• 제목/요약/키워드: IEEE Std-80

검색결과 24건 처리시간 0.021초

컴퓨터 프로그램을 이용한 접지설계 (Grounding Grid Design Using Computer Program)

  • 최종기;안용호;정길조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.165-169
    • /
    • 2002
  • Grounding grid design of substation and power generating plant has been conducted based on IEEE Std 80 or 665, which provides simple formula to estimate grounding performance such as grounding resistance, max. step and touch voltage. Although these formula are applicable for many situations, they contains many assumptions and consequent limits of application. This paper shows the limits of IEEE formula and the virtue of estimating grounding performance of grid using numerical method or computer program.

  • PDF

IEEE 1500 표준 기반의 효율적인 프로그램 가능한 메모리 BIST (IEEE std. 1500 based an Efficient Programmable Memory BIST)

  • 박영규;최인혁;강성호
    • 전자공학회논문지
    • /
    • 제50권2호
    • /
    • pp.114-121
    • /
    • 2013
  • Systems-On-Chips(SoC)에서 내장 메모리가 차지하는 비중은 비약적으로 증가하여 전체 트랜지스터 수의 80%~90%를 차지하고 있어, SoC에서 내장된 메모리에 대한 테스트 중요성이 증가하고 있다. 본 논문은 다양한 테스트 알고리즘을 지원하는 IEEE 1500 래퍼 기반의 프로그램 가능한 메모리 내장 자체 테스트(PMBIST) 구조를 제안한다. 제안하는 PMBIST는 March 알고리즘 및 Walking, Galloping과 같은 non-March 알고리즘을 지원하여 높은 flexibility, programmability 및 고장 검출률을 보장한다. PMBIST는 최적화된 프로그램 명령어와 작은 프로그램 메모리에 의해 최적의 하드웨어 오버헤드를 가진다. 또한 제안된 고장 정보 처리 기술은 수리와 고장 진단을 위해 2개의 진단 방법을 효과적으로 지원하여 메모리의 수율 향상을 보장한다.

배전용 접지전극의 안전성 분석 장치 구성 (The Construction of Safety Measurement Equipment of Grounding Electrode for Distribution System)

  • 강문호;박영근;장상옥;왕윤찬;이흥호
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.218-221
    • /
    • 2005
  • Grounding electrodes as discharge paths to the earth are normally used to ensure the safety of human body and facilities from the over-voltages in distribution power system, and each grounding mode has a prescribed ground resistance value respectively which is applied by the utilities. As the various electrodes for distribution power system are recently developing to improve the performance of them and resolve the problem of space restriction, it is necessary to measure and investigate the safety of human body of developed electrodes. Therefore, in this paper, we provide briefly a technical comparison of two standards, i.e. IEEE Std 80 and the IEC 479-1, and describe the configuration of safety measurement system which can measure the step voltage and the touch voltage of grounding electrodes based on IEEE Std 80.

  • PDF

수상환경의 대지저항률 및 접지저항 측정의 실험적 연구 (An Experimental Study on Ground Resistivity and Grounding Resistance of Water Environment)

  • 최영관
    • 한국산학기술학회논문지
    • /
    • 제15권4호
    • /
    • pp.2343-2348
    • /
    • 2014
  • 지락사고 시 지락전류에 의한 전위경도 상승으로부터 인체를 보호하기 위하여 발전소의 주 접지망을 구성한다. 이를 위한 접지설계시 일반적으로 IEEE Std-80-2000(한전설계기준 2602)에 의하여 계산한다. 그러나 이는 수상환경에서 적용하기 힘들어 수상태양광의 접지저항 확보를 위한 접지기술이 명확하지 않다. 그런데 500kW 수상태양광의 모듈표면 및 금속덕트에 정전기가 발생하고 있고, 안정적인 접지확보를 위해서는 수상환경의 접지방식에 대한 구체적인 방안이 필요한 실정이다. 따라서 본 논문에서는 수상환경에서 Wenner 4 전극법으로 대지저항률을 조사.분석하였으며, 현재 운영중인 수상태양광의 접지저항을 국제규격(IEEE std-81)에서 제시하는 전압강하법으로 측정 분석하여 안정적인 접지확보를 위한 수상태양광 접지방안을 제시하였다. 수면 1m 수중의 저항률이 ($126.3969[{\Omega}{\cdot}m]$) 하상의 저항률($97.5713[{\Omega}{\cdot}m]$)보다 대체로 높은 것을 측정 분석되었고, 제시한 접지앵커 접지방안은 수상태양광의 더욱 안정된 접지저항 확보를 위해 경제적으로 가장 효과적인 방법으로 판단되며, 향후 수상태양광 발전의 접지방법으로 활용될 것으로 기대된다.

HEMP를 대상으로 한 도전성 재료 혼입 콘크리트 전자파 차폐 벽체 시스템 개발에 관한 실험적 연구 (An Experimental Study on the Development of Electromagnetic Shielding Concrete Wall System Using Conductive Materials for Shielding High-altitude Electromagnetic Pulse(HEMP))

  • 최현준;최현국;김재영;민태범;이한승
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2016년도 추계 학술논문 발표대회
    • /
    • pp.20-21
    • /
    • 2016
  • In this study, the shielding properties of concrete with conductive materials as shielding material for electromagne- tic pulse(EMP) within 10kHz~18GHz were investigated. The shielding effectiveness of specimens were compared with different entrained materials. The shielding effectiveness were determined according to MIL-STD-188-125-1, IEEE-STD-299 at 28 days of concrete curing. The results of shielding effectiveness did not meet the criteria(80dB) severely.

  • PDF

그래프법을 이용한 안전기준에 의한 감전위험성 평가 (An Assessment of Electric Shock Hazard by Safety Criteria Using Graphical Method)

  • 김두현;강동규
    • 한국안전학회지
    • /
    • 제16권3호
    • /
    • pp.53-60
    • /
    • 2001
  • This paper presents a graphical method for hazard assessment of electric shock by safety criteria. For the human body to be safety actual body current should not exceed safety criteria, i.e. allowable body current. The assessment method presented in this paper is based m the safety criteria of the IEEE Standard 80 as well as the IEC 479-1. The hazard can be assessed in terms of alterable touch voltages instead of alterable body current. Thus, the hazard assessment of given electric shock condition is referred to a procedure by which the actual touch voltages are compared with the allowable (safe) touch voltages. Since the IEC 479-1 safety criteria are nonlinear, the graphical method is presented for the hazard assessment. Body current and body voltage are calculated with the allowable touch voltage. A comparison of the safety criteria of two widely accepted standards, i.e. the IEEE Std 80 End the IEC 479-1 is proposed. Also Thevenin equivalent resistance is obtained from electric shock model expressed by two-port earth-grid-foot system. On the basis of calculated results, the allowable touch voltage, the body current and the body voltage we can conduct the hazard or safety assessment and estimate the severity of electric shock.

  • PDF

국제 규격 접지시스템의 국내 적용을 위한 시뮬레이션 기반의 안전도 평가 방안 (Method for Safety-Decision to Apply International Standard Grounding Systems to Domestic Power System by Computer Simulation)

  • 이순;김정훈;박정욱
    • 전기학회논문지
    • /
    • 제57권3호
    • /
    • pp.344-353
    • /
    • 2008
  • To apply the appropriate new grounding system to domestic power system, safety has to be guaranteed under the given circumstances. It is not possible to decide the safety of grounding systems by the experimental test because safety experiments directly relate to the human life and the installed electric machines. Therefore, the computer simulation program to decide the safety of grounding systems based on the IEC standard systems, has to be developed. This paper proposes the computer simulation based method to decide the safety of grounding system with the concepts of touch voltage, step voltage, human resistivity, and applied electric current according to the several conditions of human body located in the corresponding grounding systems. The proposed method is implemented by Matlab/Simulink and Visual C++ programming tools for its visualization.

컴퓨터 프로그램을 이용한 66 KV 변전소 접지설계 (66 kV Substation Grounding Design using Computer Programs)

  • 최종기;곽주식;강연욱;정길조;심응보;김경철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.688-690
    • /
    • 2005
  • 변전소 접지설계를 위한 지침으로서 북미지역과 우리나라에서도 사용되는 IEEE Std 80은 접지저항, 위험전압 및 고장전류 분류계수의 평가를 위한 간단한 수계산식을 제공함으로써 접지성능을 예측계산하도록 하고 있다. 컴퓨터 성능의 비약적인 향상에 따라 수작업이 아닌 컴퓨터 프로그램을 이용하여 변전소 접지설계를 하는 사례가 점차 증가하고 있으며 한국전력공사에서도 자체 제작한 접지설계 프로그램들을 사내 전산망을 통해 배포하고 있다. 본 논문에서는 한전이 해외사업을 일환으로 수행 중에 있는 리비아 전력청 절연협조 진단프로젝트 내용 중 66 kV 변전소 접지설계 사례를 제시한다.

  • PDF

제한된 부지에서 위험전압 검토에 의한 메시 접지설계 (Mesh Grounding Design Based on the Study of Dangerous Voltage on Limited Sites)

  • 손석금;김재철
    • 조명전기설비학회논문지
    • /
    • 제25권11호
    • /
    • pp.91-97
    • /
    • 2011
  • In Korea, characterized in most cases by limited area or high earth resistivity, it is likely to design narrow distances between grounding conductors, with a view to keeping ground resistance and touch voltage below the safety margin values. A new grounding method is suggested, making use of double meshes, to lower touch voltage in a confined area, since it is difficult to lay the plugs under the ground with narrow gaps between them on a limited site. For the presentation of a new model, the suggested grounding system has been analyzed and studied in ground resistance, touch voltage and step voltage, using IEEE Std. 80 calculations and computer simulations.

시간에 따라 변하는 고속철 부하의 고조파 측정, 평가 및 시뮬레이션에 관한 연구 (A Study on the Time-varying Harmonics Measurement, Assessment and Simulation of the High Speed Electric Train Loads)

  • 김경철;진성은;이일무;왕용필;곽노홍;전영수;박상호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.78-80
    • /
    • 2006
  • High speed electric trains have nonlinear loads including converters and inverters for the control synchronous motors. Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. Direct application of the harmonic assessment to the snapshot measurements would result in ambiguous conclusions depending on which instant is sampled. A cumulative probabilistic approach is the most commonly used method to solve time varying harmonics. This paper provides an in depth analysis on harmonics field measurement of the high speed electric train loads, harmonics assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519-1992, and harmonics simulation using EDSA program for the case study.

  • PDF