• Title/Summary/Keyword: Interrupting Current

Search Result 77, Processing Time 0.022 seconds

Analysis of the Principle and Operation Characteristics of an (Igc-Free ELB) Operated by an Active Component (유효성분 동작형 누전차단기(Igc Free ELB)의 원리 및 동작 특성 해석)

  • Choi, Chung-Seog
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.4
    • /
    • pp.456-461
    • /
    • 2010
  • This study compares the criteria of earth leakage breakers (ELB) and analyzes the characteristics of an Igc-free ELB operated by an active component which is not misoperated by capacitive current. Even for the same ELB, the earth leakage current flowing through the human body is estimated to be differ greatly depending on the power source, voltage, location and status of contact, contact time duration, etc. Earth leakage breakers are classified based on the rated voltage, rated sensing current, rated operating time etc. Mounting and demounting of the existing equipment can be performed easily since an $I_{gc}$-free ELB is manufactured with the same structure as a conventional ELB. The rated operating current of a conventional and an $I_{gc}$-free ELB is 30mA, the sensing current is 25mA and the rated non-operating current is 15mA. In the analysis of non-operating current characteristics, the rated non-operating current of 15mA was satisfied up to a 20mA charging current in the conventional ELB, but does not satisfy the rated non-operating current as it operates when the resistive leakage current is lower than 15mA for a charging current exceeding 20mA. Also, the ELB is misoperated without a resistive leakage current when the charging current exceeded 25mA. However, the newly developed $I_{gc}$-free ELB satisfied the rated non-operating current even when the charging current was 60mA. Also, in comparison to the interrupting characteristics, it was confirmed that the charging current satisfying the rated non-operating current of the $I_{gc}$-free ELB was three times higher than that of the conventional ELB.

A Study on the Program Analyzing the Arc Phenomena in Gas Circuit Breaker (가스차단기의 아크현상 해석프로그램에 대한 연구)

  • Choi, Young-Kil;Choi, Sang-Tae;Lee, Kwang-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.12
    • /
    • pp.74-81
    • /
    • 2011
  • A computational approach was developed to understand about the arc quenching process in a gas circuit breaker(GCB). This approach is a program to analyze the gas flow in the breaker. The arc is processed at the same time. The program was used the so-called FLIC method for gas analysis techniques. It was referenced that the arc is interpreted the 'a Simplified Enthalpy Flow Arc Model'. In order to validate about the results of the program, a Auto Puffer GCB was chosen as the test subject. Because, the breaker is the one that arc current is interrupted by using the arc heating. And also, the current interrupting capability can be obtained only owing to the positive utilization(auto puffer) of the clogging phenomenon, without other puffer actions. In this paper, it has been realized that the entire arc quenching process is computerized, which is based on the self-flow current interruption by the auto puffer action. This program, which was verified through experiments, produced good results.

Waveform analysis of leakage current on silicon insulator for various environment condition variation (환경조건변화에 대한 실리콘애자의 누설전류 파형분석)

  • Park, Jae-Jun
    • The Journal of Information Technology
    • /
    • v.7 no.2
    • /
    • pp.69-76
    • /
    • 2004
  • This paper presents the results of spectral analysis about waveforms and leakage current waveforms on contaminated silicon insulators under various environment conditions.(salt fog, clean fog, rain). The larger the leakage current during 200ms, the higher the power spectrum at 60Hz. If contaminated insulators suffers from high salt density fog, the leakage current occurs with high crest value intermittently, results in the low spectrum. Analysis of leakage current data showed that this electrical activity was characterized by transient arcing behavior contaminants are deposited on the insulator surface during salt fog tests. This provides a path for the leakage current to flow along the surface of the insulator. It is important to have an indication of the pollution accumulation in order to evaluate the test performance of a particular insulator. If the drop in surface resistivity is severe enough, then the leakage current may escalate into service interrupting flashover that degrade power quality.

  • PDF

The prospective TRV analysis of 345KV transmission system (345 KV 송전계통의 고유 TRV 해석)

  • Yoon, Jae-Young;Jung, Wee-Sik;Park, Dong-Wook;Min, Suk-Won;Jung, Sang-Jin
    • Proceedings of the KIEE Conference
    • /
    • 1989.07a
    • /
    • pp.397-400
    • /
    • 1989
  • The interrupting capability of circuit breaker to have an effect on stability and reliability of the power system is largely determined by the fault current and prospective TRV (prospective transient recovery voltage). The prospective TRV, which is essentially a system function determined by the elements of the connected circuit, is not constant for a given system location but is affected by a number of variables. Therefore, the purpose of this study is to analyze the prospective TRV of KEPCO's 345KV transmission system by using EMTP (Electro-Magnetic Transients Program) and to compare the calculated values with the standard values in KSB 150 (1976)

  • PDF

A Study on Optimization of the Weil-Dobkes Synthetic Short-Circuit Tests (Weil-Dobke 합성단락시험로의 최적화 연구)

  • 김맹현;고희석
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.6
    • /
    • pp.287-292
    • /
    • 2001
  • This paper deals with the configuration, operating principles, systematic calculation method of parameter and optimization method of test circuit for parallel current injection method, series voltage injection method and hybrid synthetic test method as the method for performance test of circuit breaker with extra high interrupting capacity. The test method depicted above is applied to short-circuit making and breaking test (operating sequence :Os CdOs, Od-CdOs) and out-of-phase tests(operating sequence :Os, CdOs) for performance test of the newly-developed 420kV, 50kA and 800kV 50kV puffer-type gas circuit-breaker according to IEC 60056 and IEC 60427. The testing results, evaluation of equivalence for test and analyzed results are also presented in this paper.

  • PDF

Development of Medium Voltage $SF_6$ Interrupter for RMU ($SF_6$ 가스를 이용한 배전급 RMU용 소호부 개발)

  • Lee, B.W.;Sohn, J.M.;Seo, J.M.;Choe, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.301-304
    • /
    • 2001
  • This paper considers the research of the hybrid interrupter which adopts both rotating arc and thermal expansion technology. The operating principle of this device defends on rapid arc rotation due to the magnetic field created by the fault current through a coil which is mounted on contacts and also relies on the principle of thermal expansion created by arc energy in extinguishing chamber and finally causes pressure rise in expansion volume. In this research, the principle of the interrupting techniques are given and experimental results of hybrid interrupter which is developed by new technology is introduced.

  • PDF

Dynamic Characteristic of Permanent Magnetic Actuator (영구자석형 액추에이터의 동작 특성)

  • Seo, J.H.;Kim, H.K.;Joo, S.W.;Hahn, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2004.04a
    • /
    • pp.24-26
    • /
    • 2004
  • For past decade, medium voltage circuit breakers have used the spring-driven mechanical system for interrupting of electric power. However, these mechanisms have many disadvantages of high power consumption, mechanical control components and electrical switching ones for the coil current. Recently, the vacuum interrupter operated by permanent magnet actuator gives outlook on improved characteristic, higher reliability and cost price reduction as well as the feature of simple structure and few components. This paper deals with the dynamic characteristics of permanent magnet actuator used in the medium voltage distribution systems. Coupled finite element method is used to analysis the dynamic characteristics of permanent magnetic actuator and we compared with those of conventional ones.

  • PDF

Analysis of Dynamic characteristic and design of permanent magnetic actuator (영구자석형 차단기의 특성해석 및 설계)

  • Seo J. H.;Kim H. K.;Joo S. W.;Hahn S. C.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1040-1042
    • /
    • 2004
  • For past decade, medium voltage circuit breakers have used the spring-driven mechanical system for interrupting of electric power. However, these mechanisms have many disadvantages of high power consumption, mechanical control components and electrical switching ones for the coil current. Recently, the vacuum interrupter operated by permanent magnet actuator gives outlook on improved characteristic, higher reliability and cost price reduction as well as the feature of simple structure and few components. This paper deals with the dynamic characteristics of permanent magnet actuator used in the medium voltage distribution systems. Coupled finite element method is used to analysis the dynamic characteristics of permanent magnetic actuator and we compared with those of conventional ones

  • PDF

Analysis of patented technology for deriving eco-friendly road cutter design elements (친환경 도로커터기 설계요소 도출을 위한 특허기술 분석)

  • Jun, Young-Hun;Kim, Kyoon-Tai;Kim, Kyong-Hoon;Ok, Chi-Yeol
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2019.11a
    • /
    • pp.124-125
    • /
    • 2019
  • The use of road cutters in the maintenance of obsolete underground facilities maintains polluting dust, cutting sludge, etc, polluting the air environment, soil, and water, causing civil complaints caused by noise, and consequently interrupting work. Therefore, it is time for eco-friendly pavement cutting technology for fugitive dust and cutting sludge emission management and noise management. This study was based on research by the development of eco-friendly pavement cutting technology in urban areas. In this study, the current state of existing road cutters is investigated and the patented technology analysis of road cutters is conducted to derive the design elements of eco-friendly pavement cutting technology.

  • PDF

Study of Circuit Analysis & Application for Isolated Power System for the Medically Used Rooms (의료실의 비접지 배선방식 회로해석 및 적용에 관한 연구)

  • Oh, Cheong-Hwan;Kim, Young-Bae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.7
    • /
    • pp.87-93
    • /
    • 2005
  • Today, the sciences in medical and nursing fields are becoming progressively more dependent on electrical apparatus for the preservation of life of hospitalized patients. Therefore, it is required more safety medical power distribution system in order to protect patients and physicians more securely from unexpected leakage of current. Especially for the medically used rooms which use life sustaining equipment power should be provided as supplying continuously without interrupting with lowest leakage current. This thesis proposed the reason why Isolation Power System is safety through the circuit analysis and applications.