• Title/Summary/Keyword: Hydro-Generator Stator Winding

Search Result 20, Processing Time 0.03 seconds

Analysis of Correlation Endwinding Breakdown and Insulation Test for Stator winding of Hydro-Generator (수력발전기 고정자권선의 단말부 절연파괴와 절연특성시험과의 관련성 분석)

  • Lee, D.L.;Lee, K.H.;Choi, K.N.;Kim, H.L.;Oh, B.K.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07e
    • /
    • pp.103-105
    • /
    • 2005
  • The test were performed to analyze the cause of endwinding breakdown of hydro-generator which had been in service after being constructed 1971. we conducted insulation diagnostic tests and checked visual inspection and operating condition of protective relays. On the basis of these test results, this paper tried to present the importance of service environment for the generator stator winding.

  • PDF

A Study of On-line Monitoring System for a KEPCO Pumped Storage Generator/Motor

  • Kim Hee-Dong;Ju Young-Ho;Kim Yong-Joo;Cho Kyu-Bock
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.2
    • /
    • pp.90-95
    • /
    • 2006
  • An on-line diagnostic test has been studied and performed for the pumped storage generator/motor. This study aims at reducing the diagnostic cost, minimizing the technical dependency on third party manufactures. Further design of on-line diagnostic system such as shorted-turn of rotor winding, partial discharge (PD) of stator winding and air-gap between stator and rotor for pumped storage generator/motor has been verified. In addition, it needs to be validated on site performance of the developed continuous on-line monitoring system for corresponding tasks for the improvement of the availability & reliability during operation.

A Case Study of On-line PD Measuring System on the Stator Winding for High Voltage Rotating Machine (고전압회전기 고정자권선 운전중 부분방전진단시스템의 현장적용사례 연구)

  • Oh, Bong-Keun;Kang, Dong-Sik;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.109-109
    • /
    • 2010
  • On-line partial discharge(PD) diagnostic system is the most prominent systems to diagnose insulation condition for the high voltage rotating machines. Partial discharge measuring system(PDMS) series with ceramic coupler(PD detecting sensor) installed hydro generator and high voltage motor have been measured the PD data for many years. The trend of PD magnitude in the on-line PD system increased for some machines. These machines showed a same result in the conventional off-line PD test and PD magnitude decreased after stator winding insulation cleaning. This case study show that PDMS has been proved to be good results by comparing PD magnitude with on-line and off-line PD test and it is important to plan the maintenance project for the hydro generator stator winding because PD value was decreased after insulation cleaning.

  • PDF

Development of the On-line Partial Discharge Measuring Sensor and System on Stator Windings for Hydro Generator (수력발전기 고정자권선용 운전중 부분방전 측정 센서 및 시스템 개발)

  • Kang, D.S.;Sun, J.H;Hwang, D.H.;Yun, Y.H.;Seo, I.S.;Shin, B.C.;Klm, H.I.;Lee, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2005.11c
    • /
    • pp.103-106
    • /
    • 2005
  • A lot of R&D on the diagnosis of stator winding insolation for large rotating machines has been carried out since the 1970s. The on-line partial discharge measurement has proved to be an effective technique in the evaluation of the state of stator insulation in high voltage rotating machines. The purpose of this paper is to describe the method of the on-line partial discharge measurement on stator windings for hydro- generator with ceramic sensor and measuring system. We developed ceramic coupling sensor, partial discharge measuring system, terminal box and index parameters.

  • PDF

Development and Site Evaluation of the On-line Partial Discharge Measuring System on the 13 kV Class Stator Windings for Hydro Generator (13 kV급 수력발전기 고정자 권선용 On-line 부분방전 측정 시스템 개발 및 현장적용 평가)

  • Sun, Jong-Ho;Hwang, Don-Ha;Yun, Young-Ho;Shin, Byoung-Chol;Oh, Bong-Keun;Kang, Dong-Sik
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.189-198
    • /
    • 2006
  • In order to improve the reliability of stator windings for hydro generators, it is necessary to detect the defective point and life assessment of the high voltage windings. Especially the on-line partial discharge (PD) test provides the ability to monitor effects, such as slot discharge, internal discharge, and end-winding discharge without interrupting generators, this method has been proven the major testing technology in high voltage rotating machines nowadays. The purpose of this paper is to describe the method of the on-line PD measurement on stator windings for hydro-generator with 13 [kV] class ceramic coupler (CC), on-line PD measuring system, terminal box, and index parameters. Also, the developed PD measuring system and 13 [kV] class CC were installed Daechung-dam generator #2. It was found that this installed sensor and system had good electrical characteristics to detect PD activity during the operating condition with its detection frequency band is between several and several tens MHz.

Analysis of Insulation Characteristics for Stator Winding after Insulation Reinforcement (수력발전기 고정자권선의 절연보강 후 절연특성 분석)

  • Oh, Bong-Keun;Choi, Kyo-Nam;Choi, Hyung-Cheol;Lim, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2006.05a
    • /
    • pp.71-73
    • /
    • 2006
  • Our company(KOWACO) has periodically performed off-line diagnostic test for 14 hydro generators (rated 11 kV over) for 15 years. In this paper, we summarized results of dissipation factor tip-up test and partial discharge test about these generators. Among these, we chose two generators and performed insulation reinforcement (cleaning and varnish Painting). We compared change of insulation condition for the stator winding based upon off-line diagnostic test result before and after repair. Test result shows that insulation condition was improved after insulation reinforcement. This insulation reinforcement has a function to reduce cause of deterioration, so we can know that it extends lifetime of generator and it is a very important factor for stable operation of facilities.

  • PDF

Change of the Insulation Characteristic for the Rotating machine stator winding after insulation reinforcement (회전자 고정자권선의 절연보수후 절연특성변화 연구)

  • Oh, Bong-Keun;Choi, Kyo-Nam;Choi, Hyung-Cheol;Lim, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2006.07e
    • /
    • pp.51-52
    • /
    • 2006
  • Our company(KOWACO) has periodically performed off-line diagnostic test for 14 hydro generators (rated 11 kV over) for 15 years. In this paper, we summarized results of dissipation factor tip-up test and partial discharge test about these generators. Among these, we chose two generators and performed insulation reinforcement (cleaning and varnish painting). We compared change of insulation condition for the stator winding based upon off-line diagnostic test result before and after repair. Test result shows that insulation condition was improved after insulation reinforcement. This insulation reinforcement has a function to reduce cause of deterioration, so we can know that it extends lifetime of generator and it is a very important factor for stable operation of facilities.

  • PDF

Assessment of Insulation Condition for Hydro-generator (대용량 수치발전기의 절연진단에 의한 절연상태평가)

  • Lee, Kwang-Ho;Park, Jong-Jin;Kim, Ki-Won;Lee, Eun-Woong
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1810-1812
    • /
    • 2002
  • This test was performed to assess the insulation deterioration condition of the stator winding of Chung-Ju hydrogenerator #4 and Dae-Cheong hydrogenerator #2 which had been in service after being constructed 1980. The insulation diagnostic tests include resistance polarization index(P.I.) AC current, dissipation factor(Tan ${\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to factory test measurements.

  • PDF

A Technique for Removing Adjacent Induction Noise Mixed with Partial Discharge Signals of High Voltage Rotating Machines (고압 회전기 부분방전 신호에 혼합된 인접상 유도 잡음 제거 기법)

  • Youn, Young-Woo;Yi, Sang-Hwa;Hwang, Don-Ha;Choo, Young-Bae;Kang, Dong-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.335-341
    • /
    • 2009
  • Analysis of the partial discharge signal, a technique to diagnose the stator winding insulation is a key function for the diagnosis of high voltage rotating machines and requires high precision. To satisfy this requirement, various denoising techniques such as filtering and differential methods were proposed. However, these techniques can not eliminate a adjacent induction noise that decreases reliability of the diagnosis. A simple novel denoising algorithm, therefore, is proposed for removing the adjacent induction noise in this paper. The algorithm shows good performance in the real partial discharge signals measured by 13kV class capacitive couplers installed at hydro-generator in Dae-cheong Dam.

Analysis and lest of On-line and off-line PD Testing for High Voltage Rotating Machines Stator Windings using Ceramic Coupler (세라믹 커플러를 이용한 고전압회전기 고정자권선의 On-line 및 off-line 부분방전 특성 시험 및 분석)

  • Oh, Bong-Keun;Kim, Hyun-Il;Kang, Seong-Hwa;Lim, Kee-Joe
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.10
    • /
    • pp.895-900
    • /
    • 2007
  • Partial discharge(PD) test can be performed either when the rotating machine is not operating(off-line) or during normal machine operation(on-line). This paper presents an on-line and off-line PD test on a large hydro-generator and induction motor using the same PD acquisition system(PDAS) and ceramic coupler(CC) sensor. PD signal characteristics of CC sensor proved similar with that of epoxy mica coupler(EMC) sensor as a results of PD test for simulated defect winding and frequency response test. A comparison of on-line and off-line PD test for PD characteristic parameters-phase resolved PD(PRPD), maximum PD value(Qmax) and PD occurrence energy(POE)-indicated that on-line PD test could reliably and effectively diagnose insulation conditions which were verified by off-line PD test.