• Title/Summary/Keyword: Mist Spray

Search Result 85, Processing Time 0.024 seconds

A Study on Spray Characteristics of Water Mist Nozzle with Mid-low Pressure for Fire Suppression (화재용 중저압 물분무 노즐의 분무특성에 관한 연구)

  • 김성찬;유홍선;박현태;방기영
    • Journal of the Korean Society of Safety
    • /
    • v.18 no.1
    • /
    • pp.28-32
    • /
    • 2003
  • The present study investigates the spray characteristics of water mist nozzle with mid-low pressure for fire suppression. The examined nozzle types are swirl and spiral nozzle. The result shows that K factor of water mist nozzle is much smaller than those of general sprinkler. Spray angle of spiral nozzle is largest and more than $150^{\circ}$. SMD(Sauter Mean Diameter) of water mist nozzles is ranged between 100 and 200$\mu\textrm{m}$through measuring by image processing method. The spray pattern of spiral nozzle represent that water flux of first stream is 2 times larger than that of second stream. This study will contribute better understandings of the water-mist spray characteristics and useful daia for developing the water-mist nozzles.

Spray Flow Characteristics of Twin-fluid Water Mist Nozzle for Fire Suppression (2유체 미세 물분무 소화노즐의 분무유동 특성)

  • Kim, Bong-Hwan;Choi, Hyo-Sung;Kim, Dong-Keon
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.10 no.3
    • /
    • pp.60-66
    • /
    • 2011
  • In the present investigation, experimental studies were conducted on the fire suppression performance of twin-fluid water mist spray which is subjected to thermal radiation in a closed space. Downward-directed water-mist sprays, interacting with an under kerosene pool fire, were investigated in a test facility. The mass mean diameter of water-mist droplets were measured by PMAS under various flow conditions. The developed twin-fluid water mit spray nozzle satisfied the criteria of NFPA 750, Class 1. The mechanism of fire suppression by fine water mist was concluded to be the cooling of the fire surface which leads to the suppression of fuel evaporation. It was proved that the automatic twin-fluid water mist spray system under lower pressures could be applied to an industrial facilities.

A Study on the Performance of Water Mist Spray Fire Protection System (미세물분무 소화성능에 관한 연구)

  • 김봉환;김용판;문철진;홍철현;이형욱;최현호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.7
    • /
    • pp.572-578
    • /
    • 2003
  • The present study was numerically and experimentally performed to investigate the fire suppression performance of water mist spray subjected to thermal radiation in closed space. Downward-directed water mist sprays to interact with an under kerosine pool fire were investigated in test facility The mass mean diameters of water mist droplet were measured by PMAS under various flow conditions. The developed water mist spray nozzle was satisfied to the criteria of NFPA 750, Class 1. The mechanism of the fire suppression by water mist was attributed to the cooling of the fire surface which lead to suppressed of fuel evaporation. It was proved that the water mist spray system under lower pressures could be applied to underground fire protection system.

Analysis for fire suppression efficiency of intermittent water spray pattern with FDS (FDS를 이용한 교번식 미분무방식의 소화 성능 분석)

  • Jee, Moon-Hak;Lee, Byung-Kon
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.200-203
    • /
    • 2008
  • Water mist fire suppression system utilizes the fire suppression features such as cooling of fire source, dilution of ambient oxygen, and shielding of radiation heat with the evaporation of microscopic water droplets. The momentum of water mist is relatively low and the infiltration of water mist to the fire source is not effective. In addition to lower penetration force, the evaporated water vapor is liable to decline to limited portion of fire source due to its light weight and sparse density. On the other hand, the cycling water mist system is expected to improve the penetration force of water mist as well as the dilution coverage capability with the stratified spray characteristics. At this paper we present the analyzed fire suppression capability of intermittent water spray pattern by use of FDS which is computational fire dynamics fire model. We expect this analysis shall be supportive to the development of the prototype of water mist nozzle.

  • PDF

A study on the Water Mist Fire Suppression Performance (미세 물 분무 소화 성능에 관한 연구)

  • 김봉환;김용판;문철진;홍철현;이형욱
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2002.05a
    • /
    • pp.61-65
    • /
    • 2002
  • The present study was numerically and experimentally performed to investigate the fire suppression performance of water mist spray subjected to thermal radiation in closed space. Downward-directed water mist sprays to interact with an under kerosine pool fire were investigated in test facility. The mass mean diameters of water mist droplet were measured by PMAS under various flow conditions. The developed water mist spray nozzle was satisfied to the criteria of NFPA 750, Class 1. The mechanism of the fire suppression by water mist was concluded to be cooling of the fire surface which lead to suppressed of fuel evaporation. It was proved that the water mist spray system under lower pressures could be applied to underground fire protection system.

  • PDF

APPLICATION OF CFD TECHNIQUE TO PERFORMANCE PREDICTION OF SPRAY CHARACTERISTICS OF WATER-MIST FIRE SUPPRESSION NOZZLES (미분무수 소화 노즐의 분무 특성 예측을 위한 CFD기법의 적용)

  • Chung, H.T.;Lee, C.H.;Cho, B.I.;Han, Y.S.;Ock, Y.W.
    • Journal of computational fluids engineering
    • /
    • v.11 no.4 s.35
    • /
    • pp.56-61
    • /
    • 2006
  • Numerical simulation has been performed to investigate the characteristics of the mist flow through the fire suppression nozzles. The commercial CFD software, FLUENT with the proper modeling was applied for analyzing both the internal and external flow of the spray nozzles. Computations were made for the full cone nozzle in the operation range of the low pressure and high flow-rate. To validate the present computational procedure, numerical results are compared with measurements in terms of K-factor, SMD, axial spray velocity and spray angles. Numerical results suggested that the present numerical model can be used as an adequate tool for a design purpose of mist-spray nozzles.

CFD를 이용한 흡수탑 내 유동 균일효과 연구

  • 이춘만;이호경
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2004.05a
    • /
    • pp.106-106
    • /
    • 2004
  • 보일러에서 연소된 후 배출된 가스는 탈황목적으로 설치된 흡수탑 내에 유입되어 Slurry Spray Nozzle에서 분사된 Limestone Slurry에 의해 배기가스중의 SO$_2$를 흡수한 다음 반응조로 떨어지게 되지만 분사된 액적의 일부는 배기가스의 압력에 의하여 같은 유동 방향으로 미세한 Mist의 형태로 배기가스와 함께 흡수탑의 Outlet Duct를 통해 빠져나간다. 이 Mist(액적크기 40 $\mu\textrm{m}$이하)에는 고형 성분이 함유되어 있는데 보통 Chloride농도가 높아 탈황설비 후단 (duct, GGH, Stack)에 plugging, 부식 등의 문제를 유발하므로 Spray Header상부에서 Mist Eliminator를 설치하여 Mist를 제거하도록 한다.(중략)

  • PDF

Numerical Study on the Effects of Spray Properties of Water Mist on the Fire Suppression Mechanism (미분무수 특성이 화재억제 메커니즘에 미치는 영향에 대한 수치해석적 연구)

  • Bae, Kang-Youl;Chung, Hee-Taeg;Kim, Hyoung-Bum
    • Journal of ILASS-Korea
    • /
    • v.22 no.4
    • /
    • pp.175-184
    • /
    • 2017
  • The numerical investigation on the effects of water-mist characteristics has been carried out for the fire suppression mechanism. The FDS are used to simulate the interaction of fire plume and water mists, and program describes the fire-driven flows using LES turbulence model, the mixture fraction combustion model, the finite volume method of radiation transport for a non-scattering gray gas, and conjugate heat transfer between wall and gas flow. The numerical model is consisted of a rectangular enclosure of $L{\times}W{\times}H=1.5{\times}1.5{\times}2.0m^3$ and a water mist nozzle that be installed 1.8 m from fire pool. In the present study, the parameters of nozzle for simulation are the droplet size and the spray velocity. The droplet size influences to fire flume on fire suppression more than the spray velocity because of the effect of the terminal velocity. The optimal condition for fire suppression is that the droplet size and the spray velocity are $100{\mu}m$ and 20 m/s respectively.

Numerical Study on the Attenuation Effect of Water Mist on Thermal Radiation (미세물분무에 의한 열복사 감쇠 효과에 대한 수치해석 연구)

  • Ko, Gwon Hyun
    • Fire Science and Engineering
    • /
    • v.34 no.4
    • /
    • pp.7-12
    • /
    • 2020
  • A numerical study was conducted to investigate the effects of the spray characteristics of water mist on the attenuation of thermal radiation. The attenuation process of the thermal radiation, generated from a hot surface panel, passing through the water mist was calculated via Fire Dynamics Simulator (FDS), and the effects of the flow rate, droplet mean diameter, and spray injecting angle of the water mist were analyzed. The results indicated that the increase in flowrate and decrease in droplet size led to an increase in the attenuation of thermal radiation. As the thermal radiation passed through the spray droplets, the effect of the spatial distribution of spray droplets was verified by calculating the thermal radiation attenuation at different spray injecting angles. The results indicated that the radiation attenuation increases as the spray angle increases. This implies that a wider distribution of spray droplets, irrespective of the droplet size and flowrate, increases the attenuation effect on thermal radiation.

Analysis of Fire Suppression Efficiency for Intermittent Water Spray Pattern by Fire Dynamics Simulator (FDS를 이용한 교번식 미분무방식의 소화 성능 분석)

  • Jee, Moon-Hak;Lee, Byung-Kon
    • Fire Science and Engineering
    • /
    • v.22 no.3
    • /
    • pp.216-220
    • /
    • 2008
  • Water mist fire suppression system utilizes the fire suppression features such as cooling of fire source, dilution of ambient oxygen, and shielding of radiation heat with the evaporation of microscopic water droplets. The momentum of water mist is relatively lower than that of larger water droplet and the infiltration of water mist to the fire source is not effective. Contribution of evaporated water vapor is liable to decline to limited portion of fire source due to its light weight and sparse density. On the other hand, the cycling water mist pattern is expected to improve the penetration force of water mist as well as the air expelling capability with the stratified spray characteristics. At this paper, we present the analyzed fire suppression capability of intermittent water spray pattern by use of FDS which is computational fire dynamics fire model. We expect this analysis can support the basic concept to the development of the prototype of water mist nozzle.