• Title/Summary/Keyword: HIF(High Impedance Fault)

Search Result 35, Processing Time 0.023 seconds

A Study on the Detection of LIF and HIF Using Neural Network (신경회로망을 이용한 LIF 및 HIF검출에 판한 연구)

  • Choi, H.S.;Park, S.W.;Chae, J.B.;Kim, C.H.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.924-926
    • /
    • 1997
  • A high impedance fault(HIF) in a power system could be due to a downed conductor, and is a dangerous situation because the current may be too small to be detected by conventional means. In this paper, HIF(High impedance fault) and LIF(Low impedance fault) detection methods were reviewed. No single defection method can detect all electrical conditions resulting from downed conductor faults, because high impedance fault have arc phenomena, asymmetry and randomness. Neural network are well-suited for solving difficult signal processing and pattern recognition problem. This paper presents the application of artificial neural network(ANN) to detect the HIF and LIF. Test results show that the neural network was able to identify the high impedance fault by real-time operation. Furthermore, neural network was able to discriminate the HIF from the LIF.

  • PDF

High Impedance Fault Detection using Wavelet Transform (Wavelet 변환을 이용한 고저항 지락고장 검출)

  • Kim, Hyun;Kim, Chul-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.12
    • /
    • pp.1492-1497
    • /
    • 1999
  • High impedance fault(HIF) is defined as fault the general overcurrent relay can not detect or interrupt. Especially when HIF occur in residential areas, energized high voltage conductor results in fire hazard, equipment damage or personal threat. This paper proposes the model of the high impedance fault in transmission line using the ZnO arrester and resistance to be implemented within EMTP. The performance of the proposed model is tested on a typical 154[kV] korean transmission line system under various fault conditions. Wavelet transform is efficient and useful for the detection of high impedance fault in power system, because it uses variable windows according to frequency. In this paper, HIF detection method using wavelet transform can distinguish HIF form similar fault like arcfurance load, capacitor bank switching and line switching.

  • PDF

A Study on High Impedance Fault Detection using Wavelet Transform and Neural -Network (웨이브렛 변환과 신경망 학습을 이용한 고저항 지락사고 검출에 관한 연구)

  • Hong, Dae-Seung;Ryu, Chang-Wan;Yim, Wha-Yeong
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.3
    • /
    • pp.105-111
    • /
    • 2001
  • The research presented in this paper focuses on a method for the detection of High Impedance Fault(HIF). The method will use the wavelet transform and neural network system. HIF on the multi-grounded three-phase four-wires primary distribution power system cannot be detected effectively by existing over current sensing devices. These paper describes the application of discrete wavelet transform to the various HIF data. These data were measured in actual 22-9kV distribution system. Wavelet transform analysis gives the frequency and time-scale information. The neural network system as a fault detector was trained to discriminate HIF from the normal status by a gradient descent method. The proposed method performed very well by proving the right state when it was applied staged fault data and normal load mimics HIF, such as arc-welder.

  • PDF

The Analysis of the HIF Arc Model of the Distribution System and the Methodology of the Application of Direct Integration Method (배전계통 HIF 아크 모델 분석 및 직접 적분법 적용 방법론에 대한 연구)

  • Ko, Yun-Seok
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.6 no.3
    • /
    • pp.411-416
    • /
    • 2011
  • In distribution system, to enhance the reliability of a HIF (High Impedance Fault) determination, it is very important to obtain the HIF model which can represent accurately the HIF' characteristics. Accordingly, in this paper, the several HIF models which are based on the arc models are reviewed, and then the characteristics of the HIF models are compared from the reviewed results. Finally, a Methodology implementing the arc model is studied based on the direct integration method.

Fault Location Estimation for High Impedance Fault using Wavelet Transform (Wavelet 변환을 이용한 고저항 지락사고 고장점 추정)

  • Kim, Hyun;Kim, Chul-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.8
    • /
    • pp.369-373
    • /
    • 2000
  • High impedance fault(HIF) is defined as a fault that the general overcurrent relay can not detect or interrupt. Especially when HIF occurs in residential areas, energized high voltage conductor results in fire hazard, equipment damage or personal threat. This paper proposes a fault location estimation algorithm for high impedance fault using wavelet transform. The algorithm is based on the wavelet analysis of the fault voltage and current signals. The performance of the proposed algorithm is tested on a typical 154kV korean transmission line system under various fault conditions. From the tests presented in this paper it can be concluded that a fault location estimation algorithm using wavelet transform can precisely calculate the fault point for HIF.

  • PDF

Detection of High Impedance Fault Using Adaptive Neuro-Fuzzy Inference System (적응 뉴로 퍼지 추론 시스템을 이용한 고임피던스 고장검출)

  • 유창완
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.9 no.4
    • /
    • pp.426-435
    • /
    • 1999
  • A high impedance fault(HIF) is one of the serious problems facing the electric utility industry today. Because of the high impedance of a downed conductor under some conditions these faults are not easily detected by over-current based protection devices and can cause fires and personal hazard. In this paper a new method for detection of HIF which uses adaptive neuro-fuzzy inference system (ANFIS) is proposed. Since arcing fault current shows different changes during high and low voltage portion of conductor voltage waveform we firstly divided one cycle of fault current into equal spanned four data windows according to the mangnitude of conductor voltage. Fast fourier transform(FFT) is applied to each data window and the frequency spectrum of current waveform are chosen asinputs of ANFIS after input selection method is preprocessed. Using staged fault and normal data ANFIS is trained to discriminate between normal and HIF status by hybrid learning algorithm. This algorithm adapted gradient descent and least square method and shows rapid convergence speed and improved convergence error. The proposed method represent good performance when applied to staged fault data and HIFLL(high impedance like load)such as arc-welder.

  • PDF

A Modelling Method of a High Impedance Fault in a Distribution System as a Voltage Source using EMTP (EMTP를 이용한 전압원으로의 배전계통 고저항 사고 모델링 기법)

  • Kang, Yong-Choel;Nam, Soon-Ryul;Park, Jong-Keun;Jang, Sung-Il
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.11
    • /
    • pp.1388-1393
    • /
    • 1999
  • A more reliable algorithm for detecting a high impedance fault (HIF) requires fault currents at the relaying point containing information of load condition as well as HIF characteristics. This paper presents a modeling method of an HIF in a distribution system using EMTP. From the voltage and current waveforms of HIF experiment, the voltage-current characteristic is obtained and then piecewise linearized. The proposed method gets several points on the linearized voltage-current curve and then represents nonlinearity as piecewise linear resistances using Transient Analysis of Control Systems (TACS) in EMTP. Thus, an HIF is represented as a voltage source in the first and third quadrants of voltage-current plane. The method is implemented in EMTP and thus the voltage and current at the relaying point can be obtained when an HIF occurs. In this paper, an HIF was simulated on various load conditions and fault conditions in 22.9 [kV] distribution systems.

  • PDF

Fault Detection and Classification of Hi9h Impedance Fault using Wavelet Transform (웨이브렛 변환을 이용한 고저항 지락사고 검출 및 판별)

  • Ko, Y.H.;Kim, C.H.;Kim, H.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1373-1375
    • /
    • 1999
  • High impedance fault (HIF) is defined as fault the general overcurrent relay can not detect or interrupt. Especially when HIF occur in residential areas, energized high voltage conductor results in fire hazard, equiment damage or personal threat. This paper proposes the model of HIF in transmission line using the ZnO arrester and resistance to be implemented within EMTP. Wavelet transform is efficient and useful for the detection of HIF in power system, because it uses variable windows according to frequency. HIF detection method using wavelet transform can distinguish HIF from similar phenomena like arcfurance load, capacitor bank switching and line switching.

  • PDF

A Study on High Impedance Fault Detection using Lifting Scheme (Lifting을 이용한 고저항고장 검출에 관한 연구)

  • Hong, D.S.;Yim, H.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07d
    • /
    • pp.2228-2230
    • /
    • 2002
  • The research presented in this paper focuses on a method for the detection of High Impedance Fault(HIF). The method will use the Lifting and neural network system. HIF on the multi-grounded three-phase four-wires primary distribution power system cannot be detected effectively by existing over current sensing devices. These paper describes the application of lifting scheme to the various HIF data. These data were measured in actual 22.9kV distribution system. Wavelet transform analysis gives the frequency and time-scale information. The neural network system as a fault detector was trained to discriminate HIF from the normal status by a gradient descent method. The proposed method performed very well by proving the right state when it was applied staged fault data and normal load mimics HIF, such as arc-welder.

  • PDF

Performance Evaluation of the Harmonic Parameters for High Impedance Fault Detection in Distribution System (배전계통의 고 임피던스 고장 검출 고조파 변수 성능 평가)

  • Oh, Yong-Taek;Kim, C.J.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.883-885
    • /
    • 1997
  • High impedance fault(HIF) is random in its behavior even in a similar environment. The detection of Ire HIF has focused on the development of algorithms based on harmonic, parameters of the arc currents. However, a fact that proper selection of the harmonic parameters, rather than algorithm selection, is more important is shown in this paper by applying three different performance evaluation methods on two HIF detection algorithms using eight harmonic parameters.

  • PDF