• Title/Summary/Keyword: Parallel flow cycle

Search Result 44, Processing Time 0.028 seconds

Performance Characteristics of Water-Chilling Heat Pump Using CO2 on the Variation of Secondary Fluid Conditions (2차 유체 조건 변화에 대한 CO2용 수냉식 열펌프의 성능 특성에 관한 연구)

  • Son, Chang-Hyo;Oh, Hoo-Kyu
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.31 no.5
    • /
    • pp.543-551
    • /
    • 2007
  • The performance characteristics of water-chilling heat pump using $CO_2$ with respect to variation of inlet temperature and mass flow rate of secondary fluid was investigated experimentally. An experimental apparatus is consisted of a compressor, a gas cooler, an expansion valve, an evaporator and a liquid receiver. All heat exchangers used in the test rig are counter-flow-type heat exchangers with concentric dual tubes, which ate made of copper. The gas cooler and the evaporator consist of 6 and 4 straight sections respectively arranged in parallel, each has 2.4 m length. The experimental results were summarized as the followings : As inlet temperature of secondary fluid in the gas cooler increases from $10^{\circ}C$ to $40^{\circ}C$, the compressor work, heating capacity and heating COP were varied to 37.8%, -13%, -35.9%, respectively. The heating capacity, compressor work, heating COP were turned into 23.3%, 6.42%, 13.1%, respectively when ass flow rate of secondary fluid in the evaporator increases from 70 g/s to 150 g/s. The above tendency is similar with performance variation with respect to temperature variation of secondary fluid in the conventional vapor compression cycle.

The Experimental Study on the Performance of Two-Phase Loop Thermosyphone System for Electronic Equipment Cooling (전자장비 냉각을 위한 2상 순환형 써모사이폰 시스템의 성능에 대한 실험적 연구)

  • Kang, In-Seak;Choi, Dong-Kyu;Kim, Taig-Young
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.28 no.4
    • /
    • pp.415-424
    • /
    • 2004
  • Cooling the electronic equipment is one of the major focal points of the design process and the key to successful product launch. The two-phase loop thermosyphone which is a good candidate among many available options was investigated fur cooling of the high power amplifiers. The system is composed of evaporator which contains 6 parallel cold plates, fan cooled condenser, gas-liquid separator, and interconnecting tubes. Experiments were performed for several refrigerant charging values, hs and as a experiment result, the optimum charging value fur this system was proposed. In order to optimize the system design, the operating cycle pressure and inlet/outlet temperatures of evaporator and condenser are measured and analyzed. The effect of the three parameters such as flow rate and temperature of condenser cooling air, and thermal load on the evaporator are investigated. The lower the operating pressure and the cycle temperatures are also better to prevent the leakage of the system. The system invesigated in this paper can be directly used for cooling of a real unmanned wireless communication station.

Characteristic analysis of air-cooled absorption refrigeration machine (공냉식 흡수식 냉동기의 특성 해석)

  • Kwon Oh-Kyung;Moon Choon-Geun;Yang Young-Myung;Yu Sun-Il;Yoon Jung-In
    • 한국가스학회:학술대회논문집
    • /
    • 1998.09a
    • /
    • pp.249-254
    • /
    • 1998
  • This paper describes the study of developing air-cooled absorption system which uses a new working solution instead of LiBr solution to improve the performance of system. The absorption chiller-heater considered was an air-cooled, double-effect, $H_2O/LiBr+HO(CH_2)_3$ system of parallel flow type. In this study, we found out the characteristic of new working solution through the cycle simulation and compared the result that of LiBr solution to evaluate. The new working fluid has a wider working range with $8\%$ higher crystallization limit at the saturated refrigerant pressure of 0.8kPa. The optimum designs and operating conditions of air-cooled absorption system were suggested based on this cycle simulation analysis. It was demonstrated that new working fluid substantially improves the performance of the absorption refrigeration machine and is expected to increase the COP by as much as $5\%$.

  • PDF

Optimization of valve events in a 4 cycle reciprocating engine using measured intake and exhaust port pressures (4사이클 왕복동식 엔진에 있어서 흡배기 변동압 측정치를 이용한 흡기효율 최적화 컴퓨터 시뮬레이션)

  • 오세종;진영욱;정재화
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.13 no.3
    • /
    • pp.500-507
    • /
    • 1989
  • The improvement of volumetric efficiency of air charging into combustion chamber is a primary requirement to obtain better mean effective pressure of an engine. Since parameters such as the air resistances in intake and exhaust flow passages, valve lift and valve timing influence greatly to the volumetric efficiency, it is very convenient and time saving if we can optimize these parameters by computation before we enter into long time fact finding engine tests. In this study we have developed a semi-empirical engine simulation program for the determinations of intake and exhaust valve timings, valve lifts, intake and exhaust port diameters in order to obtain highest volumetric efficiency. In this computation it requires only the measured variational pressures in intake and exhaust port. Using these variational pressures as an input data for our simulation program, we can calculate volumetric efficiency more accurately and can save computing time drastically. To confirm the validity of our simulation program we have made engine operation test in parallel and taken the experimental data. Comparing the computation result with the experimental data obtained through real engine test it has shown only the difference of 3%.

Evaluation of Energy Saving with Vector Control Inverter Driving Centrifugal Pump System (벡터 제어 인버터 구동 원심펌프시스템의 에너지 절감 평가)

  • Suh, Sang-Ho;Kim, Kyungwuk;Kim, Hyoung-Ho;Yoon, In Sik;Cho, Min-Tae
    • The KSFM Journal of Fluid Machinery
    • /
    • v.18 no.2
    • /
    • pp.67-72
    • /
    • 2015
  • The purpose of this study is to achieve energy saving effect of inverter driving multistage centrifugal pump. For determining the operation points in the pump system, the system curves should be obtained experimentally. To get the system curves, three pumps combined in parallel and one pump operated with different rotational speeds. But for variable speed pump system, energy saving rates can not be evaluated from operation efficiencies. That is why operation efficiencies, system curves, duty cycles, and input powers of the pump system were measured by the constructed experimental apparatus. The duty cycle segmented into different flow rates and weighting the average value for each segment by the interval time. The system was operated with two different periods. The mean duty cycles were collected from apartment and found that the system operated at 40% and at 50% or below capacity. Measured energy saving rate was 58.16%. Estimating method of energy saving rate could be more effective operation index than that of operation efficiency.

Experimental Study on the Performance Characteristics of a CO2 Air-conditioning System for Vehicles (자동차용 CO2 에어컨 시스템의 성능 특성에 관한 실험적 연구)

  • Lee, Daewoong
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.23 no.1
    • /
    • pp.18-24
    • /
    • 2015
  • In this study, a $CO_2$ air-conditioning system was investigated with different types of electrically driven compressors, parallel flow type gas cooler, four-pass type evaporator, internal heat exchanger integrated with accumulator, and electric expansion valve. The experimental study was conducted under various operating conditions (ie., different rotational compressor speeds, air inlet temperatures and air velocity coming into heat exchangers). The experimental results showed the cooling capacity was 3.5kW at $35^{\circ}C$ ambient temperature when the vehicle was idle (ie., the worst condition for cooling off the gas cooler). In terms of performance effect of the compressor, the e-RP model had a slightly better cooling capacity and coefficient of performance than the e-GR model under the same test conditions. An experimental equation for optimum cooling-performance control was also suggested based on the results. A high-pressure control algorithm for the super critical cycle was determined to achieve both maximum cooling performance and efficient energy consumption. The results from the experimental equation coincided with those of previous experimental studies.

A Study of th Optimum of closed ${CO}_{2}$ Gas Turbine Process for Nuclear Energy Power Plant(II) - For Optimal Design of Heat Exchanger- (원자력 발전소에 대한 밀폐 ${CO}_{2}$ 가스터빈 프로세스의 최적화 연구 (II) -열교환기의 설계에 관하여 -)

  • 이찬규;이종원
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.14 no.1
    • /
    • pp.251-258
    • /
    • 1990
  • Optimal design of heat exchanger for closed CO$_{2}$ gas turbine plant of three processes selected from the result of cycle analysis have been discussed previously paper(I) has been carried out under specified inlet and outlet conditions. Independent variables such as number of parallel connection, tube diameter, shell side and tube side pressure loss as well as dependent variables such as shell diameter, number of tubes, number of serial connections were all characterized according to the standardization or so. Search method was used to construct a computer simulation together with the calculation of heat transfer rate by logarithmic mean temperature difference method. Strength analysis of major parts was carried to examine their dimensions satisfying heat transfer and pressure loss requirements.

Performance Analysis of New Working Solution for Absorption Refrigeration Machine using Treated Sewage (하수처리수이용 신용액 흡수식 냉동기의 성능해석)

  • 권오경;유선일;윤정인
    • Journal of Energy Engineering
    • /
    • v.7 no.2
    • /
    • pp.231-240
    • /
    • 1998
  • The global environmental problems such as CFC, energy losses in heat recovery system as well as summer peak time power demands, the development of high efficiency absorption refrigeration systems is one of the most promising method in this problems. The absorption refrigeration system to utilize treated sewage is available for environmental protection and energy conservation. Simulation analysis on the double-effect absorption refrigeration cucles with parallel or series flow type has been performed. LiBr+LiI+LiCl+LiNO$_3$ solution was selected as the new working fluid. The main purpose of this study is evaluating the possibilities of effective utilization of treated sewage as a cooling water for the absorber and condenser. The other purpose of the present study is to determine the optimum designs and operating conditions based on the operating constraints and the coefficient of performance in the parallel or series flow type. In this study, we found out the characteristic of new working solution through the cycle simulation and compared LiBr solution to evaluate. The absorption refrigeration machine using the new working fluid was obtained better results COP rise and compactness of system by comparison with LiBr solution.

  • PDF

A Study on Development of a Cognitive Process Simulator Based on Model Human Processor (모델휴먼프로세서를 활용한 인지과정 시뮬레이터 구축에 관한 연구)

  • 이동하;나윤균
    • Journal of the Korean Society of Safety
    • /
    • v.13 no.4
    • /
    • pp.230-239
    • /
    • 1998
  • Though limited, Model Human Processor (MHP) has been used to explain the complex users' behaviors during human-computer interactions in a simplified manner. MHP consists of perceptual, cognitive and motor systems, each with processors and memories interacting with each other in serial or parallel mode. The important parameters of memory include the storage capacity, the decay time, and the code type of a memorized item. The important parameter of a processor is the cycle time. Using these features of the model, this study developed a computerized cognitive process simulator to predict the cognitive process time of a class match task process. An experimental validity test result showed that the mean prediction time for cognitive process of the class match task simulated 50 times by the simulator was consistent with the mean cognitive process time of the same task performed by 37 subjects. Animation of the data flow during the class match task simulation will help understand the invisible human cognitive process.

  • PDF

Analysis of Heat Transfer Characteristics of Internal Heat Exchanger for $CO_2$ Refrigerator using the Hardy-Cross Method (Hardy-Cross법을 이용한 $CO_2$ 냉동기용 내부열교환기의 열전달 특성 연구)

  • Kang Hee-Dong;Kim Ook Joong;Seo Tae-Beom
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.1
    • /
    • pp.1-7
    • /
    • 2005
  • The heat transfer characteristics of an internal heat exchanger for $CO_2$ refrigeration cycle are numerically investigated. The numerical model is verified using the published experimental results for the concentric tube type internal heat exchanger. The Hardy-Cross Method gives very good agreement between the calculation and experimental results on the heat transfer rates and exit temperatures. Also, appropriate combination of heat transfer correlations is found. The operating parameters of the heat exchanger are calculated at transcritical region of $CO_2.$ The heat transfer rate of the counter flow type heat exchanger shows the $32\%$ greater than that of the parallel flow type heat exchanger. The increase of heat exchanger length enhances the heat transfer rate. The thermodynamic characteristics and heat transfer coefficient of $CO_2$ in the internal heat exchanger are estimated.