• 제목/요약/키워드: Motor Operated Valve(MOV)

검색결과 17건 처리시간 0.029초

원자력발전소에서 사용중인 모터구동밸브 스템 윤활유의 성능 비교 분석 (A comparison analysis of the stem lubricant performance for motor operated valve used in nuclear power plants)

  • Kim, Dae-Woong;Kim, Yang-Seok;Park, Chi Young;Lee, Sang Guk
    • 한국압력기기공학회 논문집
    • /
    • 제11권2호
    • /
    • pp.6-12
    • /
    • 2015
  • In this study, the performance test was carried out under various operation conditions targeting four representing types of lubricant which are mostly used in nuclear power plants, and mutually compared the characteristic and performance of lubricant. Especially, introducing the concept of the thread friction coefficient (hereinafter, TFC), which makes the friction relation between the stem nut and stem screw dimensionless. The test was performed to compare the lubricant performance for the four kinds of lubricant (Texaco, Alvania, Mobilux, MOVLL). In a test of the room temperature stem, the TFC of MOV Long Life shows the lowest value, next to Alvania EP2, Texaco EP2, and Mobilux EP0 in that order. And in a test of the high temperature stem, the TFC of Texaco EP2 shows the lowest, next to MOV Long Life, Alvania EP2, and Mobilux EP0 in that order. From the test result of the aging condition, three types of lubricant (MOV LL, Texaco EP2, Alvania EP2) show similar patterns up to 36 months, but in 60 months, the TFC of lubricant are increased rapidly.

모터구동밸브의 성능 진단을 위한 모터 토크 분석 (Motor Torque Analysis for Motor-Operated Valves Performance Evaluation)

  • 권석준;이상회;박주문;성게용;이흥호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 합동 추계학술대회 논문집 정보 및 제어부문
    • /
    • pp.337-341
    • /
    • 2002
  • 본 논문은 원자력 발전소의 안전에 있어 매우 큰 비중을 차지하는 모터 구동밸브(Motor-operated valve : MOV)의 성능진단에 직접 센서를 장착하지 않고 전기신호만을 이용하여 성능진단의 가능성을 보이기 위한 것이다. 모터 토크를 계산하기 위한 두 가지 방법으로서 D-Q frame 변환 방법과 Air-Gap 토크 식을 제시하였고, 계산된 두 토크 값은 정확하게 일치하였다. 부하를 변동하면서 토크미터로 측정된 토크 갑과는 1%의 오차범위 내에서 일치함을 확인했다. 따라서 두 토크 식은 모터구동 밸브의 성능진단을 위한 식으로 사용해도 좋다는 결론을 얻어낼 수 있었다. 계산된 토크를 주파수 분석함으로서 부하의 변동에 따라서 슬립 및 모터속도 주파수가 변화됨을 알 수 있었다. 즉 주파수 분석을 통해 MOV의 모터 및 구동기 부분의 성능 저하 감시에 유용한 단서를 제공해 줄 것이다. 결과적으로, MOV에서 전기신호의 분석은 시스템의 전기 및 기계적인 성능 저하 감시에 이용될 수 있을 것으로 기대된다.

  • PDF

모터구동 게이트밸브의 열림행정시 차압 작용에 의한 부하율 연구 (Study on the Rate-of-Loading by the Differential Pressure of Motor Operated Gate Valves in Opening Stroke)

  • 김범년;홍성인
    • 한국추진공학회지
    • /
    • 제11권6호
    • /
    • pp.35-41
    • /
    • 2007
  • 부하율은 모터구동 밸브에서 밸브 스템에 가해지는 부하(load) 변화에 따라 구동기 torque와 스템 thrust 사이의 상관관계가 변하는 현상이다. 본 논문에서는 게이트밸브의 열림행정에서 발생되는 부하율 특성을 분석하고 밸브 성능평가시 적용하는 부하율의 타당성에 대해 기술하였다. 또한, 총 40대의 게이트밸브에 대해 정적시험 및 동적시험을 수행하고 본 연구에서 개발한 열림행정에서의 부하율 평가 방법론을 적용하여 각 밸브의 열림행정 부하율을 평가한 결과를 수록하였다. 연구결과로서 열림행정의 부하율은 차압이 150 psi보다 높은 경우 (-)값으로 나타났으며, 이러한 현상은 유체 차압이 높을수록 크게 나타나는 결론을 얻었다.

Performance Evaluation of Motor-Operated Valve Using Electrical Signatures

  • Park, Joo-Moon;Joo, Hyung-Jun;Jung, Jae-Cheon;Sung, Key-Yong;Seong, Se-Jin
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2001년도 Proceedings ICPE 01 2001 International Conference on Power Electronics
    • /
    • pp.52-55
    • /
    • 2001
  • This paper is to see the availability of electrical signatures as a means for evaluating the performance and monitoring mechanical anomalies of (MOVs). To estimate motor torque, two methods such as d-q frame conversion and air-gap method are suggested and estimated results are compared with measured values. The error between measured and estimated torques is within acceptable error bound with below $1\%$ under varied load. Frequency domain analysis of calculated torque has been done as well. It is shown that monitoring of peak frequency could give useful clues to detect anomalies of MOV. As results, electrical signatures at MOV motor is expected to be an available tool for estimation of motor capacity and monitoring of electrical and mechanical abnormalities.

  • PDF

피로설계 및 평가를 위한 3차원 유한요소 응력해석에 관한 고찰;모터구동밸브를 이용한 사례연구 (3-D Finite Element Stress Analysis for Fatigue Design and Evaluation;A Parametric Study of MOV(Motor Operated Valve))

  • 김형근;이상민;장윤석;최재붕;김영진;김윤재
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2004년도 추계학술대회
    • /
    • pp.142-147
    • /
    • 2004
  • In this paper, a new procedure is proposed to accomplish the primary plus secondary stress(P+Q) at the 'structural element' instead of 'transition element'. For the P+Q evaluation, the calculated stresses by FEA are linearized along a stress classification line to extract the stress category, then the stress intensity is calculated to compare with the $3S_{m}$ limit. Also, in this paper, the 'design by analysis' criteria, adopted fundamental concepts and a new approach to calculate $K_{e}$ factors are explained. The new procedure combined with 3-D FEA has been applied to motor operated valve in order to the over conservatism and the rack of margin. The evaluation results show a good applicability and can be utilized for fatigue life evaluation by using P+Q.

  • PDF

도시가스 고압배관의 합리적인 위험감소조치 선정을 위한 비용-편익분석 (Cost-Benefit Analysis in order to Select the Reasonably Practical Risk Reduction Measures(RRMs) on High Pressure Urban Gas Pipelines)

  • 류영돈;김영섭;이수경
    • 한국가스학회지
    • /
    • 제15권2호
    • /
    • pp.40-46
    • /
    • 2011
  • 위험성 평가에서 비용-편익분석의 목적은 위험성 평가를 통해 도출된 부가적인 위험감소조치의 편익이 그 조치를 수행하는 데 든 비용보다 많음을 확인하고, 그 조치를 이행하는 것이 적절함을 보여주는 데 있다. 본 논문에서는 도시가스 고압배관의 위험성 평가에 따라 도출한 위험감소조치를 이행함에 있어 가장 효과적이고 합리적인 조치를 선정하기 위하여 비용-편익 분석을 실시하였다. 도출한 위험감소조치를 적용하여 위험성 평가를 다시 실시한 결과, 배관부식방지조치, MOV 설치 및 타공사 방지조치를 하도록 한 10번 조치가 위험감소효과가 75 %로 가장 컸으며, 비용-편익 분석 결과 합리적으로 실행가능한 것으로 판단되어 본 논문의 연구대상 배관의 위험감소조치로 선정하였다.

정량적 위험성 평가를 통해 제안된 도시가스 고압배관의 위험경감조치별 위험감소효과 (Risk Reduction Rate for Each Risk Mitigation Measure on High Pressure Urban Gas Pipelines Proposed by Quantitative Risk Analysis)

  • 류영돈;조영도;박영길;이수경
    • 한국가스학회지
    • /
    • 제14권4호
    • /
    • pp.18-23
    • /
    • 2010
  • 이 논문에서는 실제 설치예정인 도시가스 고압배관에 대하여 정량적 위험성 평가를 실시하고, 평가 결과 위험이 허용영역 밖에 위치하는 경우에는 위험경감조치를 도출하였다. 또한, 도출한 위험경감조치별 위험감소율을 계산하였다. 정량적 위험성 평가결과, 복사열에 의한 사고피해거리는 바람의 속도와 대기안정도에 따라 크게 좌우됨을 알 수 있었다. 위험감소율이 가장 큰 조치는 배관의 부식관리, MOV 설치 및 타공사로 인한 배관손상방지조치를 모두 이행하도록 하는 10번 조치로서 75%의 위험감소효과가 있었다.