Inrush Current Elimination for a Three-Phase Off-Line UPS System (3상 오프라인 무정전 전원 시스템의 돌입전류 제거)

  • Bukhari, Syed Sabir Hussain;Kwon, Byung-il
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.944-945
    • /
    • 2015
  • Many sensitive loads always rely on UPS systems to maintain continuous power during abnormal utility power conditions. As any disturbance occurs at the utility side, an off-line UPS system takes over the load within a quarter cycle to avoid a blackout. However, the starting of the inverter can root the momentous inrush current for the transformer installed before the load, due to its magnetic saturation. The consequences of this current can be a reduction of line voltage and tripping of protective devices of the UPS system. Furthermore, it can also damage the transformer and decrease its lifetime by increasing the mechanical stresses on its windings. To prevent the inrush current, and to avoid its disruptive effects, this paper proposes an off-line UPS system that eliminates the inrush current phenomenon while powering the transformer coupled loads, using a current regulated voltage source inverter (CRVSI) instead of a typical voltage source inverter (VSI). Simulations have been performed to validate the operation of proposed off-line UPS system.

  • PDF

Discrete-Time Dynamic Modeling and Start-Up Inrush Elimination Technique for New Push-Pull Quantum Series Resonant Rectifier with Wide Output Voltage Range (출력전압 범위가 넓은 새로운 푸시풀 퀀텀 직렬공진형 정류기를 위한 이산시간 동적 모델링과 기동 돌입전류 제거기법)

  • Moon, Gun-Woo;Yoon, Suk-Ho;Kim, Yong
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.4
    • /
    • pp.100-108
    • /
    • 1997
  • A combined buck and boost push-pull quantum series resonant rectifier(PPQSRR) is newly proposed to achieve a power factor correction without start-up inrush current. Based on the developed dynamic modeling of the proposed rectifier, an inrush current elimination control technique is proposed and the usefullness of the proposed rectifier and control method are verified by computer simulation and experimental results. With the proposed control method, a high power factor and wide range of output voltage can be obtained.

  • PDF

A Cost-Effective, Single-Phase Line-Interactive UPS System that Eliminates Inrush Current Phenomenon for Transformer-Coupled Loads

  • Bukhari, Syed Sabir Hussain;Atiq, Shahid;Lipo, Thomas A.;Kwon, Byung-il
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.3
    • /
    • pp.675-682
    • /
    • 2016
  • Sudden voltage drops and outages frequently disturb the operation of sensitive loads for domestic, commercial, and industrial use. In some cases, these events may even impair the functioning of relevant equipment. To maintain power under such conditions, a UPS system is usually installed. Once a disturbance happens at the grid side, the line-interactive UPS system takes over the load to prevent an interruption. But, due to magnetic saturation of the transformer, a significant inrush current may occur for the transformer-coupled loads during this transition. The generation of such transient currents may in turn decrease the line voltage and activates over-current protecting devices of the system. In this work, a cost-effective, line-interactive UPS system is proposed that eliminates the inrush current phenomenon associated with transformer-coupled loads. The strategy was implemented by connecting a standard current-regulated voltage source inverter (CRVSI) to the secondary winding of the load transformer. During any transient condition at the grid side, the load current is monitored and regulated to achieve either seamless compensation of the load current or complete transferal of load from grid to the inverter. Experimental results were obtained for a prototype under all possible operating conditions so as to validate the performance of the proposed topology.