A Simulation of Lightning Faults Reducing Effects on the 154 kV Transmission Tower by Auxiliary Grounding (보조접지선 시공에 의한 송전선로의 내뢰성 향상효과 모의)

  • Kwak, Joo-Sik;Shim, Jeong-Woon;Shim, Eung-Bo;Choi, Jong-Gi
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1843-1846
    • /
    • 1997
  • This paper describes the fault reducing effects of the 154 kV transmission tower by auxiliary grounding from the top of the tower to ground. The grounding surge impedance of the auxiliary grounding system is calculated by CDEGS(:Current Distribution Electromagnetic Interference Grounding and Soil Structure Analysis), and the critical lightning back flashover current and arcing horn dynamic characteristics are simulated by EMTP/TACS(:Electromagnetic Transient Program/Transient Analysis of Control Systems). The calculated results of total LFOR(Lightning Flashover Rate) shows that the LFOR can be reduced from 5.2(count/100km. year) to 3.4 by auxiliary grounding on the 154 kV transmission tower with one ground wire shielding system.

  • PDF

A Simulation Program for Protection Coordination in the Power Distribution System with Distributed Generators (분산전원 연계 배전계통의 보호협조 정정 프로그램 개발)

  • Kim, Sang-Ok;Seo, In-Yong;Lee, Heung-Ho;Rho, Dae-Seok
    • Journal of the Korea Society for Simulation
    • /
    • v.22 no.1
    • /
    • pp.1-8
    • /
    • 2013
  • A higher penetration of renewable energy sources and adoption of renewable portfolio standard(RPS), the penetration of distributed generators(DGs) into power distribution network is becoming a threat for the safe operation of distribution network. The ground fault current of DGs can cause parasitic trip and mal-trip of protective device in the power distribution network. KEPRI has developed a simulation program for current setting of protective devices in DGs connected distribution network. In this study, we analyzed fault currents of a sample network in two cases, i.e. case 1 is for no DG connection, case 2 for a DG connection. We performed protection coordination for relays installed in the network and analyzed the contribution of a DG.

The Development of Fault and Lightning Stroke Section Location System for Overhead Transmission Line (가공지선 전류 검출 방식의 송전선 사고 및 낙뢰 구간 검출 시스템 개발)

  • Lee C.Y.;Kim J.N.;Oh D.J.;Ha C.W.;Kim D.W.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.584-586
    • /
    • 2004
  • This paper deals with the development of on-line fault and lightning stroke section locating system for branched overhead transmission line. The section locating algorithm of this system i3 by analyzing the distribution pattern of current flowing through the overhead ground wire. It composes of three parts; current sensors, local remote terminal unit(RTU) and analysis program at surveillance tenter. Double Rogowski coil sensor having integrating amplifier was designed as current sensor. In order for current pattern analysis, the transmitted waves from each sensor wert synchronized by GPS tim c clock in RTU. While, lightning stroke location are judged only by polarity information of lightning currents. This design has a benefit in simplicity of signal processing unit of RTU.

  • PDF

Analysis of the Recovery Behavior of SFCL According to Reclosing Operation (재폐로 동작에 따른 초전도 한류기의 회복성능 분석)

  • Ha, Kyoung-Hun;Cho, Yong-Sun;Kim, Deog-Goo;Choi, Hyo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.5
    • /
    • pp.1073-1077
    • /
    • 2011
  • The breaking capacity of circuit breakers could be no more increased in the electric power system. This is because the fault current increases due to continuous increases in electric power demand and facilities. To solve the problem, it is necessary to come up with an alternative. The superconducting fault current limiter (SFCL) has received an attention among various alternatives. The SFCL effectively reduce a fault current in cooperation with a power circuit breaker. A various types of the SFCL are suggested and a study on them have been progressed. As a result of it, the SFCL can be applyed to the electric power system in the near future. But, a study on recovery behaviors of the SFCL is not enough for applying to the electric power system. If the superconducting elements do not completely recover to the superconducting state after fault operation, it might be a breakdown of the superconducting elements due to heavy power burden and it gives an bad influence on the working of other electric devices. Additionally, the distribution power system has reclosing operation such as open-0.3sec-closed/open-3min-closed/open procedure. So we need to study more about improvement of the recovery behaviors of the SFCL. In this paper, we analyzed the recovery behaviors of a flux-coupling type SFCL according to reclosing operation when a single line-to-ground fault occurred and we compared recovery behaviors of the SFCL with and without a neutral line between secondary reactors and superconducting elements. Also, the flux-coupling type SFCL has advantageous for increases of capacity by controlling the variation in turn ratios between two reactors. Consequently, when the number of turns of the secondary reactors increased, the power burden of the superconducting elements was bigger due to the increase of impedances of the secondary reactors. To distribute the power burden, two superconducting elements connected in series and the balanced quenching of the superconducting elements was induced by connecting a neutral line.

Earth Resistivity Modelling and Grounding Resistance Estimation for Yongdam Dam Power Station Grounding Design (용담댐 발전소 접지설계를 위한 대지비저항 모델링 및 접지저항 추정)

  • Oh, Min-Hwan;Kim, Hyoung-Soo;Kim, Jong-Deug
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1188-1191
    • /
    • 1998
  • Detailed estimation of subsurface resistivity distribution and accurate estimation of actual fault current coming into the grounding system are indispensible to optimun grounding system design. Especially, it is essential for efficient grounding design to estimate subsurface resistivity distribution quantitatively and logically. Accurate estimation of subsurface resistivity distribution has an absolute influence on calculating touch voltage, step voltage and ground potential rise (GPR) which are related with grounding design standard for human safety. In this study, thirty-three electrical sounding surveys were made in Yongdam Power Station to obtain detailed subsurface resistivity distribution and the sounding data were interpreted quantitatively using multi-layered model. The results of the quantitative resistivity models were adopted practically to calculate grounding resistance values. Analytical asymptotic equations and CDEGS program were used in grounding resistance calculation and the results were compared and reviewed in the study.

  • PDF

Analysis of Sequence Impedances of 345kV Cable Transmission Systems (실계통 345kV 지중송전선 대칭좌표 임피던스의 해석)

  • Choi, Jong-Kee;Ahn, Yong-Ho;Yoon, Yong-Beum;Oh, Sei-Ill;Kwa, Yang-Ho;Lee, Myoung-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.7
    • /
    • pp.905-912
    • /
    • 2013
  • Power system fault analysis is commonly based on well-known symmetrical component method, which describes power system elements by positive, negative and zero sequence impedance. In case of balanced fault, such as three phase short circuit, transmission line can be represented by positive sequence impedance only. The majority of fault in transmission lines, however, is unbalanced fault, such as line-to-ground faults, so that both positive and zero sequence impedance is required for fault analysis. When unbalanced fault occurs, zero sequence current flows through earth and skywires in overhead transmission systems and through cable sheaths and earth in cable transmission systems. Since zero sequence current distribution between cable sheath and earth is dependent on both sheath bondings and grounding configurations, care must be taken to calculate zero sequence impedance of underground cable transmission lines. In this paper, conventional and EMTP-based sequence impedance calculation methods were described and applied to 345kV cable transmission systems (4 circuit, OF 2000mm2). Calculation results showed that detailed circuit analysis is desirable to avoid possible errors of sequence impedance calculation resulted from various configuration of cable sheath bonding and grounding in underground cable transmission systems.

Strong ground motion characteristics of the 2011 Van Earthquake of Turkey: Implications of seismological aspects on engineering parameters

  • Beyen, Kemal;Tanircan, Gulum
    • Earthquakes and Structures
    • /
    • v.8 no.6
    • /
    • pp.1363-1386
    • /
    • 2015
  • The October 23 2011 Van Earthquake is studied from an earthquake engineering point of view. Strong ground motion processing was performed to investigate features of the earthquake source, forward directivity effects during the rupture process as well as local site effects. Strong motion characteristics were investigated in terms of peak ground motion and spectral acceleration values. Directiviy effects were discussed in detail via elastic response spectra and wide band spectograms to see the high frequency energy distributions. Source parameters and slip distribution results of the earthquake which had been proposed by different researchers were summarized. Influence of the source parameters on structural response were shown by comparing elastic response spectra of Muradiye synthetic records which were performed by broadband strong motion simulations of the earthquake. It has been emphasized that characteristics of the earthquake rupture dynamics and their effects on structural design might be investigated from a multidisciplinary point of view. Seismotectonic calculations (e.g., slip pattern, rupture velocity) may be extended relating different engineering parameters (e.g., interstorey drifts, spectral accelerations) across different disciplines while using code based seismic design approaches. Current state of the art building codes still far from fully reflecting earthquake source related parameters into design rules. Some of those deficiencies and recent efforts to overcome these problems were also mentioned. Next generation ground motion prediction equations (GMPEs) may be incorporated with certain site categories for site effects. Likewise in the 2011 Van Earthquake, Reverse/Oblique earthquakes indicate that GMPEs need to be feasible to a wider range of magnitudes and distances in engineering practice. Due to the reverse faulting with large slip and dip angles, vertical displacements along with directivity and fault normal effects might significantly affect the engineering structures. Main reason of excessive damage in the town of Erciş can be attributed to these factors. Such effects should be considered in advance through the establishment of vertical design spectra and effects might be incorporated in the available GMPEs.

New Diagnostic Technique and Device for Lightning Arresters by Analyzing the Wave Height Distribution of Leakage Currents (누설전류의 파고분포 분석에 의한 새로운 피뢰기 진단기술 및 장치)

  • 길경석;한주섭;송재영;조한구;한문섭
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.12
    • /
    • pp.562-567
    • /
    • 2003
  • Lightning arresters are deteriorated by repetition of protective operation against overvoltages or impulse currents in environments of its use. If a deteriorated arrester is left in power lines, it can lead to an accident such as a line to ground fault even in a normal system. Therefore, it is necessary to eliminate the deteriorated arrester in advance by checking the soundness of arresters on a regular basis, and to ensure the reliability of power systems by preventing accidents. Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the wave height distributions of the total leakage currents are remarkably changed or a new wave height are produced with the progress of arrester deterioration. To propose a new technique for the diagnosis, we designed a leakage current detection unit and an analysis program which can measure leakage current magnitudes and analyze wave height distributions. From the experimental results, we confirmed that the proposed technique by analyzing the wave height distribution can simply diagnose the mode of defects such as a partial damage and an existence of punctures in arresters as well as deterioration of arresters.

Algorithm of Detecting Ground Fault by Using Insulation Monitoring Device(IMD) in Ungrounded DC System (직류 비접지계통에서 절연저항측정장치(IMD)를 이용한 사고검출 알고리즘)

  • Kim, Ki-Young;Lee, Hu-Dong;Tae, Dong-Hyun;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.21 no.9
    • /
    • pp.528-535
    • /
    • 2020
  • Recently, the protection coordination method of DC systems has been presented because renewable energy and distributed resources are being installed and operated in distribution systems. On the other hand, it is difficult to detect ground faults because there is no significant difference compared to a steady-state current in ungrounded IT systems, such as DC load networks and urban railways. Therefore, this paper formulates the detection principle of IMD (Insulation Monitoring Device) to use it as a protection coordination device in a DC system. Based on the signal injection method of IMD, which is analyzed by a wavelet transform, this paper presents an algorithm of detecting ground faults in a DC system in a fast and accurate manner. In addition, this paper modeled an IMD and an ungrounded DC system using the PSCAD/EMTDC S/W and performed numerical analysis of a wavelet transform with the Matlab S/W. The simulation results of a ground fault case in an ungrounded DC system showed that the proposed algorithm and modeling are useful and practical tools for detecting a ground fault in a DC system.

A Study on Fault Characteristics of Wind Power in Distribution Feeders (풍력발전(DFIG)의 고압배전선로의 사고특성 해석에 관한 연구)

  • Kim, So-Hee;Kim, Byung-Ki;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.13 no.3
    • /
    • pp.1288-1295
    • /
    • 2012
  • Korea Ministry of Knowledge Economy has estimated that wind power (WP) will be occupied 37% in 2020 and 42% in 2030 of the new energy sources, and also green energies such as photovoltaic (PV) and WP are expected to be interconnected with the distribution system because of Renewable Portfolio Standard (RPS) starting from 2012. However, when a large scale wind power plant (over 3[MW]) is connected to the traditional distribution system, protective devices (mainly OCR and OCGR of re-closer) will be occurred mal-function problems due to changed fault currents it be caused by Wye-grounded/Delta winding of interconnection transformer and %impedance of WP's turbine. Therefore, when Double-Fed Induction Generator (DFIG) of typical WP's Generator is connected into distribution system, this paper deals with analysis three-phase short, line to line short and a single line ground faults current by using the symmetrical components of fault analysis and PSCAD/EMTDC modeling.