• 제목/요약/키워드: Generator protection system

검색결과 160건 처리시간 0.042초

발전기보호반을 위한 IED의 설계에 관한 연구 (A Study on Design of IED for Generator Protection Panel)

  • 박철원;박성완
    • 전기학회논문지P
    • /
    • 제62권3호
    • /
    • pp.133-138
    • /
    • 2013
  • A large generator is an important role in transferring an electric power to power system. The IEDs of large generator often use microprocessor technology to obtain a digital relay system with a wide range of measuring, protection, control, monitoring, and communication functions. However, all generator protection and control systems in Korea imported from abroad and are being operated. In order to reduce the large expense and improve the reliable operation, development of generator protection and control system by domestic technology is required. This paper deals with the design of the IED of generator protection panel for development of generator protection and control system. The major emphasis of the paper will be on the description of hardware and signal processing test results and measurement accuracy of the prototype IED. By developing of generator IED based on DSP and microprocessor, replacement of the generator protection panel imports are expected to be effective.

발전기 보호용 다기능 IED 시제품 H/W 구현에 관한 연구 (A Study on Implementation of Multi-Function Prototype IED H/W for Generator Protection)

  • 김윤상;안태풍;박철원
    • 조명전기설비학회논문지
    • /
    • 제27권12호
    • /
    • pp.74-80
    • /
    • 2013
  • Generator faults does not happen more often than the transmission and substation facility faults. However, impacts on the power system by generator faults are very large. In order to minimize the impact of generator faults, generator protection and control system with high reliability is required. Most of the generator relay in generator protection and control system of large power plant of Korea is operated by imports from abroad. Accordingly, in order to accumulate source technology and increase the import substitution effect, localization of multi-function generator protection IED is being developed. This paper deals with the implementation of a multi-function prototype IED H/W, which can be command and data exchange through communication for measuring, monitoring, protection and control. And the IED specification, various relay elements, measurement elements, communication functions, module function, and test system for the prototype IED H/W are described.

발전기 과여자 및 과전압 계전기 보호협조에 관한 연구 (A Study on the Protective Coordination of Generator Overexcitation and Overvoltage Relay)

  • 박지경;김광현;김철환;유영식;양정재
    • 전기학회논문지
    • /
    • 제66권8호
    • /
    • pp.1187-1194
    • /
    • 2017
  • After North American wide area black out on August 14, 2003, various studies have been conducted to find out the reason of the disaster. One of main reasons was misoperation of generator protection system. Since then, protective coordination between generator protection system and excitation system controls has been hot issue among electrical engineers. Among various generator protection relays, in this paper, we focused on generator overvoltage and overexcitation relay, which protect the over-flux condition of the generator. Thus, at first, we modeled the generator overvoltage, overexcitation relay and detailed power system including excitation system, governor and etc., based on actual field data. And then, we reviewed the protective coordination of generator overvoltage and overexcitation relay using electromagnetic transient program. In addition, we discussed the protective coordination method for redundant protection relays in both automatic voltage regulator and generator side.

대형 발전기 주보호를 위한 디지털 비율차동 계전기법 (Digital Ratio Differential Relaying for Main Protection of Large Generator)

  • 박철원;반우현
    • 전기학회논문지P
    • /
    • 제61권1호
    • /
    • pp.35-40
    • /
    • 2012
  • An AC generator is an important component in producing an electric power and so it requires highly reliable protection relays to minimize the possibility of demage occurring under fault conditions. It is a need for research of digital generator protection system(DGPS) for the next-generation ECMS and an efficient operation of protection control system in power station. However, most of protection and control system used in power plants have been still imported as turn-key and operated in domestic. This may cause the lack of the correct understanding on the protection systems and methods, and thus have difficulties in optimal operation. In this paper, presented ratio differential relaying(RDR) is main protective element in generator protection IED. The fault detection technique, operation zone and setting value of the RDR were studied and, compared with two of the fault detection algorithm. For evaluation performance of the RDR, the data obtained from ATPDraw5.7p4 modeling was used. The proposed methods are shown to be able to rapidly identify internal fault and did not operate a miss-operation for all the external fault.

발전기 보호용 계자상실 계전기의 적용 분석 (Application Analysis for Loss of Excitation Relay of Generator Protection)

  • 오용택;박철원
    • 전기학회논문지P
    • /
    • 제63권4호
    • /
    • pp.322-326
    • /
    • 2014
  • Recently, the LOE(loss of excitation) incidents are occurred in domestic synchronous generator frequently, the synchronous generator protection system has been much attention for the LOE protection of the incidents that threats synchronous generators and power systems. This paper was showed the characteristics and practices of distance relay that widely used LOE protection relaying in generator. Firstly, the operating characteristics and the impedance locus for LOE of the generator protection were introduced. Even if the conventional simulation program is used for modeling, but it is difficult to implement a LOE modeling and simulation of synchronous generator. So, the LOE relay operation data collected from thermal power plant and nuclear power plant in real fields were analyzed. By reviewing the applications of GE Mho relays, the reliability of LOE for synchronous generator protection in domestic were improved.

수력 발전기 제어시스템의 계자상실 모델링과 시뮬레이션 (Modeling and Simulation of Loss of Excitation of Hydro Generator Control System)

  • 박철원
    • 전기학회논문지P
    • /
    • 제63권2호
    • /
    • pp.74-80
    • /
    • 2014
  • Generator protection device has to detects an internal fault conditions in generator and abnormal operating conditions must be due to the hazards. Loss of excitation may cause generator itself failure as well as serious operating problem in power system, and then requires an appropriate response of generator protection device. Details modeling of generator control system and analysis of transient states in generator are important for optimal operation in power plants. In addition, the fault simulation data are also used for testing the characteristics of IED. In this paper, the hydro generator control system using PSCAD/EMTDC, visual simulation for power systems, was modeled. The generator control system which is composed of generator, turbine, exciter, governor was implemented. The parameters of generator control system model were obtained from field power plant. Loss of excitation simulations were performed while varying the fixed load. Several signals analysis were also performed so as to analyze transients phenomena.

345kV 계통 모델링 데이터를 활용한 과여자 보호계전기법 (Over-Excitation Protection Relaying using the 345kV Power System Modeling Data)

  • 박철원;반우현
    • 전기학회논문지P
    • /
    • 제60권4호
    • /
    • pp.175-180
    • /
    • 2011
  • A large AC generator is an important component of the power system. It is a need for research of AC generator protection relay for the next-generation ECMS and an efficient operation of protection control system. However, most of protection and control systems used in power plants have been still imported as turn-key and operated in domestic. This may cause the lack of the correct understanding on the protection systems and methods, and thus have difficulties in optimal operation. In this paper, over-excitation protection relaying is one of the protective factors in generator protection IED was presented. The cause and protection principles were dealt and, DFT-based gain compensation algorithm was adopted for the frequency measurement. The Republic of Korea 345kV modeling data by EMTP-RV was used for performance evaluation.

발전소의 발전기 보호계전시스템 (Generator Protection Relaying System in Power Plant)

  • 안준영;박철원;이종수;이상성;신명철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.151-152
    • /
    • 2006
  • Because power plant faults have severe effects on the power system and on mechanical maintenance of the generator, reliable protection systems are needed. In this paper, we compared and analyzed methods of the generator protection relaying system, which can defect internal faults of the generator, and surveyed the trends in generator protection using digital computing.

  • PDF

발전기시스템의 고정자보호 IED를 위한 개선된 알고리즘 (Advanced Algorithm for IED of Stator Winding Protection of Generator System)

  • 박철원
    • 전기학회논문지P
    • /
    • 제57권2호
    • /
    • pp.91-95
    • /
    • 2008
  • The large AC generator fault may lead to large impacts or perturbations in power system. The generator protection control systems in Korea have been imported and operated through a turn-key from overseas entirely. Therefore a study of the generator protection field has in urgent need for a stable operation of the imported goods. In present, the algorithm using the current ratio differential relaying based DFT for stator winding protection or a fault detection had been applied that of internal fault protection of a generator. the DFT used for the analysis of transient state signal conventionally had defects losing a time information in the course of transforming a target signal to frequency domain. In this paper, the discrete wavelet transform (DWT) was applied a fault detection of the generator being superior to a transient state signal analysis and being easy to real time realization. The fault signals after executing a terminal fault modeling collect using a MATLAB package, and calculate the wavelet coefficients through the process of a muiti-level decomposition (MLD). The proposed algorithm for a fault detection using the Daubechies WT (wavelet transform) was executed with a C language and the commend line function for the real time realization after analyzing MATLAB's graphical interface. The advanced technique had improved faster a speed of fault discrimination than a conventional DFR based on DFT.

풍력발전단지 보호를 위한 내외부 고장 판별 알고리즘 (A Protection Algorithm Discriminating Between Internal and External Faults for Wind Farms)

  • 권영진;강상희
    • 전기학회논문지
    • /
    • 제56권5호
    • /
    • pp.854-859
    • /
    • 2007
  • A wind farm consists of many wind generator(WG)s therefore, it is generally a complex power system. A wind farm as a distributed generation(DG) affects utility power system. If a conventional protection schemes are applied, it is difficult to detect faults correctly and the schemes can't provide proper coordination in some cases. This paper presents a protection algorithm for a wind farm which consists of a looped collection circuit. Because the proposed algorithm can distinguish between an internal fault and an external fault in a wind farm, The proposed algorithm can disconnect the faulted section in a wind farm. This algorithm is based on an overcurrent protection technique with the change of the ratio of the output current of a generator to the current of the looped line connected to each generator to collect the each generator's power. In addition, operating time of the algorithm is shortened by using the voltage drop at a generator collection point. The performance of the proposed algorithm was verified under various fault conditions using PSCAD/EMTDC simulations.