• 제목/요약/키워드: Grounding Electrodes

검색결과 115건 처리시간 0.023초

지능형빌딩의 대단위접지극의 전위간섭에 대한 실증연구 (An experimental research for Potential Interference of a Mesh electrode in Intelligent Building System)

  • 고희석;김주찬;최종규;김맹현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.414-416
    • /
    • 2005
  • This is for investigating the grounding resistance of grounding electrodes, the experiment was performed with model-scale of the grounding system and the scaled model grounding system was to this experiment using a water tank of a stainless steel-hemisphere shape. since mesh electrodes have been widely in the general building, we're tried to analyze that this water tank model and it's simulation as well.

  • PDF

배전전주의 봉상 접지전극 형태별 임피던스 특성의 모델링 (Modeling of Impedance Characteristics of Grounding Electrode for Distribution Line Pole)

  • 심건보;김경철;이형수;박재덕;최종기;박상만
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.694-696
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance characteristics of ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models and transfer function models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

인하도선 길이에 따른 과도접지임피던스 특성 (Effects of Length of Down Conductor on Transient Ground Impedance)

  • 이복희;정동철;이수봉;이태형;정현욱;이규선;이승칠
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2235-2237
    • /
    • 2005
  • This paper presents the transient impedance behaviors of grounding systems to lightning impulse current. The potential rise and effective impulse ground impedance of the test grounding electrodes were measured as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the impulse current shapes and lengths of down conductor, and the inductance of reduce of grounding electrode inductance is an important factor to improve the transient ground impedance.

  • PDF

대규모 그리드 접지전극의 과도접지임피던스의 측정 (The transient grounding impedance measurment of large grid grounding electrodes)

  • 전병욱;이수봉;이봉;이승주;정동철;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 추계학술대회 논문집
    • /
    • pp.69-72
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of large grid grounding system associated with the injection point of impulse current The measurement methods consider two possible errors in the grounding-system impedances: (1) ground mutual resistance due to current flow through ground from the ground electrode to be measured to the current auxiliary, (2) ac mutual coupling between the current test lead and the potential test lead The test circuit was set to reduce the error factors. The transient grounding impedance depends on the rise time and injection point of impulse current It is effective that grounding conductor is connected to the center of the large grid grounding system.

  • PDF

접지계의 써어지 임피던스 (Surge Impedance of Grounding System)

  • 김왕
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제6권5호
    • /
    • pp.45-49
    • /
    • 1992
  • The transient characteristics of grounding systems are very important in the insulation design of electrical installations and depend on the shape and size of electrodes, soil resistivity and the magnitude and wave of the injection current. This paper establishes an algorithm to compute the surge impedance of two or more grounding systems using the Laplace Transformation technique and deals with the analysis of the transient characteristics on grounding systems.

  • PDF

전위상승에 대한 독립접지방식과 공통접지방식의 비교 (Comparison of Individual and Common Grounding Method for Potential Rise)

  • 길형준;김동욱;김동우;이기연;최충석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.41-43
    • /
    • 2006
  • This paper deals with a comparison of individual and common grounding method for potential rise. When a test current flowed through grounding electrode, potential rise was measured and analyzed for grounding method using a electrolytic tank in real time. The grounding electrodes were designed and fabricated with ground rods on a scale of one-eightieth. Potential rises of individual grounding method were higher than those of common grounding method. The distributions of surface potential are dependent on the distance from grounding electrode.

  • PDF

서지전류에 대한 과도접지임피던스의 특성 (Characteristics of Transient Grounding Impedance under Surge Currents)

  • 이덕희;박종순
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권11호
    • /
    • pp.717-723
    • /
    • 1999
  • The transient characteristics of grounding systems play a major role in the protection of power equipments, electronic circuits and info-communication facilities against surges which arise from lightning or ground faults. Electronic devices are very weak against lightning surges injected from grounding systems and can be damaged. The malfunction and damage of electronic circuits bring about bad operation performances, a lot of economical losses, and etc. Therefore, in order to obtain the effective protection measure of electronic devices from overvoltages and lightning surges, the analysis of the transient grounding impedances in essential. One of this work is to examine the transient behaviors of grounding impedances under steplike currents for various grounding systems. And the other of this work is to evaluate the transient behaviors of a grid with rods under impulse currents and to investigate the effect of grounding lead wire. Transient grounding impedances of a grid with rods under impulse current waves have been measured as a parameter of the length of the grounding leads. Z-t, Z-i and V-i curves of transient grounding impedance under impulse current waveforms have been measured and analyzed. It was found that the grounding impedance gives the inductive, resistive and capacitive aspects under steplike current. Transient grounding impedance characteristics were very different with shapes, geometries of ground electrodes. Also, they were dependent on the waveform and magnitude of impulse current.

  • PDF

가변주파수 및 임펄스 전류를 이용한 과도접지임피턴스 분석 (An Analysis Method for the Transient Ground Impedance Using Variable Frequency Current and Lightning Impulse)

  • 조성철;엄주홍;이태형
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2007년도 추계학술대회 논문집
    • /
    • pp.231-234
    • /
    • 2007
  • This paper presents an analysis method of transient ground impedance using the lightning impulse and variable frequency currents. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient impedance of the grounding system. There are some differences between the effective impulse ground impedance which was introduced some papers and the transient ground impedance. The transient ground impedance measured from the peak value of impulse voltage and the peak value of impulse current is more reliable than the effective impulse ground impedance.

  • PDF

주파수 영역에서 봉상전극의 접지임피던스 특성 (Ground ing Impedance Characteristics of Ground Rods in frequency Domain)

  • 이형수;심건보;김경철;최종기;박상만
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.248-253
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance of various rod-type ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

형상이 다른 접지전극에 접속된 심매설 봉상 접지전극의 임펄스접지임피던스 특성 (Impulse Ground Impedances of a Deeply Driven Ground Rod Combined with Different Shape Grounding Electrodes)

  • 이복희;이수봉;장근철
    • 조명전기설비학회논문지
    • /
    • 제19권2호
    • /
    • pp.63-68
    • /
    • 2005
  • 본 논문은 메쉬 접지전극이나 침부 매설지선이 연결된 심매설 봉상 접지전극의 실효임펄스접지임피던스의 특성을 다루었다. 시험용 접지전극의 전위상승은 인가된 임펄스 전류의 상승시간의 함수로 측정되었고, 실효임펄스접지 임피던스는 산출되었다. 심매설 봉상 접지전극의 임펄스접지임피던스는 임펄스 전류의 상승시간에 강하게 의존하며 메쉬 접지전각과의 병렬연결에 의해 확연히 감소하였다.