• Title/Summary/Keyword: Minimum Cooling Load

Search Result 38, Processing Time 0.041 seconds

A Study on the Optimum Slope of the Roof for Minimum Cooling Load (냉방부하 최소화를 위한 지붕의 최적기울기에 관한 연구)

  • Tae, Won-Jin
    • Journal of the Korean Solar Energy Society
    • /
    • v.25 no.4
    • /
    • pp.119-123
    • /
    • 2005
  • The main purpose of this study is to define an optimum slope of the roof that demands minimum cooling load of the building, when the roof is affected by the solar and wind energy. Two different roof shapes were chosen: hip, gabled. The cooling load of building having those roof shapes was calculated through the computer simulation, using DOE program. For the simulation, the angle of the roof and angle of the orientation was changed. In the conclusion of this paper, an optimum slope of the roof which causes minimize cooling load is presented according to the roof shape and orientation. The result of this study could provide a practical design guideline for determining the roof angle for various climatic conditions.

A Study on Estimation of Cooling Load Using Forecasted Weather Data (기상 예보치를 이용한 냉방부하 예측 기법에 관한 연구)

  • Han, Kyu-Hyun;Yoo, Seong-Yeon;Lee, Je-Myo
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.937-942
    • /
    • 2008
  • In this paper, new methodology is proposed to estimate the cooling load using design parameters of building and predicted weather data. Only two parameters such as maximum and minimum temperature are necessary to obtain hourly distribution of cooling load for the next day. The maximum and minimum temperature that are used for input parameters can be obtained from forecasted weather data. Benchmarking building(research building) is selected to validate the performance of the proposed method, and the estimated cooling loads in hourly bases are calculated and compared with the measured data for benchmarking building. The estimated results show fairly good agreement with the measured data for benchmarking building.

  • PDF

A Study on Prediction of Hourly Cooling Load Using Building Area (건물 면적을 이용한 시간별 냉방부하 예측에 관한 연구)

  • Yoo, Seong-Yeon;Han, Kyu-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.11
    • /
    • pp.798-804
    • /
    • 2010
  • New methodology is proposed to predict the hourly cooling load of the next day using maximum/minimum temperature and building area. The maximum and minimum temperature are obtained from forecasted weather data. The cooling load parameters related to building area are set through a database provided from reference buildings. To validate the performance of the proposed method, the predicted cooling loads in hourly bases are calculated and compared with the measured data. The predicted results show fairly good agreement with the measured data for benchmarking building.

A Study on Estimation of Cooling Load Using Forecasted Weather Data (집단 건물 면적을 이용한 시간별 냉방부하 파라미터 설정 및 예측에 관한 연구)

  • Han, Kyu-Hyun;Yoo, Seong-Yeon;Lee, Je-Myo;Song, Yang-Sup
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.440-445
    • /
    • 2008
  • In this paper, new methodology is proposed to estimate the cooling load using areas of building group and predicted weather data. Only three parameters such as maximum, minimum temperature and building area are necessary to obtain hourly distribution of cooling load for the next day. The maximum and minimum temperature that are used for input parameters can be obtained from forecasted weather data. The areas of building group are used for setting several parameters that are used for estimate cooling loads. Benchmarking building(research building) is selected to validate the performance of the proposed method, and the estimated cooling loads in hourly bases are calculated and compared with the measured data for benchmarking building. The estimated results show fairly good agreement with the measured data for benchmarking building.

  • PDF

A Study on the Characteristics of Heating and Cooling Loads of Standard Chicken Houses in South Korea (국내 표준계사의 냉난방부하 특성 연구)

  • Kwon, Young-Cheol
    • Journal of the Architectural Institute of Korea Structure & Construction
    • /
    • v.35 no.10
    • /
    • pp.235-243
    • /
    • 2019
  • In South Korea, millions of poultry have died due to repeated heat waves every year. The purpose of this study is to analyze the characteristics of heating and cooling loads of chicken houses in Korea and to present an effective insulation and ventilation measures to minimize the damage of poultry due to summer heat wave and to save energy in chicken houses in winter. The heating and cooling loads of standard chicken house were calculated. As a result of the calculation of maximum heating load based on the minimum ventilation rate in winter, the outdoor air temperature requiring heating was $6{\sim}7^{\circ}C$ to keep the indoor air temperature of chicken houses as $24^{\circ}C$. The peak cooling load of chicken houses was mostly taken by the heat generated by chickens and the heat gain due to ventilation. The heat gain through building envelopes was as small as neglectable. Most of chicken houses is usually cooled by gigantic forced ventilation in summer in Korea. When the chicken houses are cooled by electric cooling machine such as cooler or air conditioner, it is more effective to keep minimum ventilation rate to reduce the maximum cooling load. To lower the temperature of supplying water to cooling pad, it is recommended to use the underground water below 10 meters from the ground if there is abundant underground water.

Effects of Inlet Water Temperature and Heat Load on Fan Power of Counter-Flow Wet Cooling Tower (입구 물온도와 열부하가 냉각탑의 팬동력에 미치는 영향 분석)

  • Nguyen, Minh Phu;Lee, Geun Sik
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.3
    • /
    • pp.267-273
    • /
    • 2013
  • In order to provide effective operating conditions for the fan in a wet cooling tower with film fill, a new program to search for the minimum fan power was developed using a model of the optimal total annual cost of the tower based on Merkel's model. In addition, a type of design map for a cooling tower was also developed. The inlet water temperature and heat load were considered as key parameters. The present program was first validated using several typical examples. The results showed that for a given heat load, a three-dimensional graph of the fan power (z-axis), mass flux of air (x-axis, minimum fan power), and inlet water temperature (y-axis, maximum of minimum fan power) showed a saddle configuration. The minimum fan power increased as the heat load increased. The conventionally known fact that the most effective cooling tower operation coincides with a high inlet water temperature and low air flow rate can be replaced by the statement that there exists an optimum mass flux of air corresponding to a minimum fan power for a given inlet water temperature, regardless of the heat load.

A Study on Building Energy Saving using Outdoor Air Cooling by Load Prediction (부하예측 외기냉방에 의한 건물에너지 절약에 관한 연구)

  • Kim, Tae-Ho;Yoo, Seong-Yeon;Kim, Myung-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.2
    • /
    • pp.43-50
    • /
    • 2017
  • The purpose of this study is to develop a control algorithm for outdoor air cooling based on the prediction of cooling load, and to evaluate the building energy saving using outdoor air cooling. Outdoor air conditions such as temperature, humidity, and solar insolation are predicted using forecasted information provided by the meteorological agency, and the building cooling load is predicted from the obtained outdoor air conditions and building characteristics. The air flow rate induced by outdoor air is determined by considering the predicted cooling loads. To evaluate the energy saving, the benchmark building is modeled and simulated using the TRNSYS program. Energy saving by outdoor air cooling using load prediction is found to be around 10% of the total cooling coil load in all locations of Korea. As the allowable minimum indoor temperature is decreased, the total energy saving is increased and approaches close to that of the conventional enthalpy control.

A Study on Correlation of Outdoor Environmental Condition about Cooling Load (냉방부하에 영향을 미치는 외기 환경조건의 상관관계에 관한 연구)

  • Lee, Je-Myo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.11
    • /
    • pp.759-766
    • /
    • 2012
  • To estimate the cooling load for the following day, outdoor temperature and humidity are needed in hourly base. But the meteorological administration forecasts only maximum and minimum temperature. New methodology is proposed for predicting hourly outdoor temperature and humidity by using the forecasted maximum and minimum temperature. The correlations for normalized outdoor temperature and specific humidity has been derived from the weather data for five years at Seoul, Daejeon and Pusan. The correlations for normalized temperature are independent of date, while the correlations for specific humidity are linearly dependent on date. The predicted results show fairly good agreement with the measured data. The prediction program is also developed for hourly outdoor dry bulb temperature, specific humidity, dew point, relative humidity, enthalpy and specific volume.

A Study on Estimation of Cooling Load for Effective Control of Ice Thermal Storage System (빙축열 시스템의 효율적인 제어를 위한 냉방부하 예측에 관한 연구)

  • Yoo, Seong-Yeon;Han, Kyu-Hyun;Lee, Je-Myo;Han, Seung-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.2
    • /
    • pp.128-136
    • /
    • 2008
  • It is necessary to estimate the cooling load of the next day for effective control of ice thermal storage system. In this paper, new methodology is proposed to estimate the cooling load using design parameters of building and predicted weather data. Only six input parameters such as sensible heat coefficient and constant, latent heat coefficient and constant, maximum and minimum temperature are necessary to obtain hourly distribution of cooling load for the next day. Two benchmarking buildings(hospital and research institute) are selected to validate the performance of the proposed method, and the estimated cooling loads in hourly and daily bases are calculated and compared with the measured data for E hospital. The estimated results show fairly good agreement with the measured data for both buildings.

Plant Minimum Stable Load (Pmin) Test for Ilijan CCPP

  • Kim, Si Moon;Yun, Wan No;Jang, Cheol Ho;Park, Se Ik
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.2 no.1
    • /
    • pp.83-88
    • /
    • 2016
  • This paper describes the test results of plant minimum stable load (Pmin) for Ilijan Power Plant. The test was conducted on May 13 through 14, 2015 to investigate the plant operating and equipment condition in accordance with "Ilijan Plant Performance Test Procedure on Plant Minimum Stable Load" [1]. This paper also contains the assessment of the impact of Pmin to plant operating parameters and possible technical operating issues when operating at lower loads and to recommend the safe minimum load operation of Ilijan per block. In addition, this paper describes the performance calculation results of efficiency and heat rate depending on the load level.