• Title/Summary/Keyword: Hot $SF_6$ gas

Search Result 13, Processing Time 0.023 seconds

A Study on A Hot Gas Velocity Measurement in GCB Using Small-Gap (Small-Gap을 이용한 가스차단기에서의 열가스 속도측정에 관한 연구)

  • Kim, Hong-Kyu;Song, Ki-Dong;Park, Kyong-Yop;Hong, Jung-Pyo;Chong, Jin-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.3
    • /
    • pp.155-158
    • /
    • 2006
  • $SF_6$ gas circuit breakers we widely used for short circuit current interruption in EHV or UHV power system. For a $SF_6$ gas circuit breaker development, the hot gas velocity measurement is necessary during $SF_6$ gas circuit breaker's trip operation. Small-gap flashover characteristics are used for this hot gas velocity measurement. This study sho was the hot gas velocity measurement results during $SF_6$ gas circuit breaker' trip operation.

Analysis of Dielectric Breakdown of Hot SF6 Gas in a Gas Circuit Breaker

  • Kim, Hong-Kyu;Chong, Jin-Kyo;Song, Ki-Dong
    • Journal of Electrical Engineering and Technology
    • /
    • v.5 no.2
    • /
    • pp.264-269
    • /
    • 2010
  • This paper presents the analysis of the dielectric characteristics of a hot $SF_6$ gas in a gas circuit breaker. Hot gas flow is analyzed using the FVFLIC method considering the moving boundary, material properties of real $SF_6$ gas, and arc plasma. In the arc model, the re-absorption of the emitted radiation is approximated with the boundary source layer where the re-absorbed radiation energy is input as an energy source term in the energy conservation equation. The breakdown criterion of a hot gas is predicted using the critical electric field as a function of temperature and pressure. To validate the simulation method, breakdown voltage for a 145kV 40kA circuit breaker was measured for various conditions. Consistent results between the simulation and experiment were confirmed.

Prediction of Hot Gas Behavior in High Voltage Self-blast Circuit Breaker (초고압 복합소호 차단부의 열가스 거동 예측)

  • Kim, Jin-Bum;Yeo, Chang-Ho;Seo, Kyoung-Bo;Kweon, Ki-Yeoung;Lee, Hahk-Sung
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2494-2499
    • /
    • 2007
  • Self-blast circuit breakers utilize the energy dissipated by the arc itself to create the required conditions for arc quenching during the current zero. The high-current simulation provides information about the mixing process of the hot PTFE cloud with $SF_6$ gas which is difficult to access for measurement. But it is also hard to simulate flow phenomenon because the flow in interrupter with high current, $SF_6$-PTFE mixture vapor and complex physical behavior including radiation, calculation of electric field. Using a commercial computational fluid dynamics(CFD) package, the conservation equation for the gas and temperature, velocity and electric fields within breaker can be solved. Results show good agreement between the predicted and measured pressure rise in the thermal chamber.

  • PDF

Steady State Hot Gas Flow Analysis for Nozzle Model Considering Nozzle Ab (노즐용삭을 고려한 노즐모델의 정상상태 열가스 유동해석)

  • Lee, B.Y.;Song, K.D.;Park, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.622-624
    • /
    • 2002
  • This paper describes a method for steady state hot gas flow analysis considering nozzle ablation for the nozzle of $SF_6$ gas circuit breaker. In order to take account of the effect of ablated nozzle material on the hot gas flow. the PTFE mass concentration equation is added to the established equations for hot gas flow analysis. The steady state simulations were carried out under the condition of DC current flows and the results are presented.

  • PDF

Melt Protection Property and Ignition Resistance Property of CaO added AZ91D Mg Alloy (CaO이 첨가된 AZ91D 마그네슘 합금의 발화저항특성 및 용탕보호특성 평가)

  • Lee, Jin-Kyu;Ha, Seong-Ho;Kim, Young-Jig;Jo, Hyung-Ho;Kim, Shae-K.
    • Journal of Korea Foundry Society
    • /
    • v.27 no.3
    • /
    • pp.131-134
    • /
    • 2007
  • [ $SF_6$ ] gas that is used as a protective cover gas for Mg and Mg alloys during melting and casting has extremely high greenhouse effect. CaO added Mg alloys could maintain their original mechanical properties and original abilities such as fluidity and hot tearing susceptibility. The ignition temperature increased with increasing CaO addition under ambient atmosphere and nitrogen atmosphere. The minimum amount of $SF_6$ gas decreased by 0.13 wt%CaO added AZ91D Mg alloy in the sealed condition.

COSMIC RAYS AND GAMMA-RAYS IN LARGE-SCALE STRUCTURE

  • INOUE SUSUMU;NAGASHIMA MASAHIRO;SUZUKI TAKERU K.;AOKI WAKO
    • Journal of The Korean Astronomical Society
    • /
    • v.37 no.5
    • /
    • pp.447-454
    • /
    • 2004
  • During the hierarchical formation of large scale structure in the universe, the progressive collapse and merging of dark matter should inevitably drive shocks into the gas, with nonthermal particle acceleration as a natural consequence. Two topics in this regard are discussed, emphasizing what important things nonthermal phenomena may tell us about the structure formation (SF) process itself. 1. Inverse Compton gamma-rays from large scale SF shocks and non-gravitational effects, and the implications for probing the warm-hot intergalactic medium. We utilize a semi-analytic approach based on Monte Carlo merger trees that treats both merger and accretion shocks self-consistently. 2. Production of $^6Li$ by cosmic rays from SF shocks in the early Galaxy, and the implications for probing Galaxy formation and uncertain physics on sub-Galactic scales. Our new observations of metal-poor halo stars with the Subaru High Dispersion Spectrograph are highlighted.

Prediction of Insulation Capability for Ground Fault to Consider Asymmetry in SF6 Circuit Breaker

  • Oh, Yeon-Ho;Song, Ki-Dong;Kim, Hong-Kyu;Lee, Hae June;Hahn, Sung-Chin
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.5
    • /
    • pp.2046-2051
    • /
    • 2015
  • Currently, most high-voltage gas circuit breakers (CBs) include asymmetrical geometries in the shield, the tank, the hot-gas exhaust, and the connection parts for bushings. For this reason, a 3-dimensional (3-D) analysis of the insulation capability is necessary, rather than a 2-D analysis. However, a 3-D analysis has difficulties due to the computational time and complex modeling. This paper presents a 3-D analysis considering the asymmetry in high-voltage gas CBs and a technique to reduce the calculation time. In the proposed technique, the arc plasma requiring the most computational time is first calculated by a 2-D analysis. Then, the results such as pressure, temperature, and velocity are input as a source for the 3-D analysis. This technique is applied to a 145kV self-blast-type CB and the analysis result exhibits good agreement with the experimental result.

The numerical analysis of gas blast arcs for 800kV GCB (800kV 가스차단기의 아크특성 해석)

  • Chulkov, V.V.;Shin, Y.J.;Park, K.Y.;Song, K.D.;Choi, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 1995.07c
    • /
    • pp.1287-1289
    • /
    • 1995
  • For the analysis of hot gas flow due to arc in puffer type $SF_6$ gas circuit breakers(GCBs), a program has been developed by adding function for arcing to the Fluid-in Cells(FLIC) method, which is often used for a two dimensional compressible flow problems, utilizing a simplified enthalpy flow arc model available for arcing. In this paper, the results of arc modelling for 800kV GCB are presented and compared with that of cold gas flow in the interrupters. It is shown that the nozzle clogging is the dominating factor in the pressure rise of the puffer chamber. It permits to estimate the dielectric strength of interrupters.

  • PDF

Analysis Of Dielectric Recovery Characteristics for $SF_6$ Gas-Blast AFC ($SF_6$아크의 절연회복특성 해석)

  • Song, Gi-Dong;Lee, Byeong-Yun;Park, Gyeong-Yeop;Park, Jeong-Hu
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.51 no.6
    • /
    • pp.273-284
    • /
    • 2002
  • In this paper, computer simulations of the physical Phenomena occurring in the arc region before and after current zero were carried out to evaluate the dielectric recovery characteristics of two types of double-flow nozzles. A commercial CFD Program "PHOENICS" is used for the simulation and the user-coded subroutines to consider the arcing phenomena were added to this program by the authors. The computed results were verified by the comparison with the test results presented by the research group of BBC. In order to investigate the state of the arc region after current zero, the simulation was carried out with four steps. They are cold gas flow analysis, steady state arc simulation, transient arc simulation before current zero, transient hot gas flow simulation after current zero. The semi-experimental arc radiation model is adapted to consider the radiation energy transport and Prandtl′s mixing length model is employed as the turbulence model. The electric field and the magnetic field were calculated with the same grid structure used for the simulation of the flow field. The streamer criterion was introduced to evaluate the dielectric recovery characteristics after current zero. Compared with the results obtained by assuming the current zero state in the former studies, it has been found that the results obtained by considering the state before current zerowere more accurate.

Calculation of Pressure Rise in a Thermal-expansion Type Arc Chamber (열팽창 분사식 가스차단부의 소호실내 압력상승 계산)

  • Choi, Y.K.;Oh, Y.H.;Shin, Y.J.;Park, K.Y.;Kim, H.J.;Choulkov, V.V.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07a
    • /
    • pp.167-169
    • /
    • 1998
  • Recently $SF_6$ gas circuit breakers utilizing the thermal-expansion principle are increasingly used in distribution power system. Active researches and developments have been conducted to reduce the size and weight, and to improve the interrupting performance of the circuit breakers. It was first developed a programme which could show the hot gas flowing into the thermal-expansion arc chamber. This programme, using so-called FLIC method basically, adopted 'Simplified Enthalpy Arc Model' which was somewhat modified to estimate the arc quenching process. The computation by it was compared with the measured results of the pressure rise in the chamber, and both showed fairly good agreement.

  • PDF