푸리에 변환을 이용한 다중 재폐로방식에서의 사고전류 특징 추출 (Feature Extraction of Fault Current using Fourier Transform in the Multi-Shot Reclosing Scheme)

  • 오정환;윤상윤;김재철
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권2호
    • /
    • pp.50-55
    • /
    • 2000
  • This paper presents the feature extraction of fault currents related to the multi-shot reclosing scheme in the power distribution system. In order to get the fault current waveform, we have measured the fault currents by the fault recorders which have been installed at the secondary side of 154/22.9[kV] substation transformer. These waveforms are classified into temporary and permanent fault. For the classified waveforms, Fourier transform is used to extract the feature of the fault current waveforms. After the waveforms are analyzed by using Fourier transform, the magnitude spectrum and the relative variation of THD (Total Harmonic Distortion) are calculated. And then the relative variation of THD is great in the temporary faults, and is small in the permanent faults.

  • PDF

푸리에 변환을 이용한 다중 재폐로방식에서의 사고전류 특징 추출 (Feature Extraction of Fault Current using Fourier Transform on the Multi-Shot Reclosing)

  • 오정환;윤상윤;이난숙;김재철;배주천;김낙경
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1130-1132
    • /
    • 1999
  • This paper presents the feature extraction of fault current related to the multi-shot reclosing scheme in the power distribution system. Fourier transform is used to extract the feature of the fault current waveform in the case of the temporary fault and the permanent fault. After the waveform is analyzed using Fourier transform, the magnitude spectrum and the relative variation of THD are calculated. These results are that the relative variation of THD is great in the temporary fault and is little in the permanent fault.

  • PDF