• Title/Summary/Keyword: Overcurrent protection

Search Result 65, Processing Time 0.023 seconds

Development of A Digital Controller for The Metal Halide Lamp Ballast (메탈할라이드 램프 안정기의 디지털 제어기 개발)

  • Moon, Tae-Hwan;Kim, Hee-Jun;Cho, Kyu-Min;Kim, Myong-Gu
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.1113-1116
    • /
    • 2001
  • This paper presents a digital controller of electronic ballast for the metal halide lamp. The proposed controller includes the control algorithm for soft starting, no load protection, overcurrent protection and dimming(or power control). The proposed controller, moreover, has the high frequency modulation scheme and the tracking algorithm to avoid acoustic resonance phenomena. For the math production with the low cost using the ASICs, the proposed controller has been designed with the EPLDs only, without any microprocessor. In this paper, the proposed control algorithms are described and the experimental results of prototype 150W metal halide electronic ballast are presented.

  • PDF

A Study on the Algorithm for Fault Discrimination in Transmission Lines using Neural Network and the Variation of Fault Currents (신경회로망과 고장전류의 변화를 이용한 고장판별 알고리즘에 관한 연구)

  • Yeo, Sang-Min;Kim, Cheol-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.8
    • /
    • pp.405-411
    • /
    • 2000
  • When faults occur in transmission lines, the classification of faults is very important. If the fault is HIF(High Impedance Fault), it cannot be detected or removed by conventional overcurrent relays (OCRs), and results in fire hazards and causes damages in electrical equipment or personal threat. The fast discrimination of fault needs to effective protection and treatment and is important problem for power system protection. This paper propolsed the fault detection and discrimination algorithm for LIFs(Low Impedance Faults) and HIFs(High Impedance Faults). This algorithm uses artificial neural networks and variation of 3-phase maximum currents per period while faults. A double lines-to-ground and line-to-line faults can be detected using Neural Network. Also, the other faults can be detected using the value of variation of maximum current. Test results show that the proposed algorithms discriminate LIFs and HIFs accurately within a half cycle.

  • PDF

DISCO: A COMPUTER PROGRAM FOR PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS (DISCO: 배전 계통 보호 기기 정정 프로그램)

  • Lee, Seung-Jae;Park, Young-Moon;Lee, Jeoung-Won;Yoon, Sang-Hyun;Yoon, Man-Chul;Lee, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 1990.07a
    • /
    • pp.125-128
    • /
    • 1990
  • A program for the protection coordination of distribution systems is reported. The developed program nailed DISCO, consisting of two modules has a capability of selling the overcurrent relays, reclosers, sectionalizers, fuses which are commonly used in the primary feeder systems. Setting is performed in a downstream fashion starting from the substation, and coordination rules are applied identifying the pattern of the primary-backup devices based on the depth-first search. T/C curves of various devices are handled by digitization for accuracy and various graphics and windows are adopted for user-friendly interface.

  • PDF

A Phenomenological Studies on Ignition Characteristics of Wires by Local Impact, Over Loading and Overcurrent (국부적 충격, 과부하 및 과전류에 의한 전선의 발화특성에 관한 현상학적 연구)

  • Lee, Jeong-Jin;Lee, Chang-Woo;Choi, Don-Mook
    • Journal of the Korea Safety Management & Science
    • /
    • v.12 no.4
    • /
    • pp.53-60
    • /
    • 2010
  • When a fire breaks out, it is difficult to find out the causes of the fire, because combustible things around fire scene are usually burnt away. Among many causes of fires are electronic wires, this thesis deal with the destroyed sheath of electronic wires caused by fire. It was studied with the use of measurement devices focusing on the distinctions of wires and conductors. This study especially emphasized the process of deterioration, burning pattern, and composition of electronic wire conductor. It also has a phenomenological approach to the distinctive cause of fire by some partial force. The fire prevention methods have been suggested through the analysing results of fire patterns. This study is expected to be a useful material for analyzing various electrical fires.

Protection Coordination Associated with Connection Location of Residual Current Devices and Surge Protective Devices (RCD와 SPD의 접속 위치에 따른 보호협조)

  • Lee, Bok-Hee;Park, Hee-Yeoul;Shin, Gun-Jin;Bae, Gwan-Young;Ryu, Chun-Hyoung;Lee, Kang-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.100-106
    • /
    • 2013
  • In this paper, in order to analyze lightning impulse response characteristics in combined installations of SPDs and RCDs, surge protection coordination between SPDs and RCDs are experimentally investigated by using the combination wave generator. Six different types of single-phase residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) being present on the domestic market are tested according to KS C IEC 61009-1 standard. As a result, when a class I SPD is located on the source side of an RCBO, all kinds of specimens are able to provide the proper coordination between the SPD and RCBOs without nuisance tripping, unintended operation or damage due to test impulse currents. However, in the case that the class II SPD is located on the load side of RCBOs, a lot of L-N mode injected currents is split into the RCBO, and a few RCBOs are damaged. Coordination between SPDs and RCDs is not valid and a role of SPDs is of no use. When combining SPDs with RCDs, it is necessary to select SPDs and RCDs in consideration of the protection voltage level of metal oxide varistor embedded in RCDs.

Safety Schematic Diagram and Sequence of Heater in FPD Wet Equipment (FPD 장비 습식공정에서의 안전한 히터 공급 계통도 및 제어 회로)

  • Yoo, Heung-Ryol;Son, Yung-Deug
    • Journal of IKEEE
    • /
    • v.23 no.1
    • /
    • pp.107-111
    • /
    • 2019
  • In FPD WET equipment, heaters are used a lot. There are many electric accidents caused by short circuit and overheating due to the use of heater, so it is necessary to have a safe electric system and interlock. Therefore, in this paper, we propose an electrical schematic and interlock for FPD WET equipment. In this paper, a hardware interlock such as a level sensor, an overheat protector, and an SSR heater sink is inserted, and the electric system is composed of ELB - MC - SSR - EOCR - heater. When the interlock occurs, the magnetic contactor (MC) is turned off and the power of the heater is cut off.EOCR, an electric overcurrent protection device, has an interlock to shut down the MC when there is an abnormality in the heater while checking the overcurrent, undercurrent and disconnection. These circuit configurations and interlocks are likely to be useful not only for WET equipment but also for any equipment in which the heater is placed.

A Study on the Algorithm for Fault Discrimination in Transmission Lines Using Neural Network and the Variation of Fault Currents (신경회로망과 고장전류의 변화를 이용한 고장판별 알고리즘에 관한 연구)

  • Yeo, Sang-Min;Kim, Chul-Hwan;Choi, Myeon-Song;Song, Oh-Young
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.366-368
    • /
    • 2000
  • When faults occur in transmission lines, the classification of faults is very important. If the fault is HIF(High Impedance Fault), it cannot be detected or removed by conventional overcurrent relays (OCRs), and results in fire hazards and causes damages in electrical equipment or personal threat. The fast discrimination of fault needs to effective protection and treatment and is important problem for power system protection. This paper proposes the fault detection and discrimination algorithm for LIFs(Low Impedance Faults) and HIFs(High Impedance Faults). This algorithm uses artificial neural networks and variation of 3-phase maximum currents per period while faults. A double lines-to-ground and line-to-line faults can be detected using Neural Network. Also, the other faults can be detected using the value of variation of maximum current. Test results show that the proposed algorithms discriminate LIFs and HIFs accurately within a half cycle.

  • PDF

Investigation of Fault-Mode Behaviors of Matrix Converters

  • Kwak, Sang-Shin
    • Journal of Power Electronics
    • /
    • v.9 no.6
    • /
    • pp.949-959
    • /
    • 2009
  • This paper presents a systematic investigation of the fault-mode behaviors of matrix converter systems. Knowledge about converter behaviors after fault occurrence is important from the standpoint of reliable system design, protection and fault-tolerant control. Converter behaviors have been, in detail, examined with both qualitative and quantitative approaches for key fault types, such as switch open-circuited faults and switch short-circuited faults. Investigating the fault-mode behaviors of matrix converters reveals that converter operation with switch short-circuited faults leads to overvoltage stresses as well as overcurrent stresses on other healthy switching components. On the other hand, switch open-circuited faults only result in overvoltage to other switching components. This study can be used to predict fault-mode converter behaviors and determine additional stresses on remaining power circuit components under fault-mode operations.

Development of High-Performance Smart Battery for Notebook PCs with Lithium Ion Battery (리튬이온전지를 이용한 노트북 PC용 고성능 Smart Battery의 개발)

  • 김현수;문성인;윤문수;고병희;김동훈
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.16 no.11
    • /
    • pp.1047-1054
    • /
    • 2003
  • Smart battery pack (SBP) for notebook PCs was developed using a cylindrical-type lithium ion battery. Batteries were connected with three serial and two parallel, the nominal capacity and the maximum load of SBP was 4,000mAh and 4.0A, respectively. The SBP was composed of a protection IC, by which safety of lithium ion batteries is maintained against overcharge, overdischarge and overcurrent, and a smart IC, which calculates the remaining capacity and the remaining run time. In matching test on notebook PC using Battery Mark 4.0, real and smart data of END voltage coincided nearly and LB and LLB signal worked norma]]y. And there were errors of less than 1% between the real and the smart data on the residual capacity in the charge and discharge test.

A Novel Algorithm for Fault Classification in Transmission Lines using a Combined Adaptive Network-based Fuzzy Inference System (Neuro-fuzzy network을 이용한 고장 검출 및 판별 알고리즘에 관한 연구)

  • Yeo, S.M.;Kim, C.H.;Chai, Y.M.;Choi, J.D.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.252-254
    • /
    • 2001
  • Accurate detection and classification of faults on transmission lines is vitally important. High impedance faults(HIF) in particular pose difficulties for the commonly employed conventional overcurrent and distance relays, and if not detected, can cause damage to expensive equipment, threaten life and cause fire hazards. Although HIFs are far less common than LIFs, it is imperative that any protection device should be able to satisfactorily deal with both HIFs and LIFs. This paper proposes an algorithm for fault detection and classification for both LIFs and HIFs using Adaptive Network-based Fuzzy Inference System(ANFIS). The performance of the proposed algorithm is tested on a typical 154[kV] Korean transmission line system under various fault conditions. Test results show that the ANFIS can detect and classify faults including (LIFs and HIFs) accurately within half a cycle.

  • PDF