A Study on the Algorithm for Interconnection of PV System on Power Distribution System Considering Reliability (신뢰도를 고려한 태양광시스템의 배전계통 연계 알고리즘에 관한 연구)

  • Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.4
    • /
    • pp.241-245
    • /
    • 2011
  • In this paper, when photovoltaic (PV) systems are connected to power distribution system, most effective capacity and connected-point of PV system are presented considering power distribution system reliability. The reliability model of PV system is presented considering the duration of sunshine. Also the model of time-varying load and reliability test system bus2 model are used. To simulate the effects of PV system, various cases are selected; (1) base case which is no connection of PV system to power distribution system when faults are occurred, (2) 3MW case which is 3[MW] connection of PV system (3) 4[MW] case, and (4) 20[MW] case which is 20[MW] connection of PV system to the bus of power distribution system. The capacity limit of connected PV system is settled to 14[MW] for all cases except case 4. The reliability for residential, general, industrial, and educational customer is evaluated.

A Study on the Priority Decision for Interconnection of PV System on Power Distribution System considering Customer Interruption Costs (정전비용 고려한 PV시스템의 배전계통 연계 우선순위 결정에 관한 연구)

  • Son, Chang-Nam;Han, Woon-Dong;Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.3
    • /
    • pp.163-168
    • /
    • 2014
  • In this paper, when photovoltaic systems are connected to distribution system, most effective capacity and location of PV system are studied considering customer interruption costs of power distribution system. The reliability model of PV system considering the duration of sunshine, the model of time-varying load and Roy Billinton test system (bus2 model) are used. To simulate the effects of PV system, various cases are selected; (1) base case which is no connection of PV system to power distribution system when faults are occurred, (2) 3MW case which is 3[MW] connection of PV system (3) 4[MW] case, and (4) 20[MW] case which is 20[MW] connection of PV system to the bus of power distribution system. The capacity limit of connected PV system is settled to 14[MW] for all cases except case 4. The reliability and customer interruption costs for residential, general, industrial, and educational customer is evaluated.

The Development of MW Class Concentrating PV system and Grid-connected technique (MW급 집중배치형 태양광 발전시스템 및 계통연계 기술개발)

  • Hwang, J.H.;Ahn, K.S.;Lim, H.C.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1213-1214
    • /
    • 2007
  • In this paper, The reach address is a development of MW class concentrating PV system and grid-connected technique. The objective of research presents a description of MW PV system. This MW PV system will use a domestic technology. It is necessary to develop a module, PCS, and system.

  • PDF

Economic Analysis on VLS-PV System from Sunbelt Region (Sunbelt 지역의 태양광발전 경제성분석)

  • Choi, Bong-Ha;Park, Soo-Uk;Lee, Deok-Ki
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2006.11a
    • /
    • pp.221-225
    • /
    • 2006
  • 본 논문에서는 국내 기술을 활용하여 Sunbelt 지역에 설치된 50kW급 PV 실증 단지에서의 태양광발전을 대상으로 경제성을 분석하였으며, VLS-PV로의 성공적인 확장 가능성을 발견하였다. 이를 바탕으로 2008년부터 2017년까지의 10년 동안 연간 10MW급의 단계적 시스템설치를 통한 최종 100MW급의 VLS-PV 개발을 가정하여 경제성 분석을 수행하였다. 이 과정에서 과거 누적 PV 설비용량과 PV 시스템 가격사이의 관계를 경험곡선을 활용하여 분석하였으며, 이에 기초하여 2017년까지의 PV 모듈 및 PV시스템의 가격을 예상하였다. 현재 실증 단계에서의 발전단가는 567.2원/kWh으로 나타나 국내 태양광발전보다 낮은 발전단가를 보였으며, 가격 하락 효과를 적용한 100MW급의 VLS-PV 시스템 개발시에는 최종 305.4원/kWh이 될 것으로 전망되었다. 향후 기술혁신에 따른 모듈의 효율향상과 시스템 수명의 증가는 경제성을 더욱 향상시킬 것이며, 환경적인 이점 및 정책적인 효과까지 고려할 경우 향후 20년 이내에 기존의 발전원과 비교하여 충분한 경쟁력을 확보할 수 있을 것으로 예상된다.

  • PDF

Economic Analysis on VLS-PV System from Sunbelt Region (Sunbelt 지역의 태양광발전 경제성분석)

  • Choi, Bong-Ha;Park, Soo-Uk;Lee, Deok-Ki;Kim, Seok-Ki;Song, Jin-Soo
    • New & Renewable Energy
    • /
    • v.2 no.4 s.8
    • /
    • pp.86-92
    • /
    • 2006
  • This paper analyses the economics of 50kW PV system installed in Tibet and using domestic technology. We show that this system can be expanded to very large-scale photovoltaic power generation [VLS-PV] system successfully. Based on this result, we conduct the economic analysis of 100MW VLS-PV system designed assuming that it will be installed from 2008 to 2017 in Tibet. In this analysis, future price of PV module and system are estimated based on the methodology of experience curve. In 50kW PV system, the generation cost is calculated at 567.2 won/kWh and this is lower than the one of domestic PV system. In future 100MW VLS-PV system. the generation cost is calculated at 305.4 won/kWh by declining system price. If the lifetime and efficiency of the system goes up, due to future technological improvements, the generation cost can be lowered. Moreover, under the environmental and political effect, VLS-PV system can be as competitive as the conventional energy within 20 years.

  • PDF

Status of Photovoltaics in Korea (국내 태양광발전 산업 현황)

  • Kim, Hyun-Il;Kang, Gi-Hwan;Park, Kyung-Eun;Yu, Gwon-Jong;Suh, Seung-Jik
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2008.11a
    • /
    • pp.196-201
    • /
    • 2008
  • The photovoltaic(PV) industry has been growing around the PV advanced countries such as Japan, Germany, Europe and USA. In recent years, China became a strong performer in the world PV market share, increasing solar cell production rapidly The global photovoltaic (PV) market grew by over 40% in 2007, with approximately 2.3GW of newly installed capacity. The global cumulative installed capacity has reached 9GW. The cumulative installed power of PV system in Korea tremendously increased to 74.7MW at the end of 2007. Up to Sep. 2008 The cumulative installed power of PV system in Korea is approximately 377MW. The value chain of photovoltaic in Korea is creating actively. Thus Korea is predicted to see 800MW of modules installed in 2010. Korea's renewable energy is also targeting to take 5% of the total energy consumption by 2011.

  • PDF

A Study on Economic Evaluation Modeling of MVDC Distribution System for Hosting Capacity of PV System (태양광전원 수용을 위한 MVDC 배전망의 경제성평가 모델링에 관한 연구)

  • Lee, Hu-Dong;Kim, Ki-Young;Kim, Mi-Sung;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.3
    • /
    • pp.1-12
    • /
    • 2021
  • Technologies for an MVDC(medium voltage direct current) distribution system are being considered as an effective alternative to overcome the interconnection delay issues of PV systems. However, the implementation of a DC distribution system might lead to economic problems because of the development of DC devices. Therefore, this paper deals with the scale of a PV plant based on its capacity and proposes hosting-capacity models for PV systems to establish a network to evaluate the feasibility of an MVDC distribution system. The proposed models can be classified as AC and DC distribution systems by the power-supply method. PV systems with hundreds of MW, dozens of MW, and a few MW can be categorized as large-scale, medium-scale, and small-scale models, respectively. This paper also performed modeling for an economic evaluation of MVDC distribution system by considering both the cost of AC and DC network construction, converter replacement, operation, etc. The profit was composed of the SMP and REC rate of a PV plant. A simulation for economic evaluation was done for the MVDC distribution system using the present worth and equal-principal costs repayment method. The results confirmed that the proposed model is a useful tool to evaluate economic issues of a DC distribution system.

Production and Present Status of Photovoltaic Modules in Korea (국내 태양전지모듈 제조기술 및 보급 현황)

  • Kang, Gi-Hwan;Kim, Hyun-Il;Park, Kyung-Eun;Park, I-Jun;Yu, Gwon-Jong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1762-1764
    • /
    • 2005
  • This paper presents manufacturing techniques and distribution status of photovoltaic(PV) module for the success of domestic PV industries. The domestic PV production facilities were about 21MW at the end of 2004. Now it is about 51MW. By 2005 a increase of production facilities expect approximately 70$\sim$80MW. Also domestic PV cumulated installations up to 2004 was about 9,358kW and in 2004 PV system installed around 2,921kW which was increased about 2.8 times compared with last year.

  • PDF

Performance of Photovoltaic Module according to Non-Uniform Azimuth (비동일한 방위각에 의한 PV모듈의 발전성능)

  • Kim, Hyun-Il;Park, Kyung-Eun;Lee, Ki-Ok;Kang, Gi-Hwan;Yu, Gwon-Jong;Suh, Sung-Jik
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.303-308
    • /
    • 2009
  • In 2008, the global photovoltaic(PV) market reached 5.6GW and the cumulative PV power installed totalled almost 15GW compared to 9GW in 2007. Due to a favourable feed-in-tariff, Korea emerged in 2008 as the 4th largest PV market worldwide. PV power installation rose 495.5 percent to 268MW in 2008 compare to 45MW in 2007. However many PV systems are not installed in suitable part which is concerned about geometrical factor. It is generally recognized that the actual output of PV system in field is a function of orientation, tilt angle, irradiance, temperature, soiling and various system-related losses. Thus this paper shows that a experimental result of PV modules(A group) with uniform azimuth angle and PV modules(B group) with non-uniform azimuth angle. As a result, the electrical output of B group is decreased 48.8% as compared with electrical output of A group.