• Title/Summary/Keyword: Large generator

Search Result 630, Processing Time 0.019 seconds

A Study on Design of IED for Generator Protection Panel (발전기보호반을 위한 IED의 설계에 관한 연구)

  • Park, Chul-Won;Park, Sung-Wan
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.3
    • /
    • pp.133-138
    • /
    • 2013
  • A large generator is an important role in transferring an electric power to power system. The IEDs of large generator often use microprocessor technology to obtain a digital relay system with a wide range of measuring, protection, control, monitoring, and communication functions. However, all generator protection and control systems in Korea imported from abroad and are being operated. In order to reduce the large expense and improve the reliable operation, development of generator protection and control system by domestic technology is required. This paper deals with the design of the IED of generator protection panel for development of generator protection and control system. The major emphasis of the paper will be on the description of hardware and signal processing test results and measurement accuracy of the prototype IED. By developing of generator IED based on DSP and microprocessor, replacement of the generator protection panel imports are expected to be effective.

Fault Simulation and Analysis of Generator (발전기의 사고 시뮬레이션과 분석)

  • Park, Chul-Won;Oh, Yong-Taek
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.3
    • /
    • pp.151-158
    • /
    • 2013
  • Large generator of power plant is very important. In order to protect large generator from faults, digital protective relay or IED is required. However, all protective relays for generators of the domestic power plant are operated by foreign products. And now, for technological independence from foreign and improvement of import substitution effect, IEDs using domestic technology are being developed. To evaluate performance of developing next-generation power devices, the study of the dynamic characteristics of the power plant, generator system modeling, fault simulation and analysis, should be considered. Specially, To obtain IEEE Standards COMTRADE format for relay operation test, generator system modeling and fault simulation using PSCAD/EMTDC tools must be preceded. Until now, a complete modeling of generator internal windings and fault simulation techniques dose not exist. In this paper, for evaluation performance of relay elements of developing IED, the generator system modeling and various faults simulation using PSCAD/EMTDC tools were performed. And then, the various transient phenomena through obtained relaying signal of developed modeling were analyzed.

A Development Study on the Evaporation Type Large Fresh Water Generator (대형 저압 증발식 조수기 개발)

  • 김병덕;송치성;김경근;김종헌;김용모
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.18 no.4
    • /
    • pp.1-12
    • /
    • 1994
  • Most merchant ships are supplied with the only essential fresh water from a port for economical cargo transportation and the reduction of a nevigation expense. And the deficient fresh water for a voyage is produced by fresh water generator with the various exhaust energy generated in the engine room on a voyage. At present, an evaporation type fresh water generator are extensively used on ship because the operating cost of it is lower than that of a reverse osmosis pressure type. This study introduce a development results on the large evaporation type fresh water generator enable to be used for large merchant ships. It is accomplished the performance test using the developed large fresh water generator.

  • PDF

Characteristics of Electron Beam Extraction in Large Area Electron Beam Generator

  • Woo, Sung-Hun;Lee, Hong-Sik
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.4C no.1
    • /
    • pp.10-14
    • /
    • 2004
  • A large area electron beam generator has been developed for industrial applications, for example, waste water cleaning, flue gas treatment, and food pasteurization. The operational principle is based on the emission of secondary electrons from the cathode when ions in the plasma contact the cathode, which are accelerated toward the exit window by the gradient of the electric potential. Conventional electron beam generators require an electron beam scanning mechanism because a small area thermal electron emitter is used. The electron beam of the large area electron beam generator does not need to be scanned over target material because the beam area is considerable. We have fabricated a large area electron beam generator with peak energy of 200keV, and a beam diameter of 200mm. The electron beam current has been investigated as a function of accelerating voltage and distance from the extracting window while its radial distribution in front of the extracting window has been also measured.

Critical Characteristics Estimation of a Large-Scale HTS Wind Turbine Generator Using a Performance Evaluation System

  • Kim, Taewon;Woo, Sang-Kyun;Kim, Changhyun
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.3
    • /
    • pp.229-233
    • /
    • 2019
  • Large-scale High Temperature Superconducting (HTS) wind power generators suffer from high electromagnetic force and high torque due to their high current density and low rotational speed. Therefore, the torque and Lorentz force of HTS wind power generators should be carefully investigated. In this paper, we proposed a Performance Evaluation System (PES) to physically test the structural stability of HTS coils with high torque before fabricating the generator. The PES is composed of the part of a pole-pair of the HTS generator for estimating the characteristic of the HTS coil. The 10 MW HTS generator and PES were analyzed using a 3D finite element method software. The performance of the HTS coil was evaluated by comparing the magnetic field distributions, the output power, and torque values of the 10 MW HTS generator and the PES. The magnetic flux densities, output power, and torque values of the HTS coils in the PES were the same as a pole-pair of the 10 MW HTS generator. Therefore, the PES-based evaluation method proposed in this paper can be used to estimate the critical characteristics of the HTS generator under high magnetic field and high torque before manufacturing the HTS wind turbines. These results will be used effectively to research and manufacture large-scale HTS wind turbine generators.

A Study on Implementation of Multi-Function Prototype IED H/W for Generator Protection (발전기 보호용 다기능 IED 시제품 H/W 구현에 관한 연구)

  • Kim, Yoon-Sang;An, Tae-Pung;Park, Chul-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.12
    • /
    • pp.74-80
    • /
    • 2013
  • Generator faults does not happen more often than the transmission and substation facility faults. However, impacts on the power system by generator faults are very large. In order to minimize the impact of generator faults, generator protection and control system with high reliability is required. Most of the generator relay in generator protection and control system of large power plant of Korea is operated by imports from abroad. Accordingly, in order to accumulate source technology and increase the import substitution effect, localization of multi-function generator protection IED is being developed. This paper deals with the implementation of a multi-function prototype IED H/W, which can be command and data exchange through communication for measuring, monitoring, protection and control. And the IED specification, various relay elements, measurement elements, communication functions, module function, and test system for the prototype IED H/W are described.

Digital Negative Sequence Relay Algorithm for Detection of Unbalanced State in a Generator (발전기의 불평형 검출을 위한 디지털 역상 계전 알고리즘)

  • Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.198-203
    • /
    • 2013
  • There are conditions that can be unbalanced three phase currents in a large generator by untransposed lines, unbalanced loads, unsymmetrical faults, and open phases. The unbalanced conditions can producing negative sequence components of current that induce two times frequence current in the surface of the rotor, the retaining rings, the slot wedges in the field windings. These rotor currents make the rotor rapidly overheat, so the rotor can cause substantial damage in a very short time. This paper presents the digital negative sequence relay algorithm for unbalanced protection in a generator. The proposed algorithm was tested by using collected current signals on PSCAD/EMTDC considering a hydro turbine based generator control system. It can be seen that the proposed relaying by negative sequence current is useful for detection of unbalanced state of large generator.

Assessment of Insulation Condition in Operating Large Turbine Generator (운전중인 대형 터빈발전기에서 절연상태 평가)

  • 김희동
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.6
    • /
    • pp.324-329
    • /
    • 2004
  • Six stator slot couplers(SSC) and a flux probe sensor installed on the stator winding slots of large turbine generator. Assessment of insulation condition has been based upon the measurements of partial discharge(PD) of stator windings and shorted-turn of rotor windings in operating large turbine generator. The maximum PD magnitude(Qm), normalized quantify number(NQN), PD pattern and shorted-turn were measured using on-line insulation condition monitoring system. The NQN and Qm of slot PD side in the phase A are indicated the highest value in six SSC sensors. Monitoring system results showed that discharge at conductor surface and internal discharge were detected at the surface of stator winding and in voids of the groundwall insulation. Insulation of stator and rotor windings in large turbine generator was judged to be in good condition.

Generator System Modeling for Large Generator Protection (대용량 발전기보호를 위한 발전기 모델링)

  • Park, Chul-Won;Ahn, Joon-Young;Lee, Sang-Seung;Shin, Myong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.121-122
    • /
    • 2006
  • The generator system modeling for large generator protection is a significant portion for the analysis of installed apparatus and development of domestic production. In this paper, MATLAB EMTP/ATP, and PSCAD/EMTDC are used to simulate the transient phenomenon for the faults of generator.

  • PDF

Prediction of 2X Vibration of a Generator Rotor with Asymmetric Shaft Stiffness (비대칭 축 강성을 가지는 발전기 회전자의 2X 진동 예측)

  • Park, C.H.;Kim, Y.C.;Cho, K.G.;Yang, B.S.
    • Journal of Power System Engineering
    • /
    • v.11 no.1
    • /
    • pp.16-19
    • /
    • 2007
  • The large generator rotor used in fossil power plant has the possibility of high 2X vibration due to asymmetric shaft stiffness. The generator rotor is machined into pole faces to reduce stiffness difference and then is tested through 2X vibration measurement when the balancing works are performed in the balancing shop. However, there are many cases of large difference values between 2X vibration in the balancing shop and 2X vibration in site. This paper presents a new method to estimate 2X vibration in site with more accuracy and applied for the retrofit of a fossil 400 MW class deteriorated generator. It shows that the new generator rotor is manufactured with a good 2X vibration characteristics and is operated in a low 2X vibration level although the generator rotor has high 2X vibration in the balancing shop.

  • PDF