Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods

  • Jung, In-Su;Park, Tae-Gyu;Chung, Hee-Taeg
    • 한국분무공학회지
    • /
    • 제15권3호
    • /
    • pp.124-130
    • /
    • 2010
  • Numerical simulation has been performed to investigate the mist flow characteristics through the fire suppression nozzles for the design purposes. The commercial softwares, FLUENT and the fire dynamic simulator, FDS with the proper modelings were chosen as the numerical tools. In order to find optimal conditions in sense of the main performances of nozzles, the spray characteristics were analyzed both inside and outside of the nozzles. Geometric factors of the injecting orifices, i.e., diameter and chamfered angle were chosen as the simulation parameters for design application. From the present numerical results, 1.0c nozzles, whose orifice-diameter was 1 mm, having the chamfered angles were shown as the best performance of the fire suppression.

교통정체가 심한 도로터널에 대한 화재시 제연방식에 관한 연구 (The study of ventilation system during fire in road tunnel with bi-directional or congested unidirectional traffic)

  • 유지오;신현준;남창호
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.474-479
    • /
    • 2008
  • The purpose of this paper is to estimate the fire safety in tunnels with bi-directional and/or congested unidirectional traffic where there may be people on both sides of the fire. Therefore, the spread and movement of smoke are simulated by Fire Dynamic Simulator code under different ventilation systems, longitudinal, semi-transverse, large port exhaust system. And as quantitative risk index, FED (Fractional Effective Dose) for each ventilation system are calculated and compared by existed code developed previous research.

  • PDF

이동식 미분무수 노즐의 소화 특성에 대한 수치 시뮬레이션 (Thermal Numerical Simulation on Fire Suppression Characteristics through Mobile Mist Spray Nozzles)

  • 배강열;정희택;김형범;정인수;김창
    • 동력기계공학회지
    • /
    • 제13권5호
    • /
    • pp.25-33
    • /
    • 2009
  • In the present study, the numerical investigation has been carried out to see the effects of water mist sprays on the fire suppression mechanism. The special-purposed program named as FDS was used to simulate the interaction of fire plume and water mists. This program solves the fire-driven flows using LES turbulence model, the mixture fraction combustion model, the finite volume method of radiation transport for a non-scattering gray gas, and conjugate heat transfer between wall and gas flow. The computational domain was composed of a rectangular space dimensioned as $L{\times}W{\times}H=4.0{\times}4.0{\times}2.5\;m^3$ with a mist-injecting nozzle installed 1.0 m high from the fire pool. In this paper, two types of nozzles were chosen to compare the performance of the fire suppression. Numerical results showed that the nozzle, type A, with more orifices having smaller diameters had poorer performance than the other one, type B because the flow injected through side holes deteriorated the primary flow. The fire-extinguishing time of type A was 2.6 times bigger than that of type B.

  • PDF

환기부족 구획화재에서 다차원 화재거동 (Multi-dimensional Fire Behaviors in an Under-ventilated Compartment Fire)

  • 황철홍;박충화;고권현
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2010년도 춘계학술논문발표회 논문집
    • /
    • pp.37-42
    • /
    • 2010
  • 실제 규모 ISO 9705 표준 화재실에서 과환기(over-ventilated) 및 환기부족(under-ventilated) 화재에 대한 열 및 화학적 특성에 관한 실험이 수행되었다. 또한 FDS(Fire Dynamic Simulator)를 이용하여 수치적 예측성능에 대한 평가와 환기부족화재에서 건물 내부의 다차원 화재현상에 대한 해석이 이루어졌다. 과환기 및 환기부족화재의 특성은 연소효율, 총괄 당량비 뿐만 아니라 고온 상층부의 온도분포, 연소 생성물의 농도에 의해 명확하게 구분되었다. 실험결과와의 비교를 통해 과환기 및 환기부족화재에서 FDS는 공간내부의 온도, 열유속 및 다양한 화학종의 분포를 정량적으로 잘 예측함을 확인하였다. 과환기화재와 비교할 때, 환기부족화재에서 내부유동은 반대방향의 다차원 재순환 유동구조를 갖고 있음을 발견하였다. 동시에 공간내부의 $O_2$ 및 CO의 분포 역시 다차원 구조를 갖기 때문에 기존화재연구에서 측정되는 고온 상층부의 열 및 화학적 특성은 환기부족화재를 이해하는데 많은 한계가 있음을 확인하였다.

  • PDF

점화원 위치 및 점화시간 변화에 따른 백드래프트 거동에 관한 수치적 연구 (A Numerical Study of the Backdraft Behavior with the Variation of the Ignition Location and Time)

  • 고민욱;오창보;한용식;도규형
    • 한국안전학회지
    • /
    • 제31권4호
    • /
    • pp.1-8
    • /
    • 2016
  • The behavior of backdraft in the compartment with different ignition locations and times was numerically investigated. The Fire Dynamics Simulator (FDS) v5.5.3 with a model-free simulation option was used in the numerical simulation of backdraft. The ignition source was located near the inside wall, at the compartment center and near the window opening, respectively. The ignition was started at the instance when the fresh air reached the ignition location or when a sufficient time passed compare to the instance of the arriving of the fresh air to the ignition location. As a result, for the ignition source was located near the inside wall, a strong fire ball was observed at once and the result was similar to the previous experimental result. For the ignition source was located at the center of the compartment, a strong fire ball was occurred and two strong fire balls were observed consecutively for the ignition time was delayed. For the ignition source was located near the window opening and longer time was given for the ignition compare the duration of the fresh air arriving to the ignition location, the rapid temperature variation was not observed because there was no flame. However, for the ignition was started at the instance when the fresh air reached the ignition location, the ignition could be initiated and a intensive fire ball was observed. The pressure measured at the upper inside part of the window opening provided a similar trend with the previous experimental result of compartment backdraft.

인명안전 관점에서 선박 화재 시 급·배기조건에 따른 배연성능 예측평가 (Smoke Exhaust Performance Prediction According to Air Supply and Exhaust Conditions for Shipboard Fires from a Human Safety Point of View)

  • 김별;황광일
    • 해양환경안전학회지
    • /
    • 제22권7호
    • /
    • pp.782-790
    • /
    • 2016
  • 선박의 기계식 환기시스템은 화재발생 시 연기의 생성과 확산 특성에 영향을 미치고, 이는 피난자의 피난경로 상의 가시도를 방해함으로써 피난자의 연기로 인한 피해를 증가시킬 위험성이 크다. 이에 이 연구에서는 선박 거주구역에서 화재발생 시 기계식 급 배기시스템이 연기확산에 미치는 영향과 위험성에 대하여 FDS를 활용하여 평가하고 화재 시 급 배기시스템을 효율적으로 사용할 수 있는 방안을 제안하였다. 연구결과 화재가 발생한 장소에 급 배기시스템이 함께 작동되고 있는 경우에는 현재 권장되고 있는 급 배기시스템을 멈추는 방법보다 작동을 유지하는 것이 효과적이고, 배기시스템만 작동되는 곳에서 화재가 발생한 경우에는 화재가 발생한 구역 이외의 구역에서 급기시스템을 함께 작동시키는 것이 피난시간을 확보하는데 효과적인 것으로 예측되었다. 그러나 화재가 발생한 곳에 급기시스템만 있는 경우에는 급기시스템이 연기확산을 가속시키기 때문에 급기방식을 중단시켜 연기의 확산을 최대한 억제할 필요가 있음을 확인하였다.

Integrated fire dynamic and thermomechanical modeling of a bridge under fire

  • Choi, Joonho;Haj-Ali, Rami;Kim, Hee Sun
    • Structural Engineering and Mechanics
    • /
    • 제42권6호
    • /
    • pp.815-829
    • /
    • 2012
  • This paper proposes a nonlinear computational modeling approach for the behaviors of structural systems subjected to fire. The proposed modeling approach consists of fire dynamics analysis, nonlinear transient-heat transfer analysis for predicting thermal distributions, and thermomechanical analysis for structural behaviors. For concretes, transient heat formulations are written considering temperature dependent heat conduction and specific heat capacity and included within the thermomechanical analyses. Also, temperature dependent stress-strain behaviors including compression hardening and tension softening effects are implemented within the analyses. The proposed modeling technique for transient heat and thermomechanical analyses is first validated with experimental data of reinforced concrete (RC) beams subjected to high temperatures, and then applied to a bridge model. The bridge model is generated to simulate the fire incident occurred by a gas truck on April 29, 2007 in Oakland California, USA. From the simulation, not only temperature distributions and deformations of the bridge can be found, but critical locations and time frame where collapse occurs can be predicted. The analytical results from the simulation are qualitatively compared with the real incident and show good agreements.

유동해석을 위한 FDS의 구조 (Structure of FDS for Flow Analysis)

  • 이주희;김동은;김봉찬;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2012년도 춘계학술발표회 초록집
    • /
    • pp.270-273
    • /
    • 2012
  • 오픈 소스인 FDS(fire dynamic simulator)는 건물, 터널내의 화재나 연기, 열기류의 거동을 연구하기 위하여 국내외적으로 광범위하게 이용되고 있다. 체계적인 연구와 확장이 가능하도록 소스코드와 프로그램구조, 각종 메뉴얼을 갖추고 있으며 향후 개발 방향을 온라인을 통해서 소스코드와 함께 공개하고 있다. 비압축성 비정상해석을 근간으로 하고 있으며 난류유동을 해석할 수 있도록 DNS와 LES모델을 가지고 있다. 화재, 연소, 스프링클러, 화재 확산 등의 모델링을 제공하고 있다. 이러한 모델을 바탕으로 다양한 시나리오의 재난, 피난에 적용할 수 있다. 향후 이러한 기본 모델을 바탕으로 새로운 재난 시나리오에 따라 새로운 알고리즘의 적용하기 위해서는 FDS 기본적인 구조와 모델, 그리고 한계점을 이해할 필요가 있다. 본 연구에서는 이러한 FDS모델을 더욱 확장하기 위한 일환으로 FDS(V5.5.3)의 기본적인 구조을 파악하고 몇 가지 검증모델(verification)에 적용하였다. 또한 이를 향후 FDS의 소스코드를 확장할 수 있는 근간으로 삼고자 한다.

  • PDF

유동해석에 있어서의 FDS의 수치모델 (Numerical models for hydrodynamic flows in FDS)

  • 이주희;김동은;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2011년도 추계학술논문발표회 논문집
    • /
    • pp.139-142
    • /
    • 2011
  • 오픈 소스인 FDS(fire dynamic simulator)는 건물, 터널내의 화재나 연기, 열기류의 거동을 연구하기 위하여 국내외적으로 광범위하게 이용되고 있다. 소스코드 또한 공개 되어 있어 그 활용범위가 더욱 넓어지고 있다. 대부분의 기본적인 화재, 방재 해석을 위한 모델들을 제공하고 있으나 이를 더욱 발전시키고 새로운 알고리즘의 적용하기 위해서는 이러한 모델의 구조를 잘 이해할 필요가 있다. 본 연구에서는 이러한 FDS모델을 더욱 확장하기 위한 일환으로 현 FDS의 기본적인 구조를 검증모델(verification)을 이용하여 파악하고 이를 향후 소스코드를 확장할 수 있는 근간으로 삼고자 한다.

  • PDF

지하 공간의 워터커튼 시스템 화재제어 특성 분석 (An Analysis of the Smoke Control Characteristics of Water Curtain System for Underground Space)

  • 유우준;남준석;최진종;이정균;김동준;유홍선
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2011년도 추계학술논문발표회 논문집
    • /
    • pp.298-301
    • /
    • 2011
  • 본 연구에서는 지하 방호공간에서 화재가 발생한 경우 워터커튼 시스템에 의한 연기의 차단효과와 화재제어 특성을 분석하였다. 이를 위해서 분사각도 $180^{\circ}$, 오리피스 직경 8.2 mm의 노즐과 지하방호 공간용 실화재 실험 장치를 제작하였으며, 화재강도 1.5 MW 기준 A급 1단위 화재 실험으로부터 온도분포와 가시도를 측정하여 연기의 차단효과를 확인하였다. 화재제어 특성을 분석하기 위해서 NIST(National Institute of Standards and Technology)의 해석프로그램인 FDS(Fire Dynamic Simulator)를 사용하여 동일한 실험조건에서 온도분포를 비교하였으며 노즐의 설치개수 변화에 대한 화재해석 및 실험결과로부터 워터커튼 시스템은 노즐의 설치위치와 개수, 화원으로부터의 거리, 제연 등의 설비 조건과 분사 노즐의 특성, 공급 유량 등이 중요한 상관관계를 갖고 있음을 확인하였다.

  • PDF