• Title/Summary/Keyword: Next generation technology

Search Result 2,091, Processing Time 0.031 seconds

Autonomous Adaptive Digital Over Current Relay (계통변화를 고려한 자율 적응형 과전류 계전기)

  • J.S., Jun-Seok;Lee, S.J.;Choi, M.S.;Kang, S.H.;Kim, S.T.;Lim, S.I.;Oh, S.M.;Kim, J.K.;Park, S.J.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.6-8
    • /
    • 2002
  • In this paper present Autonomous Adaptive Digital Over Current Relay which acts autonomous setting using voltage and current measured by relay in the change of power systems. Automation of relay setting is required for distribution automation although manual relay setting is used at present. This paper presents Autonomous Relay Setting which knows change of the power system and acquires setting element using the Recursive Least Squares. Relay setting is very difficult work. But proposed relay is expected to decrease burden of relay setting using acquired information of power system change and autonomous setting. Also fast protective ability is expected according to change of power system.

  • PDF

A Study on communication method between OverCurrent Relay Agents using DNP 3.0 (DNP3.0을 이용한 과전류 계전기 에이전트의 통신 방안 연구)

  • Lee, H.W.;Jung, K.H.;Lim, S.I.;Hyun, S.H.;Choi, M.S.;Lee, S.J.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.265-267
    • /
    • 2002
  • In this paper, the communication between Over-Current Relay agents is realized using DNP(Distributed Network Protocol), which is the standard communication protocol of distribution automation system in KEPKO. The key words in OCR agent communication are defined and represented by use of DNP application function code. And the DNP index for OCR agent is defined. The proposed communication scheme is tested by use of Communication Test Harness, a test tool for DNP protocol to show its soundness.

  • PDF

Optimal protection by using Parametric Protection Ability Index (파라미터를 이용한 배전계통 보호능력 평가 및 최적화)

  • Shin, J.H.;Hyun, S.H.;Lim, S.I.;Lee, S.J.;Choi, I.S.;Jin, B.G.
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.202-204
    • /
    • 2003
  • This paper suggests an optimal parameter setting method by use of parametric protectability index, as the objective function. In this paper, a gradient based optimization method is used under the assumption that the initial values of a parameter is in a convex set including the optimal value, which is verified by a plenty of simulation studies. The proposed method is applied to a sample distribution network to shows its effectiveness.

  • PDF

Development of ACL Modul For Agent Communication in Auto-Adaptive OCR Agent (자율적응형 과전류계전기 에이전트의 통신을 위한 ACL모듈 개발)

  • Oh, T.W.;Lee, S.J.;Choi, M.S.;Kim, K.H.;Lim, S.I.;Min, B.W.;Lee, H.W.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.193-195
    • /
    • 2002
  • In this paper, a communication module is proposed to be applied to communication between over current relay (OCR) agents in multi agent protection system. A multi agent system can achieve a global goal beyond the ability of each individual agent by working together, in which it is the prerequisite for each agent to be able to exchange or share information or processing status with other agent. The proposed communication module is purposed to enable not only each agent to bring about its own goal, but also the whole protective system to provide much improved coordinated protection. It is applied to a self adaptive protection system for a distribution network using multi agent concept to show its effectiveness.

  • PDF

Investigation into Transformer Protective Relay Setting Rule Considering Error Ratio (오차를 고려한 765kV 변압기 보호 계전 정정룰 고찰)

  • Bae, Y.J.;Lee, S.J.;Choi, M.S.;Kang, S.H.;Kim, S.T.;Choi, J.L.;Jeong, C.H.;Yoo, Y.S.;Cho, B.S.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.229-231
    • /
    • 2002
  • The digital current differential relaying scheme is widely used for primary protection of 765(kV) power transformer. The current differential relay pickup the internal fault at the threshold which is set at 30% of rating current. Margin of 30% include current transformer error 5%, relay error 5%, on load tap changer error 7% and margin factor 140% obtained from the field experience. In this paper transformer protection relay and relay setting rule of high voltage power system are discussed. And we verify the correctness of relay setting rule with current differential relay using Matlab simulation.

  • PDF

THE DEVELOPMENT OF WEB SERVER FOR KOREAN ELECTRICAL DISTRIBUTION-SYSTEM PROTECTION (한국전력 송전 계통보호를 위한 웹 서버 개발)

  • Zhang, Li;Choi, M.S.;Lee, S.J.;Min, B.U.;Kim, S.H.;Oh, S.M.
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.178-180
    • /
    • 2003
  • Since faults often occur on power system, relay protection has become an important part to protect the equipments of power system efficiently and safely. Database can store the data about the relay protection efficiently, and these data must be shown to users through the web. Proset2000(an overall program system to protect power system) can realize this function in some measure, but it needs to be developed. This paper is about the further development of Proset2000. In this paper, web of Proset2000 is made by ASP programming technology, and users can browse and search the useful data through the web. There are some new functions, such as the summary of setting values, the message board and the management of administrator.

  • PDF

Implementation of an Over-Current Relaying Algorithm with TMS320C32 (TMS320C32를 이용한 한시 과전류 계전기의 구현)

  • Yoo, Sung-Rok;Yoon, Byung-Wook;Park, Byung-Woo;Choi, Chang-Yung;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2193_2194
    • /
    • 2009
  • A digital over current relay(OCR) is realized by using TMS320C32 microprocessor. Fourier Transform is used to obtain the phasor of a current signal and a 2nd low pass filter is adopted to prevent aliasing error. H/W test shows almost same results with those of the S/W test. It could be possible that confirm simularity between H/W and S/W test in this paper.

  • PDF