• Title/Summary/Keyword: Over-Excitation Limiter

Search Result 4, Processing Time 0.022 seconds

On-line Tests of on the Yang-Yang Pumped Storage Plant for the Reactive Power Limits and the OEL Dynamics (양양양수 온라인 무효전력 운전범위 시험과 과여자제한기(OEL) 동특성 시험)

  • Kim, Dong-Joon;Moon, Young-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.8
    • /
    • pp.1343-1350
    • /
    • 2007
  • This paper describes the tests on the reactive power output limit and the Over-Excitation Limiter (OEL) dynamics of a generation unit. The suggested test methods on reactive limit can identify the allowable maximum/minimum reactive power at 100% rated MW in the steady-state unit operation condition. The on-line OEL test method can identify the time characteristics of OEL with the generation output at 50% of the rated MW. These methods are validated by applying to four Yang-Yang pumped storage units with 282 rated MVA each.

Application of Fuzzy-PSS to KEPCO power system and stability enhancement (퍼지형 전력계통안정화제어기의 실계통 적용 및 안정도 향상)

  • Choi, Kyung-Sun;Lee, Dong-In;Lee, Kwang-Sik
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.1052-1055
    • /
    • 1997
  • The importance of dynamic stability of power system is increasing as the excitation system using static type are greatly enlarged. There are several types of PSS at Present, Elements of PSS consist of Notch filter, lead-lag filter, washout limiter which are variable. The existing power system has a difficulty in determining the optimal PSS parameters whenever PSS is installed. And it is recommended to retune PSS parameters periodically because system characteristics change due to aging. In this paper, intelligent PSS using fuzzy concept is introduced to get over difficulties mentioned above. The usefulness of fuzzy-type PSS was verified by applying FPSS to KEPCO power system. Generally, the voltage regulation deteriorates if conventional PSS is applied because supplementary signal is added into AVR summing point to damp Power oscillation. In this paper this problem is solved by AVR limiter and fuzzy members tuning.

  • PDF

Tests on the Reactive Power Limit and the OEL Dynamics of Yang-Yang P/P in Operation (양양 양수 발전기의 계통 운전시 무효전력 운전범위와 OEL 동특성 시험)

  • Kim, D.J.;Moon, Y.H.;Han, J.R.;Lee, K.S.
    • Proceedings of the KIEE Conference
    • /
    • 2006.11a
    • /
    • pp.384-386
    • /
    • 2006
  • This paper deals with tests on the reactive power output limit and the Over-Excitation Limiter (OEL) dynamics of generation unit. The suggested reactive limit test methods can identify the allowable maximum/minimum reactive power at 100% rated MW in the steady-state operation condition. The on-line OEL limit test method can identify the time characteristics of OEL with the generation output at 50% of the rated MW. These methods are validated by applying to Yang-Yang Pumped storage units of 282 MVA.

  • PDF

Application of Multi-step Undervoltage Load Shedding Schemes to the KEPCO System

  • Shin, Jeong-Hoon;Nam, Su-Chul;Lee, Jae-Gul;Choy, Young-Do;Kim, Tae-Kyun;Song, Hwa-Chang
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.4
    • /
    • pp.476-484
    • /
    • 2009
  • This paper deals with improvements to the special protection schemes (SPS) which have been applied to the low probability and high impact contingencies in the Korea Electric Power Corporation (KEPCO) system since 2004. Among them, the SPS for voltage instability in the Seoul metropolitan area is considered in this paper, and is a form of event-based undervoltage load shedding with a single-step scheme. Simulation results based upon a recent event that occurred on 765kV lines show that the current setting values of the SPS have to be revised and enhanced. In addition, by applying response-based multi-step undervoltage load shedding (UVLS) schemes to severe contingencies in the system, more effective results than those of the existing single-step SPS can be obtained. Centralized and distributed UVLS schemes are considered in the simulation. ULTC-based load recovery models and over excitation limiters (OXL) for the KEPCO system are also included in the long-term voltage instability studies.