• Title/Summary/Keyword: ISO 9705

Search Result 63, Processing Time 0.027 seconds

An Experimental Study on Fire Safety Performance of Glass Wool Sandwich Panel (그라스울 샌드위치패널의 화재 안전 성능에 대한 실험적 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl;Min, Se-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.21-27
    • /
    • 2012
  • A real A real scale fire test was performed in accordance with KS F ISO 9705 test method to investigate the combustion characteristics of glass wool sandwich panels. To do this, six kinds of specimens having different density and thickness were examined. The glass sandwich panels were installed inside the room, which had internal dimensions of 2.4 m wide${\times}3.6m$ deep${\times}2.4m$ high. also, combustion characteristic are determined through the exposure of specimens to flame by the propane gas burner has a capacity of 100 kW (10 minutes) and 300 kW (10 minutes) for total 25 minutes of test time. Results of the real sale fire test, it was found that maximum HRR of each specimen was 333.2~365.5 kW, maximum heat flux was 12.4~12.9 kW/$m^2$ And, maximum internal temperature for all specimens was not over $500^{\circ}C$. During the real scale fire test, flash-over didn't occur and the difference by density and thickness of specimen was not found from the results of HRR, heat flux, and internal temperature measurement.

A Room-Corner Fire Model을 적용한 건축내장재의 화재확산 특성 평가(1)

  • Kim, Un-Hyeong
    • Fire Protection Technology
    • /
    • s.24
    • /
    • pp.32-39
    • /
    • 1998
  • A room-corner fire scenario of ISO 9705 with flame spread model developed by Quintiere is applied to the interior finish materials to show the sensitivity of properties derived from AST, E-1321 and ASTM E-1354 is investigated and various range of thermal properties by the author were analyzed in the model. There are including flame heat flux and thermal inertia, lateral flame spread parameter, heat of combustion and effective heat of gasfication. The time for total energy release rate to reach 1MW is examined. Though some areas are neede for improvements, The model appears to predict good results with all the range of input properties and could be

  • PDF

Investigation of the Relationship Between Wall Thermal Conductivity and Inner Room Temperature in Compartment Fires (구획화재에서 벽면의 열전도 계수와 내부 온도의 상관관계 분석)

  • You, Woo Jun;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.17-23
    • /
    • 2018
  • In this study, the relations of the wall thermal conductivity and surface temperature in a compartment fire are investigated using Buckingham Pi theorem. The dimensionless parameters of the previous study are analyzed in order to correlate the dimensionless groups of the heat release rate, the thermal conductivity, the volume of compartment and the convective heat transfer coefficient. In addition the reduced scale of compartment, which has 1/6 size of ISO 9705 Room Corner Tester, is manufactured and the oxygen concentration and the maximum temperature in the space are measured for the gasoline pool fire ($10cm{\times}10cm$, $15cm{\times}15cm$ and $20cm{\times}20cm$). Finally, the criterion of the wall temperature increase are suggested in accordance with the thermal conductivity and the convective heat transfer coefficient. In addition, the dimensionless empirical equation using Buckingham Pi theorem considering the heat release rate are presented suggested. The results of this study will be useful especially for the fire phenomenon investigation of the wall thermal conductivity coefficient and shape in the compartment space.

A Study on the Characteristics of FDS Heat Release Rate Predictions for Fire involving Solid Combustible Materials in a Closed Compartment (밀폐된 구획 내 복합소재 고체 가연물의 연소시 열방출률의 FDS 예측 특성)

  • Hong, Ter-Ki;Roh, Beom-Seok;Park, Seul-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.21 no.11
    • /
    • pp.349-356
    • /
    • 2020
  • The heat release rate (HRR) and fire growth rate of fire for the solid combustibles consisting of multi-materials was measured through the ISO 9705 room corner test, and the computational analysis in a closed compartment was performed to simulate a fire using the heat release rate prediction model provided by a Fire Dynamics Simulator (FDS). The method of predicting the heat release rate provided by the FDS was divided into a simple model and a pyrolysis model. Each model was applied and computational analysis was performed under the same conditions. As the solid combustible consisting of multi-materials, a cinema chair composed mostly of PU foam, PP, and steel was selected. The simple model was over-predicted compared to the predicted heat release rate and fire growth rate using the pyrolysis model in a closed compartment.

Prediction Performance of FDS on the Carbon Monoxide Production in the Under-Ventilated Fires (환기부족 화재에서 일산화탄소 발생에 대한 FDS의 예측성능)

  • Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.25 no.5
    • /
    • pp.93-99
    • /
    • 2011
  • In the present study, a numerical simulation was conducted to estimate the prediction performance of FDS on the carbon monoxide production in the under-ventilated compartment fires. Methane and heptane fires located in the a 2/5 scale compartment based on the ISO-9705 standard room was simulated using FDS Ver. 5.5. Through the comparison between the computed results and the earlier published experimental data, the performance of FDS was estimated on the predictions of the combustion gases concentration in the hot upper layer of the compartment and the effects of CO yield rate on the estimation of CO production at local points were analyzed. From the results, it was known that FDS Ver. 5.5, in which the two-step reaction mixture fraction model implemented, was more effective on the prediction of CO concentration compared to the previous FDS version. In addition, controlling CO yield rate made the predicted CO concentration get closer to the experimental data for the fires of the under-ventilated condition.

Characteristics of Heat Flux in a Compartment Fire - Reduced Scale Test (구획공간 화재의 열유속 특성 - 축소 실험)

  • Kim, Sung-Chan;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.25 no.5
    • /
    • pp.128-133
    • /
    • 2011
  • The present study performs a series of 40 % reduced scale of ISO-9705 fire test to investigate the characteristics of heat flux on the floor level in terms of fire characteristics and location in the compartment. The heat flux was measured with Schmidt-Boelter type heat flux gauge at two locations on the floor level of inside and doorway side of the compartment. Different types of fuel - methane, heptane, toluene, ethanol, polystyrene - were burned in this test series. The measured heat flux inside of the compartment was relatively higher than that of front side as the heat release rate of fire and upper layer temperature increased. The difference of measured heat flux at inside and doorway side increased for high sooty fire. The present study shows that the heat flux distribution at lower layer greatly depend on the thermal radiation from fire and upper layer, not only the upper layer temperature but also various fire characteristics such as composition of combustion gases, soot concentration, ventilation condition and so on.

Analysis on the Results of Measured Concentration of the Combustion Gases Considering Respiration Characteristics in Gasoline Pool Fire (가솔린 풀 화재에서 인체 호흡량 변화를 고려한 연소가스 농도 측정 결과 분석)

  • Choi, Seung Il;Kang, Jung Ki;You, Woo Jun
    • Fire Science and Engineering
    • /
    • v.33 no.4
    • /
    • pp.83-88
    • /
    • 2019
  • This study examined the concentration of combustion gases while considering low ventilation and respiration frequency. A one-quarter-size ISO 9705 room corner test was performed. The concentrations of carbon monoxide and oxygen were measured in each case with the continuous inhalation of combustion gas with low ventilation (2, 6, and 10 LPM) and different respiration frequencies (2 s, 5 s, and infinity). The combustion of a gasoline pool fire in the compartment had a theoretical heat release rate of 5.34 kW. The results show that the deviation of the gas concentrations becomes higher as the low ventilation increases compared to the respiration frequency. In addition, as the respiration frequency increases, the variation in the minimum oxygen concentration is larger than the average value, while in the case of carbon monoxide, the variation in the average value is larger than the maximum value. These results show that the inhalation characteristics of refugees should be considered to investigate fires.

A Validation Study of Temperature Field Predicted by Computational Fire Model for Spray Fire in a Multi-Compartment (다중구획공간내 분무화재시 화재해석모델의 온도장 검증연구)

  • Kim, Sugn-Chan
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.23-29
    • /
    • 2014
  • The present study has been conducted to investigate the validity of the computational fire model and the results predicted by BRANZFIRE zone model and FDS field model are compared with a real scale fire test with spray fire in a multi-compartment. The liquid spray fires fueled with toluene and methanol are used as the fire source and the quantitative measurement of heat release rate is performed in an isolated ISO-9705 compartment with a standard door opening. The temperature field predicted by FDS model showed good agreement with the measurement in the fire room and the corridor, and BRANZFIRE model also gave acceptable result in spite of its simplicity and roughness. The mean temperature predicted by FDS model corresponds with measurement within maximum discrepancy range of 25% and the overall mean value of FDS model matched well with experimental data less than 10%. This study can contribute to establish the limitation and application scope of computational fire model and provide reference data for applying to reliable fire risk assessment.

On the Reliability of the Computational Fire Model Based on the Yield Rate Concept of Combustion Gases (생성율 개념에 기초한 화재모델의 신뢰성에 대한 연구)

  • Kim, Sung-Chan;Ko, Gwon-Hyun;Lee, Seong-Hyuk
    • Fire Science and Engineering
    • /
    • v.23 no.4
    • /
    • pp.130-136
    • /
    • 2009
  • The present study has been performed to evaluate the reliability of the fire field model (FDS version 5.2) with yield rate concept of combustion products. The CO and smoke density predicted by FDS model was directly compared with measurement in a reduced scale ISO-9705 room. The GER (global equivalence ratio) concept was used to characterize the CO and smoke density with ventilation condition in the fire compartment. The FDS model tends to under-predict CO concentration and smoke density than those of measurement for the under-ventilated conditions. Also, the discrepancy between predicted and measured result increases as GER increases. In order to improve the reliability of the fire model for performance evaluation of fire safety, the fire model is necessary to be validated in various fire cases as well as develop detailed physical model.

Application Study of Design Fire Curves for Liquid Pool Fires in a Compartment (구획실 내 액체 풀화재에 대한 디자인 화재곡선 적용 연구)

  • Baek, Bitna;Oh, Chang Bo;Lee, Eui Ju;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.31 no.4
    • /
    • pp.43-51
    • /
    • 2017
  • In this study, new design fire curves were suggested for the utilization in fire simulations. Numerical simulations with the Fire Dynamics Simulator (FDS) were performed for the n-octane and n-heptane pool fires in the ISO 9705 compartment to evaluate the prediction performance of the previous quadratic, exponential design fire curves and newly suggested ones. The numerical results were compared with the experimental temperature and concentrations of $O_2$ and $CO_2$. The numerical results with the previous quadratic and exponential curves showed slow increase and decrease trend than experiments. However, the numerical results with the newly suggested 2 design fire curves showed more similar variation trend in temperature, $O_2$ and $CO_2$ concentrations than the quadratic and exponential curves. It was found that the newly suggested design fire curves can be possibly used in the numerical simulation of fires in a practical respect.