• Title/Summary/Keyword: Hot-gas bypass

Search Result 29, Processing Time 0.035 seconds

An Experimental Study on the Performance Characteristics of Hot-gas and Liquid Bypass Heat Pump Systems for Capacity Modulation (고온가스 및 액체 바이패스 적용 용량가변 히트펌프의 성능특성에 관한 실험적 연구)

  • Ahn, Jae Hwan;Joo, Youngju;Yoon, Won Jae;Kang, Hoon;Kim, Yongchan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.3
    • /
    • pp.137-142
    • /
    • 2013
  • A small air-conditioner or chiller for a constant temperature bath normally uses a constant speed compressor. The constant speed compressor is relatively inexpensive, but it uses on/off control for capacity modulation. The on/off control has several disadvantages, specifically energy loss and large temperature fluctuation. Continuous operation with a bypass system can be an alternative to on/off control, for capacity modulation. In this study, a heat pump system having a hot-gas bypass and a liquid bypass was adopted. The performance of the bypass-type heat pump was measured, by varying the bypass valve opening. The differences of the COP between the hot-gas bypass and the liquid bypass, in the cooling and heating operations, were within 2% and 1%, respectively. The liquid bypass showed a wider range of capacity control in the cooling operation but the hot-gas bypass showed a wider range of capacity control in the heating operation.

Experimental Study on the Performance Characteristics of Hot-gas Bypass and On-off Defrosting Cycle in a Showcase Refrigeration System (쇼케이스에서 고온가스 바이패스 및 단속운전 제상사이클의 성능특성에 관한 실험적 연구)

  • 김용찬;조홍현;노현일;김영득;박윤철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.6
    • /
    • pp.493-502
    • /
    • 2002
  • During the defrosting process, the temperature in the cabinet of a showcase becomes high as compared to the setting point, which is not desirable for stored foods or materials. It is necessary to develop a more efficient defrosting method to prevent large temperature fluctuation. In this study, the performance of a showcase refrigeration system with three evaporators is investigated by employing a hot-gas bypass defrosting technology in the system under frosting and defrosting conditions. The operating characteristics are compared with those for the on-off defrosting method that has been widely used in current products. As a result, the hot-gas bypass defrosting method shows higher refrigerating capacity and less temperature fluctuation than the on-off method under frosting/defrosting conditions, while the power input is relatively high for the hot-gas bypass method.

An Experimental Study on the Performance Characteristics of a Heat Pump System in the Heating Operation Mode with the Hot Gas Bypass (열펌프의 난방운전시 핫가스 바이패스에 따른 성능 특성에 관한 실험적 연구)

  • Ahn, Jae-Hwan;Joo, Young-Ju;Cho, Il-Yong;Kang, Hoon;Kim, Yong-Chan;Choi, Jong-Min
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.539-543
    • /
    • 2009
  • When the suction pressure of compressor decreases under its limit, the compression ratio is increased causing the malfunctions of compressor. As the method to decrease the compression ratio, hot gas bypass system is usually adopted in heat pump system. In the hot gas bypass system, the discharged gas from the compressor is bypassed into the compressor suction, which causes the increase of suction pressure and the decrease of compression ratio. In this study, the characteristics and performances of the hot gas bypass system in heat pump was investigated experimentally with a variation of the bypass flow rate ratio. With the increase of the bypass rate ratio, the compressor suction pressure was increased, even though the total capacity and COP was decreased. From the analysis of the experimental results, the optimum pressure control algorithm was suggested in this study.

  • PDF

A Study on High Precision Temperature Control of an Oil Cooler for Machine Tools Using Hot-gas Bypass Method

  • Jung, Young-Mi;Byun, Jong-Yeong;Yoon, Jung-In;Jeong, Seok-Kwon
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.33 no.7
    • /
    • pp.1003-1011
    • /
    • 2009
  • This study aims at precise control of oil outlet temperature in the oil cooler system of machine tools for enhancement of working speed and processing accuracy. PID control logic is adopted to obtain desired oil outlet temperature of the oil cooler system with hot-gas bypass method. We showed that the gains of PID controller could be easily determined by using gain tuning methods to get the gain of PID controller without any mathematical model. We also investigated various gain tuning methods to design the gains of PID and compared each control performance for selecting the optimal tuning method on the hot gas bypass method through experiments. Moreover, we confirmed excellent control performance with proposed PI controller gain even though disturbances were abruptly added to the experimental system.

A Study on Performance Improvement of Heat Pump Adopting the Hot Gas Bypass Method (고온냉매 우회방법을 적용한 열펌프의 성능 개선 연구)

  • Kang, Shin-Hyung;Byun, Ju-Suk
    • Journal of Energy Engineering
    • /
    • v.15 no.4 s.48
    • /
    • pp.235-242
    • /
    • 2006
  • This study experimentally investigates the performance improvement of the heat pump by adopting the hot gas bypass method and using the internal heat exchanger according to the automatic defrost test conditions of ISO 5151 This study compares the hot gas bypass method with the time step method, and investigates effect on outdoor coil fan speed when the hot gas of compressor outlet enter outdoor coil inlet after the frost formation. The tests were made for the fan speeds of the outdoor coil controlled at 90, 60 and 30% of the normal speed together with the case of the stationary fan. The performance of the heat pump is evaluated by variables such as COP, heat capacity, and the average COP during the 210 minutes heating mode. Results show that average COP of the hot gas bypass mettled is $2.2{\sim}6%$ higher than that of the time step method. When the outdoor coil fan speed is 60% (780 rpm) of the normal speed, it shows the best COP and heating capacity.

Performance characteristics of hot-gas bypass refrigerator with the variation of operation conditions (운전조건 변화에 따른 hot-gas 바이패스 냉동장치의 성능 특성)

  • Baek, Seung-Moon;Son, Chang-Hyo;Heo, Jeong-Ho;Choi, In-Soo;Yoon, Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.9
    • /
    • pp.1021-1026
    • /
    • 2014
  • In this paper, among various systems applying hot-gas bypass control, outdoor temperature, outlet temperature of water cooler, superheating and subcooling degree, which are the factors affecting the performance of the system bypassing hot-gas to evaporator inlet were analyzed. The main results were summarized as following. Frist of all, performance of refrigeration system bypassing hot-gas to evaporator inlet was affected by outdoor temperature, outlet temperature of water cooler, superheating and sub cooling degree. Thus, providing basic planning date of refrigeration system obtained through optimization of variables is expectable. Thus, providing the basic design data of refrigeration system can be offered by performing the optimization of these variables. Also, the feasibility of this refrigeration system proposed in this paper was obtained by analyzing operating characteristics of the system bypassing hot-gas to evaporator inlet.

Performances of Hot Gas Bypass Type Oil Cooler System (Hot Gas를 이용한 오일쿨러의 성능평가)

  • Lee, Seung-Woo;Yeom, Han-Kil;Park, Kil-Jong
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.26 no.3
    • /
    • pp.73-80
    • /
    • 2009
  • In accordance with the trend for high-speed multi-axes, and the increasing technical sophistication of machine tools, thermal deformation has become an important factor in the accuracy of machine tools. It was analyzed that thermal deformation error accounts for about 70% of all errors made with machine tools. For precise temperature control, both cooling and heating should be implemented. A hot gas bypass type cooling cycle method has a simplified structure and temperature control accuracy to with in ${\pm}0.1^{\circ}C$. In this study, the performances of oil cooler system, including temperature controllability according to hot gas floe and preset temperature sustainability according to temperature load, were tested. It is expected that this study will contribute to the development and performances of oil cooler system, which could minimize thermal errors and improve the quality of precision machine tools.

Temperature Control of Oil Cooler with Hot-gas Bypass (토출가스 바이패스제어에 의한 산업용 냉각기의 온도제어)

  • Byun, Jong-Yeong;Joo, Woo-Jin;Choi, Jun-Hyuk;Moon, Choon-Geun;Yoon, Jung-In;Jeong, Seok-Kwon
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.961-966
    • /
    • 2009
  • This paper presents precise temperature control of oil outlet in an oil cooler with hot-gas bypass control as an industrial refrigerator. The control system was designed for obtaining precise temperature control performance even though abrupt disturbances based on flow rate control of hot-gas bypass. PID controller was adopted in feedback control system. We showed that the gain of PID could be easily determined by using gain-tuning methods without any numerical model. Through some experiments, excellent control performances such as overshoot within 1.7%, steady state temperature error within ${\pm}0.1^{\circ}C$ were established by a simple PI controller. We expect that the system can control the target temperature within error of $0.33^{\circ}C$ under abrupt disturbances.

  • PDF

Characteristics of On-off Control and Hot-Gas Bypass Control in an Industrial Cooler (산업용 냉각기의 온오프 제어와 토출가스 바이패스 제어 특성 비교)

  • Baek, Seung-Moon;Moon, Choon-Geun;Kim, Eun-Pil;Jeong, Seok-Kwon;Yoon, Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.35 no.4
    • /
    • pp.429-435
    • /
    • 2011
  • In this study the operational characteristics of the temperature control system between an on-offemployed cooler and a bypass type cooler is analyzed. Currently an on-off controller employed coolerwhich is the industry's leading type on the market for industrial coolers is used. The new type cooler isused a bypass controller at discharge gas. The COP of the bypass controlled cooler with discharge gas is at least 8% higher than the on-off controlled cooler. The maximum COP difference is about 20%. Based on the results, the bypass control with discharge gas shows the possible temperature control with high precision.