• 제목/요약/키워드: PD (Partial Discharge)

검색결과 501건 처리시간 0.025초

13 kV급 수력발전기 고정자 권선용 On-line 부분방전 측정 시스템 개발 및 현장적용 평가 (Development and Site Evaluation of the On-line Partial Discharge Measuring System on the 13 kV Class Stator Windings for Hydro Generator)

  • 선종호;황돈하;윤영호;신병철;오봉근;강동식
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권4호
    • /
    • pp.189-198
    • /
    • 2006
  • In order to improve the reliability of stator windings for hydro generators, it is necessary to detect the defective point and life assessment of the high voltage windings. Especially the on-line partial discharge (PD) test provides the ability to monitor effects, such as slot discharge, internal discharge, and end-winding discharge without interrupting generators, this method has been proven the major testing technology in high voltage rotating machines nowadays. The purpose of this paper is to describe the method of the on-line PD measurement on stator windings for hydro-generator with 13 [kV] class ceramic coupler (CC), on-line PD measuring system, terminal box, and index parameters. Also, the developed PD measuring system and 13 [kV] class CC were installed Daechung-dam generator #2. It was found that this installed sensor and system had good electrical characteristics to detect PD activity during the operating condition with its detection frequency band is between several and several tens MHz.

모의된 GIS에서 발생하는 부분방전에 관한 연구 (The Simulated study of different partial discharge sources in GIS)

  • 강대용;오광영;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1737-1739
    • /
    • 1998
  • The paper presents experimental results of Partial Discharge(PD) in Gas Insulated Switchgear(GIS), obtained using a computer-aided PD measurement system. Different discharge sources are simulated and identified. These included internal, interface, surface and protrusion. For internal discharge, it showed symmetrical discharge type between positive and negative cycle. Interface discharge showed smaller number and higher peak than internal discharge but symmetrical discharge as well. For surface discharge, it showed small number and high peak in positive half cycle but large number and low peak in negative half cycle. For protrusion discharge, small number and high peak of discharge were shown only in negative half cycle.

  • PDF

A Study on the Pattern Recognition Rate of Partial Discharge in GIS using an Artificial Neural Network

  • Kang Yoon-Sik;Lee Chang-Joon;Kang Won-Jong;Lee Hee-Cheol;Park Jong-Wha
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권2호
    • /
    • pp.63-66
    • /
    • 2005
  • This paper describes analysis and pattern recognition techniques for Partial Discharge(PD) signals in Gas Insulated Switchgears (GIS). Detection of PD signals is one of the most important factors in the predictive maintenance of GIS. One of the methods of detection is electro magnetic wave detection within the Ultra High Frequency (UHF) band (300MHz $\~$ 3GHz). In this paper, PD activity simulation is generated using three types of artificial defects, which were detected by a UHF PD sensor installed in the GIS. The detected PD signals were performed on three-dimensional phi-q-n analysis. Finally, parameters were calculated and an Artificial Neural Network (ANN) was applied for PD pattern recognition. As a result, it was possible to discriminate and classify the defects.

이종 비유전율에서 TDR을 이용한 PD발생 위치 추적방법 (Using the TDR in specific inductive capacity for Partial Discharge Signals Detection Method)

  • 최문규;차한주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1477-1480
    • /
    • 2015
  • 본 논문은 TDR(Time Domain Reflectometry)을 이용하여, 비유전율내에서 PD(Partial Discharge) 발생 시 부분방전 위치를 추적할 수 있는 한분야의 방법으로 비율전율간의 이동속도를 적용하여 PD위치를 쉽게 겁근할 수 있는 방법이다. 기존에는 절연유와 SF6 가스의 연결부에서 부분방전 발생 시 30cm/ns의 이동속도를 이용하여 위치를 추적함으로써 약 31% 오차가 발생하였다. 절연유내에서의 이동속도를 20cm/ns의 상수를 적용하여 현장에 적용결과 PD위치의 오차를 저감할 수 있었으며, PD발생 부분을 절연유와 SF6 가스구역으로 구분을 할 수가 있었으며, 이를 통하여 점검예산을 확보할 수 있는 계기가 되었다. 비유전율 상수를 이용한 이동속도를 산출하여 PD위치를 추적하는 방법을 활용하면, 기존의 PD발생위치 추적을 보다 용이하게 접근할 수 있는 방법이라 생각한다.

  • PDF

Pattern Classification of Partial Discharge Data

  • Kim Sung-Ho;Bae Geum-Dong
    • International Journal of Fuzzy Logic and Intelligent Systems
    • /
    • 제5권4호
    • /
    • pp.347-352
    • /
    • 2005
  • PD(Partial discharges) are small electrical sparks that occur within the electric insulation of cables, transformers and windings on motors. PD analysis is a proactive diagnostic approach that uses PD measurements to evaluate the integrity of this equipment. Recently, several diagnostic algorithms for classifying the type of PD and locating the defect position have been developed. In this work, a new PD recognition system is proposed, which utilizes approximate coefficients of wavelet transform as a feature vector, furthermore, introduces bank of Elman networks to recognize the various PD phenomena. In order to verify the performance of the proposed scheme, it is applied to the simulated PD data.

고압전동기 모델 코일의 부분방전 분석 (Analysis of Partial Discharge in High Voltage Motor Model Coils)

  • 김희동;공태식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2091-2093
    • /
    • 2005
  • Five model coils of 6.6kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals, respectively The voltage applied to the coils was 3.81kV, 4.76kV, 6.0kV and 6.6kV. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector (PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns coincide with both PDD and TGA.

  • PDF

전력케이블에서 교류전압과 진동파 전압을 이용한 부분방전 측정 (Partial Discharge Detection for the Power Cables using AC and Oscillating wave Voltage)

  • 김정태;김남준;이전선;구자윤
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권4호
    • /
    • pp.247-252
    • /
    • 1999
  • In this paper, in order to investigate availability of the OW-PD measurement method which has been proposed as an alternative of AC-PD measurement method to an after laying test and/or diagnosis for the power cable system, partial discharges owing to the needle-type defect integrated into the cable have been measured using AC and OW(Oscillating Wave) voltages. In the AC-PD measurement, the magnitude, phase and pulse number of partial discharges have been changed with the duration of voltage application, which can be analyzed through the relation with the process of the electrical tree initiation and propagation. In addition, the characteristics of partial discharges using OW voltage are appeared to be similar to those in case of AC-PD measurement and to be different with the shapes of electrical tree. From these results, it is concluded that the OW-PD measurement method is available to the tests for the cable system.

  • PDF

유전알고리즘을 이용한 부분방전 패턴인식 최적화 연구 (A Study on the Optimization of PD Pattern Recognition using Genetic Algorithm)

  • 김성일;이상화;구자윤
    • 전기학회논문지
    • /
    • 제58권1호
    • /
    • pp.126-131
    • /
    • 2009
  • This study was carried out for the reliability of PD(Partial Discharge) pattern recognition. For the pattern recognition, the database for PD was established by use of self-designed insulation defects which occur and were mostly critical in GIS(Gas Insulated Switchgear). The acquired database was analyzed to distinguish patterns by means of PRPD(Phase Resolved Partial Discharge) method and stored to the form with to unite the average amplitude of PD pulse and the number of PD pulse as the input data of neural network. In order to prove the performance of genetic algorithm combined with neural network, the neural networks with trial-and-error method and the neural network with genetic algorithm were trained by same training data and compared to the results of their pattern recognition rate. As a result, the recognition success rate of defects was 93.2% and the neural network train process by use of trial-and-error method was very time consuming. The recognition success rate of defects, on the other hand, was 100% by applying the genetic algorithm at neural network and it took a relatively short time to find the best solution of parameters for optimization. Especially, it could be possible that the scrupulous parameters were obtained by genetic algorithm.

LabView 기반 부분방전 분석장치의 설계 및 제작 (Design and Fabrication of a LabView Based Partial Discharge Analyzer)

  • 차현규;이정윤;박대원;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제25권3호
    • /
    • pp.229-235
    • /
    • 2012
  • This paper dealt with the fabrication of a partial discharge (PD) analyzer for insulation diagnosis of power facilities like transformers, cables and gas-insulated switchgears. An analytic algorithm for the phase (${\phi}$), the magnitude (q), and the pulse count (n) of PD pulse was designed and a time-frequency (TF) map algorithm was applied in the system to eliminate noises by analyzing the time and the frequency component of signals. All the algorithms were operated by a LabView graphical program. The detection circuit consists of a coupling capacitor, a detection impedance, and a low noise amplifier. A plane-plane and a point-plane electrode system were fabricated to simulate different types of insulation defects. In the experiment, we could easily understand the characteristics of PD pulses using the prototype PD analyzer.

13[kV]급 수력발전기 고정자 권선의 운전 및 정지 중 진단시험 현장적용 평가 및 분석 (Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings)

  • 장정호;이동근;이흥호
    • 조명전기설비학회논문지
    • /
    • 제25권11호
    • /
    • pp.73-82
    • /
    • 2011
  • The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line). The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, ${\Delta}tan{\delta}$ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings.