• 제목/요약/키워드: Ground-source heat pump system

검색결과 228건 처리시간 0.027초

지열 시스템의 도입이 지중온도환경에 미치는 영향에 대한 해석적 검토 (Numerical Analysis of the Effect of Ground Source Heat Pump Systems on the Underground Temperature)

  • 남유진
    • 설비공학논문집
    • /
    • 제25권8호
    • /
    • pp.427-431
    • /
    • 2013
  • Ground heat pump systems utilize the annually stable underground temperature to supply heat for space heating and cooling. The underground temperature affects not only the underground ecosystem, but also the performance of these systems. However, in spite of the widespread use of these systems, there have been few researches on the effect of the systems on underground temperature. In this research, case studies with numerical simulation have been conducted, in order to estimate the effect of ground heat pump systems on underground temperature. The simulation was coupled with the ground water-ground heat transfer model and the ground surface heat transfer model. In the result, it was found that the underground change depends on the heat transfer from the ground surface, the heat exchange rate, and the heat conductivity of soil.

한랭지(몽골) 지열 히트펌프 시스템의 난방 성능 분석 (Heating Performance of Geothermal Heat Pump System Applied in Cold Climate Region(Mongolia))

  • 손병후;최재호;민경천
    • 설비공학논문집
    • /
    • 제27권1호
    • /
    • pp.31-38
    • /
    • 2015
  • Geothermal heat pump (GHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. These systems use the ground as a heat source in heating mode operation and a heat sink in cooling mode operation. The aim of this study is to evaluate the heating performance of the GHP system for a residential building ($420m^2$) in Ulaanbaatar, Mongolia. In order to demonstrate the feasibility of a sustainable performance of this system, we installed the water-to-water geothermal heat pump with ten vertical ground heat exchangers and measured operation parameters from October 19, 2013 to March 26, 2014. The results showed that the entering source temperature of brine from the ground heat exchangers was in a range of the design target temperature of $-10^{\circ}C$ for heating. For total values of the representative results, the ground heat exchangers extracted heat of 53.51 MWh from the ground. In addition, the GHP system supplied heat of 83.55 MWh to the building and consumed power of 30.27 MWh. Consequently, the average heating seasonal performance factor ($SPF_h$) of the overall system was evaluated to be 2.76 during the measurement period of the heating season.

건물 기초를 이용한 지중열 공조시스템의 개발에 관한 연구 (2) (A Study on Development of a Ground-Source Heat Pump System Utilizing Pile Foundation of a Building)

  • 오오카 료죠;황석호;세키네 켄타로;시마와키 요스케;남유진
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.155-160
    • /
    • 2005
  • To purpose of this research is to develop the numerical model for simulating performance of ground heat exchanger with high prediction accuracy. This paper describes the development of a numerical model that simulates the heat transfer between ground and circulation water in ground heat exchanger. Furthermore, we propose the estimating technique of soil properties, such as thermal conductivity, heat capacity and hydraulic conductivity, based on ground investigation. Comparison between experiment and numerical analysis based on the model developed above was conducted under the condition of the experiment in 2004. The result of analysis agreed well with the experimental result.

  • PDF

국내 지중열전도도 측정 방법의 한계 및 개선 방향 (Limitations and improvement of the in situ measurements of ground thermal conductivity in Korea)

  • 심병완
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2011년도 춘계학술대회 초록집
    • /
    • pp.195.2-195.2
    • /
    • 2011
  • The borehole heat exchanger of Geothermal Heat Pump (GHP) system should be sustainable and cost effective for long term operation. To guaranty the performance of the system thermal Response Tests (TRTs) with simple recommended procedures have been applied in many countries. Korea government developed a standard TRT procedure in order to control the quality on GHP projects. In the TRT procedure interpretation method has a rule that data set has to be interpreted by the line source model(LSM). The LSM employes some assumptions that surrounding medium is homogeneous and the line source is infinite and constant heat flux, however real ground condition is unisotropic and heterogeneous, and showing regional or local ground water flows in many cases. We need to develope improved evaluation models to estimate accurate ground thermal conductivity with respect to geological and influence of ground water because current TRT standard test procedure has limitations to be applied for every locations and system. This study surveyed the uncertainty of the thermal parameters from the interpretation method considering different evaluation period. The interpretation of 208 TRT data sets represents limitations of LSM application that some obtained ground thermal conductivities are statistically unstable and convergence time of ground thermal conductivity over test period shows trends responding the length of test period. This evaluation study will be helpful to provide some effective procedure for the thermal parameter estimation and to complement current TRT standard procedure.

  • PDF

태양열 및 지열 이용 히트펌프 시스템의 성능예측 시뮬레이션에 관한 연구 (Study on the Performance Prediction Simulation of the Heat Pump System using Solar and Geothermal Heat Source)

  • 남유진;까오신양
    • 한국태양에너지학회 논문집
    • /
    • 제34권3호
    • /
    • pp.75-81
    • /
    • 2014
  • Recently, the use of renewable energy has been attracted due to the interest in energy-saving and the reduction of CO2 emission. In order to reduce the energy consumption of the cooling and the heating in the field of the architectural engineering, heat pump systems using renewable energy have been developed and used in various applications. In many researches, integrated heat pump systems are suggested which use solar and geothermal heat as the heat source for cooling and heating. However, it is still difficult to predict the performance of the systems, because the characteristic of heat exchange in each system is complicated and various. In this system, the performance prediction simulation of the heat pump was developed using a dynamic simulation model. This paper describes the summary of the suggested systems and the result of the simulation. The average temperature of the heat source, heating loads and COP were calculated with the cases of different local conditions, different system composition and different operation time by TRNSYS 17.

이중 축열조를 갖는 축열식 지열원 히트펌프시스템의 노인공동주택 적용 분석연구 (Application analysis to a shared apartment house of heat storage type GSHP system with dual storage tank)

  • 박종우;이상훈;조성환
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.27-32
    • /
    • 2008
  • The present study has been conducted economic analysis of heat storage type ground source heat pump system(HSGSHP) and normal ground source heat pump (GSHP) which are installed at the same building in the shared an apartment house. Cost items, such as initial cost, annual energy cost and maintenance cost of each system are considered to analyze life cycle cost (LCC) and simple payback period (SPP) with initial cost different are compared. The initial cost is a rule to the Government basic unit cost of production. LCC applied present value method is used to assess economical profit of both of them. Variables used to LCC analysis are prices escalation rate and interest rate mean values of during latest 10 years. The LCC result shows that HSGSHP (1,050,910,000won) is more profitable than GSHP by 68.9% initial cost. And SPP appeared 3.0 year overcome the different initial cost by different annual energy cost.

  • PDF

업무용 건물의 지열 히트펌프 시스템에 대한 성능 예측 (Performance Prediction on the Application of a Ground-Source Heat Pump(GSHP) System in an Office Building)

  • 손병후;권한솔
    • 설비공학논문집
    • /
    • 제26권9호
    • /
    • pp.409-415
    • /
    • 2014
  • Ground-source heat pump (GSHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy efficiency. These systems use the ground as a heat source and the heat sink for cooling mode operation. The purpose of this simulation study is to evaluate the performance of a hypothetical GSHP system in an office building and to assess the energy saving effect against the existing HVAC systems (boiler and turbo chiller). We collected monthly energy consumption data from an actual office building ($32,488m^2$) in Seoul, and created a model to calculate the hourly building loads with EnergyPlus. In addition, we used GLD (Ground Loop Design) V8.0, a GSHP system design and simulation software tool, to evaluate hourly and monthly performance of the GSHP system. The energy consumption for the GSHP system based on the hourly simulation results were estimated to be 582.6 MWh/year for cooling and 593.2 MWh/year for heating, while those for the existing HVAC systems were found to be 674.5 MWh/year and 2,496.4 MWh/year, respectively. The seasonal performance factor (SPF) of the GSHP system was also calculated to be in the range of 3.37~4.28.

지열-태양열원 복합시스템의 성능평가에 관한 연구 (A Study on the Performance Evaluation of Hybrid Energy System with Geothermal and Solar Heat Sources)

  • 황인주;우남섭;이홍철
    • 설비공학논문집
    • /
    • 제18권3호
    • /
    • pp.279-286
    • /
    • 2006
  • The present study concerns the annual performance evaluation of a hybrid-renewable energy system with geothermal and solar heat sources for hot water, heating and cooling of the residential buildings. The hybrid energy system consists of ground source heat pump of 2 RT for cooling, solar collectors of $4.8m^2$, storage tank of 250 liters and gas fired backup boiler of 11.6 kW. The averaged coefficients of performance of geothermal heat pump system during cooling and heating seasons are measured as 4.1 and 3.5, respectively. Also solar fraction for hot water is measured as 35 percent. Overall, the results shows that the hybrid-renewable energy system satisfactorily operated under all climatic conditions.

주거용 건물의 지하수 이용 지열 히트펌프 시스템의 난방성능 특성에 관한 연구 (Research on the heating performance of SCW heat pump system for residential house)

  • 김주화;김주영;홍원화;안창환
    • 한국주거학회:학술대회논문집
    • /
    • 한국주거학회 2008년도 춘계학술발표대회 논문집
    • /
    • pp.431-435
    • /
    • 2008
  • Geothermal heat pump system using standing column wells as their ground heat exchanger can be used as a highly efficient source of heating and cooling in massive buildings. But there is no case of a small scale residential house. So this study estimated heating coefficient of performance(COP) of geothermal heat pump system using standing column well type which is excellent in heat recovery in the residential house. As a result of analysis, The COP of heat pump is over average 6 and is excellent. And in consequence of making a comparative study according to the bleeding, the cop is higher in the case of bleeding. Therefore, bleeding affects the performance of the system. This study has shown performance result that stands on actual data. Therefore, this study provides ground data that needs when a low capacity of system designs for a residence with confidence elevation.

  • PDF

Life cycle cost analysis and smart operation mode of ground source heat pump system

  • Yoon, Seok;Lee, Seung-Rae
    • Smart Structures and Systems
    • /
    • 제16권4호
    • /
    • pp.743-758
    • /
    • 2015
  • This paper presents an advanced life cycle cost (LCC) analysis of a ground source heat pump (GSHP) system and suggests a smart operation mode with a thermal performance test (TPT) and an energy pile system constructed on the site of the Incheon International Airport (IIA). First, an economic analysis of the GSHP system was conducted for the second passenger terminal of the IIA considering actual influencing factors such as government support and the residual value of the equipment. The analysis results showed that the economic efficiency of the GSHP system could be increased owing to several influential factors. Second, a multiple regression analysis was conducted using different independent variables in order to analyze the influence indices with regard to the LCC results. Every independent index, in this case the initial construction cost, lifespan of the equipment, discount rate and the amount of price inflation can affect the LCC results. Third, a GSHP system using an energy pile was installed on the site of the construction laboratory institute of the IIA. TPTs of W-shape and spiral-coil-type GHEs were conducted in continuous and intermittent operation modes, respectively, prior to system operation of the energy pile. A cooling GSHP system in the energy pile was operated in both the continuous and intermittent modes, and the LCC was calculated. Furthermore, the smart operation mode and LCC were analyzed considering the application of a thermal storage tank.