• Title/Summary/Keyword: On-line PD test

Search Result 47, Processing Time 0.023 seconds

Characteristics of Capacitive Coupler for Partial Discharge Measurement in 6.6kV Rotating Machines (6.6kV 회전기 부분방전 측정용 Capacitive Coupler 특성)

  • Kang, Dong-Sik;Yoon, Dae-Hee;Kim, Yong-Joo;Yun, Yung-Ho;Lee, Jung-Jun;Song, Sang-Ock
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1619-1622
    • /
    • 2001
  • Recently many researches on the diagnosis of stator winding insulation for large rotating machines have been developed sine the 1970s. Capacitive coupler has been the most widely used sensor for on-line partial discharge(PD) in rotating machines. The 105 [pF] ceramic coupler(CC) has been developed to continuously measure the PD activity in operating motor stator windings. This paper presents frequency characteristics and laboratory test to compare traditional 80 [pF] epoxy-mica coupler(EMC) and 105 [pF] CC for PD measurement in 6.6 [kV] stator windings.

  • PDF

Feature Extraction of Partial Discharge for Stator Winding of High Voltage Motor (고압전동기 고정자권선의 부분방전 특징추출)

  • Park, Jae-Jun
    • The Journal of Information Technology
    • /
    • v.7 no.4
    • /
    • pp.61-69
    • /
    • 2004
  • On-line monitoring of fault discharge is an important approach for indicating the condition of electrical insulation of stator winding in high voltage motor. In this paper, several key aspects of on-line monitoring system are discussed, involving the characteristics of fault discharge of stator winding in high voltage motor, spectrum analysis of four simulation fault signals, feature extraction of internal fault discharge from apply voltage to breakdown. The study of the partial discharge activities allows to highlight the ageing stage in the winding fault under test. During the life of the winding insulation fault, the shape of PD signal change relating to the ageing stage. The ageing of stator winding insulation fault of high voltage motor is investigated based on the characteristics of partial discharge pulse distribution and statistical parameters, such as maximum, skewness and kurtosis using discrete wavelet trnasform coefficients.

  • PDF

A Study of On-line Monitoring System for a KEPCO Pumped Storage Generator/Motor

  • Kim Hee-Dong;Ju Young-Ho;Kim Yong-Joo;Cho Kyu-Bock
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.2
    • /
    • pp.90-95
    • /
    • 2006
  • An on-line diagnostic test has been studied and performed for the pumped storage generator/motor. This study aims at reducing the diagnostic cost, minimizing the technical dependency on third party manufactures. Further design of on-line diagnostic system such as shorted-turn of rotor winding, partial discharge (PD) of stator winding and air-gap between stator and rotor for pumped storage generator/motor has been verified. In addition, it needs to be validated on site performance of the developed continuous on-line monitoring system for corresponding tasks for the improvement of the availability & reliability during operation.

An adoption of the HFPD measuring system using directional coupler sensors to XLPE cable & accessories (방향성센서를 이용한 고주파 부분방전 측정시스템의 XLPE 케이블 및 접속함 적용)

  • Yu, In-Kee;Kim, Ki-Young;Jeong, Young-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1674-1676
    • /
    • 2002
  • In this paper, High Frequency PD measuring system using directional coupler sensors(DCS) is introduced. Especially the principles of the DCS and characteristics of the system are introduced. Evaluation of this system was carried by an adoption to the test circuit of 345kV XLPE $2000mm^2$ cable and EB-A, EB-G, PIJ, PNJ. In the test a PD measurement was carried out without shieldroom and under the on-line state and in the high frequency range at the remote site from the test object. The test result was satisfactory and this is due to the use of DCS and using a high frequency range and specific filter for radio and TV signal and low pass. This system can be used to the test of a new construction of cable and accessories and measuring of long-term deterioration of cable and accessories. And this will bring us the reliability of a power transmission.

  • PDF

PD Diagnosis on 22.9kV XLPE Underground Cable using Ultra-wideband Sensor

  • Lwin, Kyaw-Soe;Lim, Kwang-Jin;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.3 no.3
    • /
    • pp.422-429
    • /
    • 2008
  • This paper presents compact low frequency ultra-wide band (UWB) sensor design and study of the partial discharge diagnosis by sensing electromagnetic pulse emitted from the partial discharge source with the newly designed UWB sensor. In this study, we designed a new type of compact low frequency UWB sensor based on microstrip antenna technology to detect both the low frequency and high frequency band of the partial discharge signal. Experiments of offline PD testing on medium voltage (22.9kV) underground cable mention the comparative results with the traditional HFCT as a reference sensor in the laboratory. In the series of comparative tests, the calibration signal injection test provided with the conventional IEC 60270 method and high voltage injection testing are included.

A New Directional Coupler Type Partial Discharge Sensor Installed on the Power Lead of Rotating Machine

  • Yi, Sang-Hwa;Hwang, Don-Ha;Park, Wee Sang
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.6
    • /
    • pp.1769-1776
    • /
    • 2016
  • For on-line partial discharge (PD) monitoring of rotating machines, a novel sensor is proposed, which can be installed on the power lead inside the terminal box of the machine. The sensor has been designed to have high capacitance, and minimal reflection of measured pulses. As a sensitivity of the sensor, transfer impedance $Z_t$ has been measured and compared to conventional coupler-type sensors. A simple method is presented for measuring $Z_t$ of coupler sensors, using a vector network analyzer and a practical lead-cable of rotating machine. Through this method, it became possible to measure the $Z_t$ of coupler sensors including the installation environment of them. The $Z_t$ of the proposed sensor is higher than that of same sized other conventional couplers at frequencies between 30 and 92 MHz. Another sensitivity test has been performed using a PD calibrator as a test pulse source. The proposed sensor has higher measured peak voltage than the conventional coupler type sensors when the same charges were input.

Feature Extraction of Partial Discharge for Stator Winding of High Voltage Motor (고압전동기 고정자권선의 부분방전 특징추출)

  • Park, Jae-Jun;Kim, Hee-Dong;Lee, Dong-Yoon
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.112-116
    • /
    • 2004
  • On-line monitoring of fault discharge is an important approach for indicating the condition of electrical insulation of stator winding in high voltage motor. In this paper, several key aspects of on-line monitoring system are discussed, involving the characteristics of fault discharge of stator winding in high voltage motor, spectrum analysis of four simulation fault signals, feature extraction of internal fault discharge from apply voltage to breakdown. The study of the partial discharge activities allows to highlight the ageing stage in the winding fault under test. During the life of the winding insulation fault, the shape of PD signal change relating to the ageing stage. The ageing of stator winding insulation fault of high voltage motor is investigated based on the characteristics of partial discharge pulse distribution and statistical parameters, such as maximum, skewness and kurtosis using discrete wavelet transform coefficients.

  • PDF

UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear (가스절연 개폐장치의 내부절연 성능검증을 위한 UHF 협대역 부분방전 진단법)

  • Song Won-Pyo;Kim Jung-Bae;Kim Min-So;Jung Jae-Ryong;Park Seung-Jae;Ko Heui-Suk
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.9
    • /
    • pp.414-420
    • /
    • 2005
  • A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation.

Detecting Characteristics of Ultrasonics Generated by Partial Discharge in Insulating Oil Using the Optical Fiber Mach-Zehnder Interferometer (광섬유 Mach-Zehnder 간섭계를 이용한 부분방전 초음파 검출특성)

  • 이상훈;심승환;이광식;김달우
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.4
    • /
    • pp.50-56
    • /
    • 2003
  • It is well known that a partial-discharge(PD) in insulation oil is the source of various physical and chemical phenomena, such as heat, light, gas, chemical transformation, electric current, electromagnetic radiation and ultrasonics. The PD can be detected by measuring one of these changes. Although some techniques are employed in this purpose, several obstacles interfere with an on-line measurement. Ultrasonic-wave detection is a useful method for the diagnosis of the transformer-insulation condition. Conventionally, ulyrasonic waves are detected by Piezo-electric transducer, but we use optical method that has many advantages. In this paper, we constructed a Mach-Zehnder interferometer with optical fiber and investigated the principle of operation. Test arrangement is based on the needle-plane electrode system in oil and applied AC high voltage. Ultrasonic waves were detected and analyzed with wavelet transform.

End-fitting Design and Performance Evaluation of Polymer Insulator (폴리머 애자의 End-fitting 설계 및 성능 평가기술)

  • Cho, H.G.;Lee, U.Y.;Han, S.W.;Han, D.H.;Ji, W.Y.;Yeo, H.G.;Kang, D.W.;Chun, J.U.;Lee, H.K.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.25-29
    • /
    • 2004
  • Corona on polymer materials causes deterioration by the combined action of the discharge striking the surface and the action of certain chemical compounds that are formed by the discharges. In the design and manufacture of polymer insulators must be sufficiently large to avoid corona discharges, otherwise a shielding or corona ring (grading ring) needs to be installed on the insulator. To conduct this purpose, many researchers have investigated end-fitting of polymer insulator by voltage distribution simulation and electrical test. Grading rings are used to improve the performance of the insulator in multiple ways. They can reduce corona and associated audible noise and radio influence and television interference. The factors determining the uses of a grading ring are line voltage, geometry and dimensions of end fittings, geometry and dimensions of line hardware, and environmental conditions. In this paper, electrical property of polymer insulator with end-fitting design have been investigated by electrical field analysis, various end-fitting design, tracking wheel test, corona inception voltage and extinction voltage. Electrical field analysis is conducted by FEM program and various end-fitting is designed through this result. Designed end-fittings are manufactured and their performance is conducted by electrical performance test.

  • PDF