• Title/Summary/Keyword: Fire-Driven Flow

Search Result 38, Processing Time 0.027 seconds

THE STUDY ON THE CHARACTERISTICS OF FIRE DRIVEN SMOKE-FLOW FOR DIFFERENT FIRE-LOCATION IN DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하역사에서 화원 위치에 따른 연기거동 특징 연구)

  • Kim, H.B.;Jang, Y.J.;Lee, C.H.;Jung, W.S.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.202-207
    • /
    • 2009
  • In this study, Numerical simulations were performed to analyze the characteristics of fire driven smoke flow for different location of fire source in the deeply underground subway station with using FDS code. The fire driven smoke-flow which was simulated by using Parallel Computational Method for fast calculation and LES for turbulence model. In this research, the fire location to obstruct a suitable egress from the fire disaster were discussed.

  • PDF

ANALYSIS OF STEADY FIRE-DRIVEN FLUID FLOW FOR RAILWAY TUNNEL BY DIFFERENT VELOCITY CONDITIONS AT THE END OF TUNNEL (종단부 유속조건 변화에 따른 철도터널 내 정상상태 화재유동해석)

  • Lee, D.C.;Lee, D.H.;Jung, W.S.;Park, S.H.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.208-213
    • /
    • 2010
  • In this study CFD(Computational Fluid Dynamics) analysis of the steady fire-driven fuid flow for the performance test of ventilation at railway tunnel between Heuksok and Nodeul Station from Seoul Metro 9 is performed. There were fans with exhaust and intake modes and each was installed at the middle and both ends of the tunnel. For this test, the pool fire source of methyl alcohol with 1.5MW and smoke generators were installed between the middle of tunnel and Heuksok Station. In this test, the smoke behavior from natural convection was observed for 10 minutes from the ignition of pool fire and then fans with intake-modes at both sides of Heuksok effect of fan-on with intake mode located in the opposite side of the tunnel nearby Heuksok Station on fire-driven fluid flow is studied on when the boundary conditions of fan-on at the tunnel between Heuksok and Nodeul Station are the same as test. FLUENT, a commercial CFD code, is used for this analysis.

  • PDF

The Study of fire Driven flow and Smoke Exhaust Efficiency for PSD Installation Subway Station (PSD 설치역사의 화재유동 및 배연 효율 연구)

  • Jang, Yong-Jun;Lee, Chang-Hyun;Kim, Hag-Beom;Kim, Jin-Ho
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.1054-1061
    • /
    • 2009
  • This research was performed with emphasis on fire driven flow behavior and smoke exhaust efficiency which depend on the presence of PSD which are being installed domestically and overseas. For simulation, Jung-ang-ro station of Dae-gu subway station was chosen as model, and fire driven flow analysis was performed by using FDS as flow analysis code. Since many calculation time are required for calculation due to increase in the number of grid as the entire station is modeled, simulation was conducted in parallel processing technique. The fire driven flow analysis was analyzed case by case with composing fire scenario to compare fire driven flow and smoke exhaust efficiency changes depending on the presence of PSD. For fire scale, fire strength of 10MW was studied by referring to NFPA-l30. The calculation results were analyzed with focus on passenger safety by referring to NFPA-130.

  • PDF

Comparative Study on The Numerical Simulation for The Back-Layer of The Tunnel Fire-Driven Flow with LES and RANS (터널화재유동의 역기류 해석을 위한 LES 및 RANS 결과의 비교 고찰)

  • Jang, Yong-Jun;Kim, Hag-Beom;Kim, Jin-Ho;Han, Seok-Youn
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.33 no.3
    • /
    • pp.156-163
    • /
    • 2009
  • In this study, comparative analysis on the back-layer phenomena in the tunnel-fire driven flow is performed using numerical simulation with LES and RANS. FDS(Fire Dynamics Simulator) code is employed to calculate the fire-driven turbulent flow for LES and Smartfire code is used for RANS. Hwang and Wargo's data of scaling tunnel fire experiment are employed to compare with the present numerical simulation. The modeled tunnel is 5.4m(L) ${\times}$ 0.4m(W) ${\times}$ 0.3m(H). Heat Release Rate (HRR) of fire is 3.3kW and ventilation-velocity is 0.33m/s in the main stream. The various grid-distributions are systematically tested with FDS code to analyze the effects of grid size. The LES method with FDS provides an improved back-layer flow behavior in comparison with the RANS (${\kappa}-{\epsilon}$) method by Smartfire. The FDS solvers, however, overpredict the velocity in the center region of flow which is caused by the defects in the tunnel-entrance turbulence strength and in the near-wall turbulent flow in FDS code.

The Analysis of the effects of the platform screen door on the fire driven flow in The Deeply Underground Subway Station (대심도 지하역사에서의 화재시 플랫폼 스크린 도어에 의한 열, 연기 거동 영향 분석)

  • Jang, Y.J.;Kim, H.B.;Lee, C.H.;Jung, W.S.
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.1984-1989
    • /
    • 2008
  • In this study, fire simulations were performed to analyze the characteristics of the fire driven flow and the effects of the platform screen door on the smoke flow in the station, when the fire occurred in the center of the platform. Soongsil Univ. station (line number 7, 47m in depth underground) was chosen which was the one of the deepest underground subway stations in the Seoul metro, SMRT. The parallel computational method was employed to compute the heat and mass transfer eqn's with 6 CPUs of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source. The 10,000,000 structured grids were used.

  • PDF

THE COMPARISON ON THE CHARACTERISTIC OF THE FIRE DRIVEN SMOKE-FLOW FOR THE PLATFORM TYPES IN THE DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하철 승강장의 종류별 연기전파특성 비교고찰)

  • Kim, H.B.;Jang, Y.J.;Lee, D.H.;Jung, W.S.;Whang, H.B.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.505-507
    • /
    • 2010
  • In this paper, the comparison on the fire driven smoke flow for platform types was conducted in the Deeply Underground Subway Station. Soongsil-University station (47m depth) as a bank type platform and Mandeok Station as a island type platform were selected for fire numerical simulation. The characteristics of fire driven smoke-flows were analyzed from the simulation results. The proper plan of evacuation against fire for each type was considered through the results.

  • PDF

THE EXAMINATION OF ACCURACY OF FIRE-DRIVEN FLOW SIMULATION IN TUNNEL EQUIPPED WITH VENTILATION (환기가 있는 터널에서의 화재유동 해석의 정확성에 대한 고찰)

  • Jang, Yong-Jun;Lee, Chang-Hyun;Kim, Hag-Beom;Jung, Woo-Sung
    • Journal of computational fluids engineering
    • /
    • v.14 no.3
    • /
    • pp.115-122
    • /
    • 2009
  • Numerical methods are applied to simulate the smoke behavior in a ventilated tunnel using large eddy simulation (LES) which is incorporated in FDS (Fire Dynamics Simulator) with proper combustion and radiation model. In this study, present numerical results are compared with data obtained from experiments on pool fires in a ventilated tunnel. The model tunnel is $182m(L){\times}5.4m(W){\times}2.4m(H)$. Two fire scenarios with different ventilation rates are considered with two different fire strengths. The present results are analyzed with those from LES without combustion and radiation model and from RANS ($\kappa-\epsilon$) model as well. Temperature distributions caused by fire in tunnel are compared with each other. It is found that thermal stratification and smoke back-layer can be predicted by FDS and the temperature predictions by FDS show better results than LES without combustion and radiation model. The FDS solver, however, failed to predict correct flow pattern when the high ventilation rate is considered in tunnel because of the defects in the tunnel-inlet turbulence and the near-wall turbulence.

Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station (대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.66-72
    • /
    • 2008
  • In this study, transient 3D numerical simulations were performed to analyze the characteristics of fire driven flow for smoke ventilation system operating conditions in the deeply underground subway station. The smoke flow patterns were compared and discussed under smoke fan operating mode and off mode in the platform. Soongsil Univ. station(line number 7)was chosen for simulation which was the one of the deepest underground subway stations in the each lines of Seoul. The geometry for model is 365m in length include railway, 23.5m for width, 47m for depth. Therefore 10,000,000 structured grids were used for fire simulation. The parallel computational method for fast calculation was employed to compute the heat and mass transfer eqn's with 6 CPUs(Intel 3.0GHz Dual CPU, 12Cores) of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source.

  • PDF

The Study on Fire Phenomena in The Deeply Underground Subway Station (대심도 지하역사에서의 화재현상 연구)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.1773-1780
    • /
    • 2008
  • When the fire occur in the deeply underground subway station, the difficulties of passenger evacuation are expected because of many stairs to the exit. In this study, SOONGSIL-University station (7 line, 47m depth) is the one of the deepest subway stations of the each line in the Seoul metro. The numerical computational-simulation was performed for the fire driven flow in the subway station. Hot and smoke flow was analyzed from the simulation results. The proper plan of evacuation against fire was considered through the results. The fire driven flow was simulated using FDS code in which LES method was applied. The Heat Release Rate was 10MW and the ultrafast model was applied for the growing model of the fire source. The proper mesh size was determined from the characteristic length of fire size. The parallel computational method was employed to compute the flow and heat eqn's in the meshes, which are about 10,000,000, with 6cpu of the linux clustering machine.

  • PDF

Nonlinear Thermo-mechanical Analysis Considering Heat Flow under Fire Conditions (화재 열 유동을 고려한 구조물의 열응력해석)

  • Pak, Hongrak;Kang, Jun Won;Lee, Jinwoo
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.29 no.4
    • /
    • pp.369-376
    • /
    • 2016
  • In this study, a numerical analysis framework for investigating the nonlinear behavior of structures under fire conditions is presented. In particular, analysis procedure combining fire-driven flow simulation and thermo-mechanical analysis is discussed to investigate the mechanical behavior of fire-exposed representative volume structures made of steel and concrete, respectively. First of all, fire-driven flow analysis is conducted using Fire Dynamics Simulator(FDS) in a rectangular parallelepiped domain containing the structure. The FDS simulation yields the time history of temperature on the surface of the structure under fire conditions. Second, mechanical responses of the fire-exposed structure with respect to prescribed uniformly distributed loads are calculated by a coupled thermo-mechanical analysis using the time-varying surface temperature as boundary conditions. Material nonlinearities of steel and concrete have been considered in the thermo-mechanical analysis. A series of numerical results are presented to demonstrate the feasibility of the multiphysics structural fire analysis for investigating the structural behavior under fire conditions.