• Title/Summary/Keyword: Louver pattern

Search Result 8, Processing Time 0.02 seconds

Airside Performance of Convex Louver Fin-and-Tube Heat Exchangers

  • Kim, Nae-Hyun;Oh, Wang-Kyu
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.16 no.3
    • /
    • pp.100-107
    • /
    • 2008
  • The heat transfer and friction characteristics of heat exchangers having convex louver fins are experimentally investigated, and the results are compared with those of wave fin counterparts. Eighteen samples (nine convex louver fin samples and nine wave fin samples) which had different fm pitches (1.81 mm to 2.54 mm) and tube rows (one to four) were tested. The convex angle was $11.7^{\circ}$. The j factors are insensitive to fin pitch, while f factors increase as fin pitch increases. The effect of fin pitch on f factor is more significant for the wave fin compared with the convex louver fin. It appears that the complex fin pattern of the convex louver fin induces intense mixing of the flow, and thus reduces the effect of fin pitch. Both the j and f factors decrease as the number of tube row increases. However, as the Reynolds number increases, the effect of tube row diminishes. Comparison of the convex louver fin j factors with those of wave fin reveals that convex louver fin j factors are 18% to 29% higher than those of wave fin. The f factors are 16% to 34% higher for the convex louver fin. The difference increases as fin pitch decreases. Existing correlation fails to adequately predict the present data. More data is needed for a general correlation of the convex louver fin geometry.

Air-side Performance of Louver-Finned Flat Aluminum Heat Exchangers at a Low Velocity Region (저속 영역에서 루버휜이 장착된 평판관형 알루미늄 열교환기의 공기측 전열 성능에 대한 실험적 연구)

  • Cho, Jin-Pyo;Oh, Wang-Kyu;Kim, Nae-Hyun;Youn, Baek
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.12
    • /
    • pp.1681-1691
    • /
    • 2002
  • The heat transfer and pressure drop characteristics of heat exchangers with louver fins were experimentally investigated. The samples had small fin pitches (1.0 mm to 1.4 mm), and experiments were conducted up to a very low frontal air velocity (as low as 0.3 m/s). At a certain Reynolds number (critical Reynolds number), the flattening of the heat transfer coefficient curve was observed. The critical Reynolds number was insensitive to the louver angle, and decreased as the louver pitch to fin pitch ratio (L$_{p}$F$_{p}$) decreased. Existing correlations on the critical Reynolds number did not adequately predict the data. It is suggested that, for proper assessment of the heat transfer behavior, the louver pattern in addition to the flow characterization need to be considered. The heat transfer coefficient increased as the fin pitch decreased. At low Reynolds numbers, however, the trend was reversed. Possible explanation is provided considering the louver pattern between neighboring fins. Different from the heat transfer coefficient, the friction factor did not show the flattening characteristic. The reason may be attributed to the form drag by louvers, which offsets the decreased skin friction at a low Reynolds number. The friction factor increased as the fin pitch decreased and the louver angle increased. A new correlation predicted 92% of the heat transfer coefficient and 90% of the friction factor within $\pm$10%.10%.

A Study on Ventilation Characteristics of Industrial Windows (공장창호의 환기특성에 관한 연구)

  • Piao, Cheng-Xu;Kim, Tae-Hyeung;Ha, Hyun-Chul;Xu, Rong-Bin
    • Journal of Environmental Science International
    • /
    • v.20 no.5
    • /
    • pp.581-587
    • /
    • 2011
  • Industrial natural ventilation systems consist of gravity ventilator, the high/low windows and doors. Especially, the high windows play an important role in the industrial natural ventilation systems. Generally speaking, industrial high windows are divided into 3 types; louver type, $45^{\circ}$ open type and $90^{\circ}$ open type. This study was numerically and experimentally conducted. Three types of windows were tested to know the ventilation characteristics and estimate the ventilation efficiencies. Numerically, computational fluid dynamics software (AIR PAK Ver. 2.0) was used to observe the flow characteristics inside the industrial building and the concentration contours generated by the tracer gas method. Experimentally, the flow visualization technique and the tracer gas method were applied with the model building to characterize the flow pattern inside the model building and to estimate the ventilation efficiencies with the different windows. It was found that $90^{\circ}$ open type window was most effective for the discharge of pollutants from the industrial building. On the other hand, the louver type window was found to be less effective than any other windows.

Optical Characteristics of Transparent Privacy Film with SiO2/SiON Multi-Layer (SiO2/SiON 다층박막 적용 투명보안필름의 광특성 연구)

  • Sung, Hyeong Seok;Kwon, Jin Gu;Chae, Hee Il;Han, Hyeon Seong;Lee, Seong Eui
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.32 no.4
    • /
    • pp.287-295
    • /
    • 2019
  • Privacy films are typically manufactured by combining black resin and transparent louver-shaped patterns. The use of black resin results in excellent light-shielding. However, black resin can reduce the transmittance of privacy films at the front viewing angle. In this study, we applied $SiO_2/SiON$ multi-layer thin films on a privacy film to maintain transmittance at the front viewing angle and improve light-shielding at the side viewing angle. We determined the optimum combination of thicknesses of the $SiO_2/SiON$ multi-layer stacks to increase the overall transmittance; the light shielding could be maximized at the side viewing angle.

A Study on Ventilation Characteristics of Cargo-oil pump room (화물유 펌프실의 환기특성에 관한 연구)

  • 박찬수;조대환
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.24 no.1
    • /
    • pp.134-141
    • /
    • 2000
  • In this study, a scaled model chamber was built to investigate ventilation characteristics of the Under floor Air-conditioning System. Experimental study was performed in model for cargo-oil pump room with inlet and outlet by visualization equipment with laser apparatus. Instant simultaneous velocity vectors at whole field were measured by 2-D PIV system(CACTUS'2000) which adopted two-frame grey-level cross correlation algorithm. The flow pattern reveals the large scale counterclockwise forced-vortex rotation from upside louver to lower scupper toward diagonal corner and also found small eddies at bottom layer

  • PDF

A Study on Tendency of Particles Appearing in Architectural Space Kengo Kuma (쿠마 켄고 건축공간에 나타나는 입자화 경향에 관한 연구)

  • Lim, Taehee
    • Korean Institute of Interior Design Journal
    • /
    • v.23 no.6
    • /
    • pp.14-21
    • /
    • 2014
  • Kengo Kuma is one of the features of the building is 'natural architecture'. He is saying that the construction of the building in which he is seeking is a natural material of construction is only applied to the issue as to whether the material nature, but that the relationship between humans, the environment, natural point of view in his book. Like repeating units are part of the two hundred ninety-four came mainly small ways to create a relationship, or have architectural features make up the sum of his architecture. I present a comprehensive study is reported in terms of that the 'grain' of such a small part of the unit, according to the architecture of Kengo Kuma mainly granulation characteristics of the construction of one of the practical expression studies Kengo Kuma. Is represented as louvers, check pattern, hole, granulation unit such trend, but have become developed in other directions such simple types are combined. Analysis and particle characteristics in terms of the architectural space of Kengo Kuma, serve as the purpose of the present study reveal that each of the features that have a meaning in the construction of any Kengo Kuma.

An Evaluation of Heat Transfer Characteristics of Individualized Fin Type Using Large Scale Model (확대모델을 이용한 특성화된 핀형상의 열전달평가)

  • 윤점열;강희찬;이관수;김무환
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.1
    • /
    • pp.166-175
    • /
    • 1996
  • In recent years, air-conditioning units designed with higher efficiency and more compactness are required due to emphasis on energy efficiency in home electrical appliances. This trend in the air-conditioning industries has accelerated the development of improved heat exchanger with a better performance in heat transfer aspects. In this study, experiments were performed to investigate the shape and configuration of fins affecting on the performance of the conventional fin-and-tube type heat exchanger equipped in a commercial air conditioners. The geometry similtude method was employed to measure the heat transfer coefficient and pressure drop. Experimental results show that this method is very useful to analyze the heat transfer characteristics of the fin-and-tube type heat exchanger. It is also found that the slit fin has better performance than the conventional fin type in the air conditioners. The present results indicate that heat transfer from the fin si influenced by the parameters such as the forming area of the slit fin, the type of interrupted surfaces like a louver or slit, slit patterns and slit raised direction, and it also affects the overall heat exchanger performance.

  • PDF

Evaluation of Internal through Analysis of Airflow and Ventilation of Coal Storage Shed (옥내저탄장 기류 흐름 및 환기량 분석을 통한 내부 유동 평가)

  • Jo, Hyun-Joung;Lee, Jin-Hong
    • Journal of Environmental Impact Assessment
    • /
    • v.31 no.5
    • /
    • pp.334-342
    • /
    • 2022
  • The stringent air environment conservation act forced to build an indoor dome for coal storage. However, it causes some problems due to accumulation of fly ash and harmful substances inside. To solve this problem, this study analyzed the pattern of internal airflow and the amount of ventilation for an indoor coal yard. Overall, the airflow inside the indoor coal yard tended to move to the southwest facing the mountain. In addition, sea-breeze was blowing from the northern louver window facing the sea, where airflow was flowing in. The total flow rate flowing into the indoor coal yard was 918,691 m3/h, and the number of natural ventilation per hour was 0.6 times. Therefore, it is proposed to install a forced ventilation device at the location where internal air flow is concentrated.