• Title/Summary/Keyword: KOFEIS 0301

Search Result 1, Processing Time 0.014 seconds

A Study on the Response Characteristics Depending on Service Life of Ionization Smoke Detector (이온화식연기감지기의 사용기간에 따른 응답특성 연구)

  • Baek, Won-Don;Kim, Shi-Kuk;Ok, Kyung-Jea;Lee, Chun-Ha;Jee, Seung-Wook
    • Fire Science and Engineering
    • /
    • v.22 no.4
    • /
    • pp.61-64
    • /
    • 2008
  • This paper studied on the response characteristics depending on service life of ionization smoke detector. The experimental samples used ionization smoke detectors (360 EA) for over 5 years which were influenced by environment set up with fire objects. The experimental method performed operate and non-operate test according to 'Type Approval and Technical Regulation of Detector (KOFEIS 0301)', for estimate the response characteristics of ionization smoke detector depending on service life. The results showed that their response characteristics were rapidly decreasing when the longer their using period. Accordingly, it is desirable that ionization smoke detector has to be changed for early fire detection when passed their service life.