• 제목/요약/키워드: Interconnected Distribution System

검색결과 125건 처리시간 0.027초

연계형 태양광발전설비의 새로운 오동작 방지 및 재병입 알고리즘 제안 (Algorithm for Preventing Malfunction and Reclosing in Grid-Connected PV Systems)

  • 황민수;전태현
    • 조명전기설비학회논문지
    • /
    • 제26권7호
    • /
    • pp.70-76
    • /
    • 2012
  • In general, the unidirectional power flow is normal in distribution feeders before activation of distributed power source such as PV. However, the interactive power flow is likely to occur in case of the power system under distributed generation. This interactive power flow can cause an unexpected effect on convectional protection coordination systems designed based only on the unidirectional power flow system. When the power line system encounters a problem, the interactive power flow can be a contributed current source and this makes the fault current bigger or smaller compared to the unidirectional case. The effect of interactive power flow is varied depending on the location of the point to ground fault, relative location of the PV, and connection method. Therefore it is important to analyse characteristics of fault current and interactive flow for various transformer connection and location of the PV. This paper proposes a method of improved protection coordination which can be adopted in the protective device for customers in distribution feeders interconnected with the PV. The proposed method is simulated and analysed using PSCAD/EMTDC under various conditions.

전력산업 구조개편에 대비한 적정 TRM 및 ATC 결정에 관한 연구 (A Study of TRM and ATC Determination for Electricity Market Restructuring)

  • 이효상;최진규;신동준;김진오
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권3호
    • /
    • pp.129-134
    • /
    • 2004
  • The Available Transfer Capability (ATC) is defined as the measure of the transfer capability remaining in the physical transmission network for further commercial activity above already committed uses. The ATC determination s related with Total Transfer Capability (TTC) and two reliability margins-Transmission Reliability Capability (TRM) and Capacity Benefit Margin(CBM) The TRM is the component of ATC that accounts for uncertainties and safety margins. Also the TRM is the amount of transmission capability necessary to ensure that the interconnected network is secure under a reasonable range of uncertainties in system conditions. The CBM is the translation of generator capacity reserve margin determined by the Load Serving Entities. This paper describes a method for determining the TTC and TRM to calculate the ATC in the Bulk power system (HL II). TTC and TRM are calculated using Power Transfer Distribution Factor (PTDF). PTDF is implemented to find generation quantifies without violating system security and to identify the most limiting facilities in determining the network’s TTC. Reactive power is also considered to more accurate TTC calculation. TRM is calculated by alternative cases. CBM is calculated by LOLE. This paper compares ATC and TRM using suggested PTDF with using CPF. The method is illustrated using the IEEE 24 bus RTS (MRTS) in case study.

신 에너지전원이 연계된 배전계통의 통합 보호기기의 알고리즘 개발에 관한 연구 (A Study on the Algorithm for Multi-Functional Protection Devices in Distribution Systems with New Energy Sources)

  • 윤기갑;강대훈;노대석
    • 한국산학기술학회논문지
    • /
    • 제10권9호
    • /
    • pp.2253-2260
    • /
    • 2009
  • 본 논문에서는 태양광과 풍력, 연료전지 등의 신 에너지전원(또는 분산전원)이 연계된 배전계통에 있어서 발생 가능한 보호협조의 문제점을 해결하기 위한 통합 보호기기의 알고리즘을 제시한다. 신 에너지전원을 배전계통에 연계함으로써 에너지 효율을 높일 수 있으며, 송배전 선로 건설비용의 절감, 전력 손실 감소, 전압 보상 및 전력 공급의 신뢰도 향상과 같은 많은 장점을 얻을 수 있다. 이러한 많은 장점에도 불구하고 신 에너지전원을 배전 계통에 연계하였을 경우, 전압변동, 고조파, 전력 품질 저하, 단락 용량 증대와 같은 많은 문제점도 발생하여, 이러한 문제점을 해결하기 위한 계통연계 장치 및 보호기기의 필요성이 증대하고 있는 실정이다. 즉, 현재의 배전계통 보호 방식은 단방향 조류방식으로 구성되어 있으나 분산전원의 도입으로 보호 기기가 설치되어 있는 계통에 정상상태임에도 불구하고 역방향의 전력조류가 발생될 수 있다. 따라서 본 논문에서는 이에 대한 새로운 배전 보호 알고리즘을 탑재한 보호기기의 알고리즘을 제시한다.

분산전원 배전계통연계 기술검토 시스템 개발 (The Development of Analysis System for Distributed Generation Interconnected to The Distribution System)

  • 윤기갑;채우규;김상준;박창호;정원욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.531-532
    • /
    • 2006
  • 태양광 발전, 풍력발전 등과 같은 신재생에너지 전원은 주로 수용가에 가까운 배전계통에 연계되어 운영되고 있다. 이들이 도입된 배전계통은 기존의 단방향 공급형태와는 달리 부하와 전원이 혼재되어 운용되고 있으며 양방향 전력공급의 형태로 되기 때문에 전력품질 및 보호협조 측면에서 배전계통에 연계시 복잡한 기술적인 검토가 요구되고 있다. 현재의 경우 수작업이나 EMTDC Tool에 의해 기술검토가 이루어지고 있으나 신뢰성, 정확성, 객관성외 측면에서 다소 미흡한 것이 사실이다. 따라서 한국전력 공사에서 운영하고 있는 신배전정보시스템(NDIS)를 이용하여 8가지 검토항목인 전력용량, 전기방식, 역률, 뱅크역조류, 상시 순시 전압변동, 플리커, 단락용량, 연계가능 용량을 객관적으로 검토할 수 있는 시스템을 개발하였다.

  • PDF

태양광전원이 연계된 배전계통의 최적전압운용 알고리즘 개발 (A Study on Optimal Voltage Algorithm for Distribution System Interconnected with Photovoltaic System)

  • 손준호;노대석
    • 한국산학기술학회:학술대회논문집
    • /
    • 한국산학기술학회 2010년도 춘계학술발표논문집 1부
    • /
    • pp.67-70
    • /
    • 2010
  • 국가차원의 신 재생에너지 활성화 방안에 따라 태양광, 풍력발전 등의 대규모 분산전원 단지의 도입이 이루어지고 있으며, 현재 배전계통의 전압조정 방법은 배전용 변전소의 부하시 탭 절환기(Under Load Tap Changer, 이하 ULTC)와 배전선로의 선로전압조정장치(Step Voltage Regulator, 이하 SVR)로 수용가에 규정전압(220${\pm}$6%)을 만족시키는 전압을 공급한다. 하지만 대규모의 태양광, 풍력 등의 분산 전원이 배전계통에 도입되는 경우, 전력품질[과전압/저전압]의 문제가 발생된다. 본 논문에서는 부하율에 따라 변화된 LDC 정정치를 적용 및 시뮬레이션을 통한 수용가 직하 및 말단의 규정전압(220${\pm}$6%) 즉 207V이하의 저전압, 233V이상의 과전압 여부를 검증함으로써 전력품질을 유지 할 수 있는 태양광전원이 연계된 배전계통의 최적전압운용 알고리즘을 개발하였다.

  • PDF

차세대 전기에너지공급시스템(FRIENDS)에 의한 최적 전압관리방안에 관한 연구 (Optimal Voltage Management Based on the Flexible, Reliable, Intelligent and Energy-conservative Distribution System (FRIENDS))

  • 노대석
    • 한국산학기술학회논문지
    • /
    • 제4권4호
    • /
    • pp.409-417
    • /
    • 2003
  • 본 논문에서는 세계적인 추세에 있는 전력산업의 규제완화와 지구규모적인 환경문제, 전기의존도의 증가, 수용가의 다양한 요구 등 배전계통을 둘러싼 환경변화에 대응할 수 있는 차세대 전기에너지공급시스템의(FRIENDS)의 기본개념과 운용모델을 제안하여, 기존계통에의 도입적용에 대한 구체적인 실현형태를 제시한다. 특히, 배전계통의 목표관리로 수행되고 있는 수용가전압의 전압관리 측면에서 FRIENDS의 운용모델과 기존의 전압관리 운용방안을 비교ㆍ평가하는 수법을 제시하여, FRIENDS의 운용효과를 정량적으로 평가한다. 여기서, 차세대 배전계통은 유연하게 계통구성을 변화시킬 수 있고, 수용가에 멀티메뉴 서비스를 제공할 수 있으며, 각종 설비의 고효율운전을 가능하게 하는 고유연ㆍ고신뢰ㆍ고효율 전기에너지유통시스템을 말한다.

  • PDF

Optimal Algorithms for Voltage Management in Distribution Systems Interconnected with New Dispersed Sources

  • Rho, Dae-Seok;Kook, Kyung-Soo;Wang, Yong-Peel
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권2호
    • /
    • pp.192-201
    • /
    • 2011
  • The optimal evaluation algorithms for voltage regulation in the case where new dispersed sources are operated in distribution systems are studied. Handling the interconnection issues for proper voltage managements are often difficult and complicated because professional skills and enormous amounts of data during evaluations are needed. Typical evaluation algorithms mainly depend on human ability and quality of data acquired, which inevitably cause the different results for the same issue. Thus, unfair and subjective evaluations are unavoidable. In order to overcome these problems, we propose reasonable and general algorithms based on the standard model system and proper criterion, which offers fair and objective evaluation in any case. The proposed algorithms are divided into two main themes. One is an optimal algorithm for the voltage control of multiple voltage regulators in order to deliver suitable voltage to as many customers as possible, and the other is a proper evaluation algorithm for the voltage management at normal and emergency conditions. Results from a case study show that proposed methods can be a practical tool for the voltage management in distribution systems including dispersed sources.

Sensor Nodes Localization for Temperature Distribution Measurement System

  • Ohyama, Shinji;Alasiry, Ali Husein;Takayama, Junya;Kobayashi, Akira
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2005년도 ICCAS
    • /
    • pp.1781-1786
    • /
    • 2005
  • In sensor network systems, all the nodes are interconnected and the positional information of each sensor is essential. To measure the temperature, position detection and communication functions are required. Many sensor nodes are distributed to a measurement field, and these sensors have three main functions: they measure the distance to the other nodes, the data of which are used to determine the position of each node; they communicate with other nodes; and they measure the temperature of each node. A novel range measurement method using the difference between light and sound propagation speed is proposed. The experimental results show the temperature distribution as measured with the aid of the determined positions. The positions of every node were calculated with a PC program. Eight nodes were manufactured and their fundamental functions were tested. The results of the range measurement method, which takes relatively accurate measurements, contribute significantly to the accuracy of the position determination. Future studies will focus on 3-D position determination and on the architecture of appropriate sensors and actuators.

  • PDF

분산전원의 배전계통연계 자동판정 알고리즘 개발에 관한 연구 (A Study on the Evaluation Algorithm of Distribution Systems Interconnected with Dispersed Generations)

  • 노대석;김재언
    • 전기학회논문지
    • /
    • 제56권11호
    • /
    • pp.1910-1920
    • /
    • 2007
  • This paper deals with the optimal evaluation algorithms for voltage regulation in the case where new dispersed generations(DG) are operated in distribution systems. It is very difficult and complicated to handle the interconnection issues for proper voltage managements, because professional skills and enormous amounts of data for the evaluations are required. The typical evaluation algorithms mainly depending on human ability and quality of data acquired, inevitably cause the different results for the same issue, so unfair and subjective evaluations are unavoidable. In order to overcome these problems, the paper proposes reasonable and general algorithms based on the standard model system and proper criterion, which offers the fair and objective evaluations in any case. The proposed algorithms are divided by two main themes. One is an optimal algorithm for the voltage control of multiple voltage regulators in order to deliver suitable voltage to as many customers as possible, and the other is a proper evaluation algorithm for the voltage management at normal and emergency conditions. The results from a case study show that the proposed methods can be a practical tool for the voltage management in distribution systems including dispersed sources.

배전계통에 있어서 선로전압조정장치의 LDC방식에 의한 태양광전원의 수용성 향상 평가알고리즘 (Evaluation algorithm for Hosting Capacity of PV System using LDC Method of Step Voltage Regulator in Distribution Systems)

  • 이세연;이후동;태동현;노대석
    • 한국산학기술학회논문지
    • /
    • 제21권7호
    • /
    • pp.20-28
    • /
    • 2020
  • 최근, 정부의 재생에너지 3020 정책에 따라 태양광전원 등의 신재생에너지전원을 확대하는 보급 사업이 적극적으로 시행되고 있다. 하지만, 대용량의 태양광전원이 배전계통에 연계되는 경우, 수용가전압이 규정전압 범위를 벗어나게 되는 현상이 발생될 수 있어, 태양광전원의 수용성이 저하되어 보급이 지연될 가능성이 있다. 따라서, 본 논문에서는 대용량의 태양광전원이 배전계통에 연계될 경우, 태양광전원의 수용성을 향상시키기 위하여, 선로전압조정장치(step voltage regulator, SVR)의 LDC(line drop compensation, LDC)방식에 의한 태양광전원의 수용성 향상 평가알고리즘을 제시한다. 또한, 배전계통 상용해석 프로그램인 PSCAD/EMTDC를 이용하여, LDC방식의 SVR과 대용량의 태양광 전원 등으로 구성된 복합 배전계통의 모델링을 제시한다. 이를 바탕으로, SVR의 운용방식에 따른 태양광전원의 수용성을 비교·분석한 결과, LDC방식으로 운용하는 경우에는 태양광전원이 6.5[MW]까지 연계되어도 수용가전압이 규정전압 범위 이내로 유지되어, 본 논문에서 제안한 LDC 방식에 의한 태양광전원의 수용성 향상 평가알고리즘의 유용성을 확인하였다.