at the estimated position based on the amplitude and arriving time of the ultrasonic signals. Therefore, it was verified that the ultrasonic detection system is effective as a preventive diagnosis method for the power transformer. Also, the reliability of the ultrasonic detection system in detecting partial discharges in the transformer was also confirmed. It is expected, therefore, that the ultrasonic detection system will have beneficial effects on applications and verifications in detecting partial discharges for the power transformer.

PD Measurement in oil with defects (결함별 절연유중 부분방전 측정 연구)

  • Sun, J.H.;Yi, S.H.;Kim, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.67-69
    • /
    • 2004
  • Since partial discharges in power transformers weaken their insulation performance the detection of partial discharge is very important for prevention of fatal incidents. This study describes use of electromagnetic coupler for measurement of partial discharge of transformers. Spiral antennas of which bandwidth is 0.5GHz to 3GHz were used as coupler and setup in chamber for partial discharge tests. Test results showed that outputamplitudes are increased with PD increase and frequencies of signal measured by these antennas are mostly distributed below about 800MHz.

  • PDF

Assessment of Insulation Condition in Gas Turbine Generator Stator Windings (가스터빈 발전기 고정자 권선의 절연상태 평가)

  • Kim, Hee-Dong;Yang, Gyu-Hyun;Ju, Young-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.8
    • /
    • pp.1423-1428
    • /
    • 2010
  • The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tan${\delta}$), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude($Q_m$) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and $Q_m$ values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.

A Study on the Insulation Characteristics for Stator Windings of IGBT PWM Inverter-Fed Induction Motors

  • Hwang, Don-Ha;Kang, Dong-Sik;Kim, Yong-Joo;Lim, Tae-Hoon;Bae Sung-Woo;Kim Dong-Hee;Ro Chae-Gyun
    • Journal of Power Electronics
    • /
    • v.3 no.3
    • /
    • pp.159-166
    • /
    • 2003
  • The winding insulation of low-voltage induction motors in adjustable-speed drive system with voltage-fed Inverters is substantially stressed due to the uneven voltage distribution and excessive voltage stress (dv/dt), which result in the premature insulation breakdown In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, discharge inception voltage, AC current, and dissipation factor tests Also, insulation breakdown tests by high voltage pulses are performed, and the corresponding breakdown voltages obtained.

Performance Verification and Improvement of UHF Sensor for the Increasement of the Partial Discharge Detection Reliability (부분방전검출 신뢰도 향상을 위한 UHF 센서개선 및 성능검증)

  • Kim, Won-Gyu;Kim, Min-Soo;Baek, Young-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.10
    • /
    • pp.1461-1466
    • /
    • 2014
  • GIS(Gas Insulated Switchgear) is important power apparatus which have strong dielectric strength, supply electric power and is a part of the power system. Most substation type is configured as GIS. Recently, because of continuous increasement of GIS demand resulted from high quality & big capacity of electric power, the necessity of the preventive & diagnosis system is being expanded gradually. GIS partial discharge occurred on the UHF band is detected effectively by the method to IEC 60270 that recommend to be able to detect the apparent minimum discharge, 5 pC. Additionally, the UHF sensor should be installed to detect PD signal if Partial discharge signal, 5 pC occur in every part of GIS. Currently PD diagnosis system applying UHF sensor for GIS with various voltage level like 154 kV, 345 kV, 765 kV have been operated. And it is necessary to measure and analyze insulation breakdown phenomenon of inside GIS exactly. In this paper, we proposed Fat-dipole patch UHF sensor that is developed and more sensitive, excellent wide-range characteristic than the exising UHF sensor. And we performed KERI (Korea Electrotechnology Research Institute) reference test, which showed the excellent result for the all tests.

Partial Discharge Tests for Traction Motor Using 1000 pF Couplers (1000 pF 커플러를 이용한 견인전동기 부분방전특성)

  • Ko, Byeong-Hun;Park, Hyun-June;Kwon, Sam-Young;Na, Hae-Kyung;Lee, Hyung-Woo
    • Proceedings of the KSR Conference
    • /
    • 2007.05a
    • /
    • pp.214-218
    • /
    • 2007
  • With the development of high speed railway, traction motors play a critical role in the operation of railway vehicle. This paper describes the use of 1000 pF coupler as a on-line partial discharge (PD) measurement for the assessment of railway traction motor. The PD tests are performed with developed PD analyzer and the 5 model coils such as thermal, electrical, mechanical and environmental aging respectively at various AC voltages. On-line PD tests using 1000 pF couplers show that PD patterns can be detected successfully at 2.3 kV.

  • PDF

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.