• Title/Summary/Keyword: Gas-Insulated Switchgear

Search Result 223, Processing Time 0.035 seconds

The Development and the Performance Test of Bay Controller for the High-Voltage Gas Insulated Switchgear (초고압 가스절연개폐기의 베이 컨트롤러 개발 및 성능시험)

  • Woo, Chun-Hee;Lee, Bo-In
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.179-184
    • /
    • 2010
  • The digital substation automation system has contributed hugely to increasing the stability of power systems by providing not only protection and control of power systems but diagnostic features alongside them. Digital substation automation systems in the scale of substations consist of integrated operation systems and intelligent electronic devices. The main intelligent electronic devices currently in use are digital protection relays and the bay controllers in Gas insulated switchgears. Proficiently accomplishing the coordination of protection within the power system as a means of ensuring reliability and contriving for the stability of power supply through connection of function, the application of bay controllers is crucial, which collectively manage the protection relay at the bay level in order to achieve both. In this research, the bay controllers to be used in high-voltage Gas insulated switchgear has been localized, and in particular, the logic function and editor required in order to minimize the complicated hardware-like cable connections in the local panel have been developed. In addition, to ensure the strength and reliability of the bay controller hardware developed herein, the type tests from KERI have been successfully completed.

Development of Diagnosis Algorithm for 25.8kV N2 insulated Pad-mounted Switchgear (25.8kV급 N2 절연 지중다회로 개폐기 진단알고리즘 개발)

  • Kim, Chun-Won;Jang, Sung-Il;Choi, Jung-Hwan;Kim, Kwang-Ho
    • Journal of Industrial Technology
    • /
    • v.34
    • /
    • pp.67-70
    • /
    • 2014
  • In this paper, we propose a diagnosis algorithm for 25.8kV $N_2$ insulated Pad-mounted Switchgear in oder to improve reliability by preventing of fault in advance. The proposed algorithm can diagnose the problems of Pad-mounted Switchgear such as gas leakage and VI(Vacuum Interrupter) trouble (contact abrasion, coil aging etc.) by using pressure sensor, stroke sensor and coil current sensor.

  • PDF

The Analysis of Insulation Properties with Electron Collision Processes on SF6 Mixture Gases (전자충돌과정을 통한 SF6 혼합기체의 절연특성 분석)

  • So, Soon-Youl
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.197-201
    • /
    • 2010
  • $SF_6$ gas would be used in power transformer, GIS (Gas insulated switchgear) and so on because of its electrically superior insulation and chemically stable structure. Recently, the reduction of $SF_6$ is required to avoid global warming and the researches on the dilution of $SF_6$ with other gases have been carried out. $SF_6$ mixture gases with $N_2$ and $C_xF_y$ have drawn attention to the synergy effect. However, in order to understand the mechanism of the synergy effect, it is important to analyze and evaluate properties of mixture gases quantitatively. In this paper, we investigated the mechanism of synergy effect from electron collision processes and electron energy distribution by solving Boltzmann equation with propagator method. Three kinds of gases for dilution of $SF_6$ ($SF_6/N_2$, $SF_6/CF$4 and $SF_6/C_4F_8$) are considered in this simulation. On the properties of $SF_6/N_2$ mixture gas, the variation of reduced electric field was shown highly within 0%~40% mixtures of $SF_6$. And the more low-level electron energy has been distributed, the higher insulation capability has appeared.

Reliability of FRP Insulated Rod for GIS(Gas Insulated Switchgear) (GIS용 FRP 절연로드 신뢰성시험)

  • Kim, J.B.;Yang, D.I.;Jin, S.Y.;Song, W.P.;Heo, J.C.;Park, T.G.;Ko, H.S.;Choi, I.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1646-1648
    • /
    • 2004
  • 수입외자재에 의존하고 있는 GIS(Gas Insu.lated Switchgear)용 FRP 절연로드의 전기적, 기계적 신뢰성시험에 대하여 언급하고자하며, 본 논문에 기술된 신뢰성시험을 통하여 제품특성을 재확인하였으며 최소 GIS의 수명과 동일함을 확인, 파악함으로써 국산화 개발을 실현하였다.

  • PDF

EMTP Analysis for Ferroresonsnce of Gas Insulated Switchgear (가스절연개폐장치(GIS) 철공진(Ferroresonance) EMTP해석)

  • Chung, Y.H.;Lee, D.S.;Kim, J.B.;Lee, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.366-367
    • /
    • 2008
  • This paper deal with the study of the phenomenon of Ferroresonance in the 170kV Gas Insulated Switchgear(GIS). The Electromagnetic Transient Program(EMTP) was used to simulate the phenomenon of Ferroresonance and conducted the study of the transient over-voltage. An example power system, used in this study, have an accident that the ferroresonance phenomenon happens at MOFVT(Voltage Transformer). The simulation results notices that the secondary part of VT has to be connected by ferroresonance suppressor when the circuit breaker connected with grading capacitor is switched off.

  • PDF

A Suggestion to Choose Location of Bellows for Gas Insulated Switchgear (가스절연 개폐장치의 벨로우즈 위치선정을 위한 제언)

  • Hwang, Kyeong-Min;Jang, Jung-Bum
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2000_2001
    • /
    • 2009
  • 최근 옥외 변전소 형식으로 많이 채택되고 있는 Gas Insulated Switchgear(GIS) 변전설비는 라인 구조물 형태로서, 온도응력에 대한 길이방향의 변형을 수용토록 하기 위하여 GIS 곳곳에 벨로우즈가 설치되어 있다. 특히, GIS는 강재 지지대로 높은 위치에 설치되어 지진 시 지반보다 높은 가속도를 받기 때문에 벨로우즈의 설치 위치가 GIS에 영향을 줄 가능성이 크다. 따라서 본 연구에서는 다양한 경우의 민감도 해석을 통하여 벨로우즈의 위치가 GIS의 내진성능에 미치는 영향을 분석하였으며, 그 결과 최적의 벨로우즈 위치조건을 도출하였다.

  • PDF

A Study on Functionally Graded Material Spacer and Electrodes Shape in Gas Insulated Switchgear for the Improvement of Insulation Performance (절연성능 향상을 위한 가스절연 개폐장치에서의 경사 기능성 재료 스페이서 및 전극 형상 연구)

  • Ju, Heung-Jin;Kim, Bong-Seok;Ko, Kwang-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1358_1359
    • /
    • 2009
  • 가스 절연 개폐장치(Gas Insulated Switchgear : GIS)의 고체 스페이서에 경사기능성 재료(Functionally Graded Material : FGM)를 적용할 때, 전계의 완화를 예상할 수 있다. 특히, 균일 유전율 분포를 가지는 스페이서에서 양극 근처에 집중된 높은 전계가 FGM 스페이서를 사용할 때, 스페이서와 $SF_6$ 가스의 접촉부로 옮겨지며, 그 크기가 완화됨을 확인할 수 있었다[1]. 본 연구에서는 상용 고체 스페이서의 양극 부근에서의 전계 집중을 감소시키기 위해 전극 형상의 최적화를 수행하였다. 최적화 기법으로는 완전계승계획법(Full Factorial Design : FFD)과 결합된 반응표면법(Response Surface Method : RSM)을 이용하였으며, 균일 유전율 스페이서에서 양극 형상을 최적화하였다. 또한 타원형 유전율 분포를 가지는 FGM 스페이서를 이용함으로써, 상용 GIS 모델에 비해 최대 전계가 크게 완화될 수 있음을 확인하였으며, 상용 GIS의 외함부의 크기를 줄여 실제 소형화 가능 여부를 확인하였다.

  • PDF

Development of drive mechanism for 245kV 40kA high-voltage Gas Insulated Switchgear(GIS) using SPMSM (SPMSM을 이용한 '245kV 40kA GIS' 조작기 개발)

  • Jeong, Kyun-Ha;Seo, Kyong-Bo;Kim, Jung-Bea;Suh, In-Young
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.980-981
    • /
    • 2008
  • Mechanical spring and hydraulic pressure operated mechanisms are applied in most of today's High Voltage Gas Insulated Switchgear(GIS)s. This paper proposes a new type of operation mechanism for GIS circuit breakers rated at 245kV and 40kA. The Motor-Direct-Drive-Mechanism (MDDM) has many advantages compared to conventional operating mechanisms. It has a very simple structure with only one moving part, low mechanical stress and audible noise. It also allows monitoring, operation speed control and self-diagnosis functions.

  • PDF