• Title/Summary/Keyword: GCB(Gas Circuit Breaker)

Search Result 53, Processing Time 0.025 seconds

Development of 63kA Gas Insulated Circuit Breaker (초고압 대용량 63kA 가스차단기 개발)

  • Kim, D.S.;Song, W.P.;Kweon, K.Y.;Chung, J.M.;Shin, I.H.;Park, K.Y.;Song, K.D.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07a
    • /
    • pp.170-172
    • /
    • 1998
  • In the future, it is expected that a fault-current of 345kV power system is beyond 60kA and stability and reliability in transmission system will be more important. From these points of view, we needed a development of a circuit breaker having ability of breaking a large fault current, more than 60kA. This paper describe the specification and history of a development on 362kV 63kA 8000A GCB(Gas insulated Circuit Breaker) of which we completed a development. A development of this GCB will contribute to improve the technique to design and make GCB, and the stability and reliability of power system in our country.

  • PDF

A Study on A Hot Gas Velocity Measurement in GCB Using Small-Gap (Small-Gap을 이용한 가스차단기에서의 열가스 속도측정에 관한 연구)

  • Kim, Hong-Kyu;Song, Ki-Dong;Park, Kyong-Yop;Hong, Jung-Pyo;Chong, Jin-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.3
    • /
    • pp.155-158
    • /
    • 2006
  • $SF_6$ gas circuit breakers we widely used for short circuit current interruption in EHV or UHV power system. For a $SF_6$ gas circuit breaker development, the hot gas velocity measurement is necessary during $SF_6$ gas circuit breaker's trip operation. Small-gap flashover characteristics are used for this hot gas velocity measurement. This study sho was the hot gas velocity measurement results during $SF_6$ gas circuit breaker' trip operation.

Analysis of Compressible Flow Fields in a High Voltage Gas Circuit Breaker (초고압 가스차단기 내부의 압축성 유동장 해석)

  • Lee, J.C.;Oh, I.S.;Kim, Y.J.
    • Proceedings of the KSME Conference
    • /
    • 2001.06e
    • /
    • pp.305-310
    • /
    • 2001
  • This paper presents the computational method for analyzing the compressible flow fields in a high voltage gas circuit breaker. There are many difficult problems in analyzing the gas flow in GCB due to complex geometry, moving boundary, shock wave and so on. In particular, the distortion problem of the grid due to the movement of moving parts can be worked out by the fixed grid technique. Numerical simulations are based on a fully implicit finite volume method of the compressible Reynolds-averaged Navier-Stokes equations to obtain the pressure, density, and velocity through the entire interruption process. The presented method is applied to the real circuit breaker model and the pressure in front of the piston is good agreement with the experimental one.

  • PDF

Study on the Measurement of Radiation Energy of the Arc in GCBs (가스차단기내 아크의 복사에너지 측정에 관한 연구)

  • Song, Ki-Dong;Oh, Yeon-Ho;Chong, Jin-Kyo;Cho, Young-Sung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.12
    • /
    • pp.2122-2126
    • /
    • 2007
  • A special PM-Tube(Photo Multiplier Tube) that is using the photoelectric effect has been designed and manufactured to measure the radiation energy of arc in a gas circuit breaker(GCB). The PM-Tube, LLG(liquid light guides), ND(neutral density) filter, and a model gas circuit breaker have been combined for the reception and the transmission of the light and a simplified synthetic test facility with the arc energy measuring system has been established. In the case of $SF_6$ gas pressure $5kg.f/cm^2$ and arc length 20mm, the radiation energy increases with the arc current but it tend to be saturated in the above 20kA. Under the arc current 20kA, the total radiation energy has the biggest value around 8kA and was not exceeded 40% of the total arc energy.

Study on The Small-Gap Measuring System for Gas Velocity Measurement of $SF_6$ Gas Circuit Breaker ($SF_6$ 가스차단기에서 가스 속도측정을 위한 Small-Gap 측정시스템에 관한 연구)

  • Kim Hong-Kyu;Dong Song-Ki;Lee Woo-Young;Park Kyong-Yop;Chong Jin-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.3
    • /
    • pp.139-144
    • /
    • 2005
  • [ $SF_6$ ] gas circuit breakers are widely used short circuit current interruption in EHV or UHV power system. For a $SF_6$ gas circuit breaker development, the $SF_6$ gas velocity measurement is necessary during $SF_6$ circuit breaker's trip operation. Small-gap flashover characteristics are used for this measurement. So, small-gap measuring system which will be used to develope GCB should be developed. This study shows the characteristic analysis and experimental results of small-gap measuring system.

Thermal Flow Characteristics Driven by Arc Plasmas in a Thermal Puffer Type GCB (열파퍼식 가스차단기에서 발생하는 아크 플라즈마에 의한 열유동 특성)

  • Lee, Jong-Chul;Kim, Youn J.
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.11
    • /
    • pp.527-532
    • /
    • 2005
  • During the last ten years the new interruption techniques, which use the arc energy itself to increase the pressure inside a chamber by the PTFE nozzle ablation, have displaced the puffer circuit breakers due to reduced driving forces and better maintainability. In this paper, we have investigated the thermal flow characteristics inside a thermal puffer type gas circuit breaker by solving the Wavier-Stokes equations coupled with Maxwell's equations for considering all instabilities effects such as turbulence and Lorentz forces by transient arc plasmas. These relative inexpensive computer simulations might help the engineer research and design the new interrupter in order to downscale and uprating the GIS integral.

A Study on Arc Conductance of Puffer Type SF6 GCB at Current Zero Period (전류영점 영역에서 파퍼식 SF6 가스차단기의 아크 컨덕턴스에 관한 연구)

  • Chong, Jin-Kyo;Song, Ki-Dong;Lee, Woo-Young;Kim, Gyu-Tak
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.2
    • /
    • pp.328-332
    • /
    • 2010
  • The SLF(Short Line Fault) breaking capability test for high voltage class $SF_6$ GCB(Gas Circuit Breaker) was conducted. Simplified LC resonant circuit test facility was used for SLF breaking test. During test, Test current was measured by Rogwski coil and arc voltage was measured by voltage divider. Arc conductance was calculated by using these test results before 200ns at current zero. Critical arc conductance value at rated voltage 145kV class is about 2.3mS regardless of breaking current magnitude and arc conductance value at rated voltage 170kV class is about 2.6mS.

Investigation of Small Current Interruption Performance for New Type of Interrupting Chamber in SF$_{6}$ Gas Circuit Breaker (신차단방식 SF$_{6}$ 가스 차단기의 소전류 차단성능 연구)

  • Song, Won-Pyo;Kweon, Ki-Yeoung;Lee, Jae-Sung;Song, Ki-Dong;Kim, Maeng-Hyun;Ko, Hee-Seok
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.11
    • /
    • pp.519-526
    • /
    • 2005
  • This paper presents computer simulation results for developing new type of SF$_{6}$ Circuit Breaker in terms of cold gas flow after small current interruption. This cold gas flows down a nozzle into the chamber of a circuit breaker. There are many difficult problems in analyzing the gas flow due to complex geometry, moving boundary, shock wave and so on. When predicting the dielectric capability of a gas circuit breaker after interruption, the gas pressure and density distributions due to the cold gas must be considered in addition to the electrical field imposed across the gas. A self-coded computational fluid dynamics (CFD) program is used for the simulation of cold gas flow in order to evaluate the electrical field characteristic across open contacts and transient characteristics of insulations after small current interruption.

The Development of Gas Bushing for 25.8kV/2000A GCB (25.8kV 2000A GCB용 개스붓싱 개발)

  • Kim, J.B.;Song, W.P.;Lee, C.H.;Noh, C.W.;Jang, W.Y.;Choi, J.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1385-1387
    • /
    • 1994
  • For the development of the 25.8kV outdoor GCB (Gas - Circuit - Breaker), which have a surge surpression performance in closing & opening of circuit and a high reliability performance, we have developed the 25.8kV gas bushing first of all in KOREA. After manufacturing of 25.8kV/2000A gas bushing, we carried out the dimension & visual test and electrical & mechanical test and we have got the favorable test-results. And it was put together real outdoor GCB, and then we carried out type test at KERI and have confirmed the performance of this bushing.

  • PDF

Interrupting Characteristics of 25.8kV Gas Circuit Breaker Using Thermal-Expansion Principle (열팽창분사원리를 이용한 25,8kV급 가스차단기의 차단특성)

  • Chang, K.C.;Shin, Y.J.;Park, K.P.;Jeong, J.K.;Kim, J.K.;Kim, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1603-1605
    • /
    • 1994
  • Recently, Gas Circuit Breakers are rapidly replacing Vacuum Circuit Breakers in the medium voltage switchgear. This is due to the improved performance of - GCB in interrupting capability, price, weight, size etc., while the countermeasure to suppress the switching surges of VCB has not been satisfactory. Intensive research works on the GCB have been conducted in the world widely since 1980. Nowadays it is well known that the thermal expansion type GCB can provide- better performance than puffer type in the distribution power system. KERI has conducted researches in the GCB rated at 25.8kV 25kA with Jinkwang Co. using the thermal expantion principle since 1993. In this paper, the calculated results of electric and magnetic fields for the model GCB are presented and analyzed. The effect of permanent magnet used to improve the interruption capabilty at the low current level is also investigated. The design parameters for the interrupter inspected through the short-circuit tests conducted at high power laboratory of KERI.

  • PDF