Thermal Numerical Simulation on Fire Suppression Characteristics through Mobile Mist Spray Nozzles

이동식 미분무수 노즐의 소화 특성에 대한 수치 시뮬레이션

  • Published : 2009.10.31

Abstract

In the present study, the numerical investigation has been carried out to see the effects of water mist sprays on the fire suppression mechanism. The special-purposed program named as FDS was used to simulate the interaction of fire plume and water mists. This program solves the fire-driven flows using LES turbulence model, the mixture fraction combustion model, the finite volume method of radiation transport for a non-scattering gray gas, and conjugate heat transfer between wall and gas flow. The computational domain was composed of a rectangular space dimensioned as $L{\times}W{\times}H=4.0{\times}4.0{\times}2.5\;m^3$ with a mist-injecting nozzle installed 1.0 m high from the fire pool. In this paper, two types of nozzles were chosen to compare the performance of the fire suppression. Numerical results showed that the nozzle, type A, with more orifices having smaller diameters had poorer performance than the other one, type B because the flow injected through side holes deteriorated the primary flow. The fire-extinguishing time of type A was 2.6 times bigger than that of type B.

Keywords

References

  1. S. C. Kim and H. S. Ryou, 2003, "An Experimental and Nwnerical Study on Fire Suppression using a Water Mist in an Enclosure", Building and Environment, Vol. 38, Issue 11, pp. 1309-1316. https://doi.org/10.1016/S0360-1323(03)00134-3
  2. S. C. Kim and H. S. Ryou, 2004, "The Effect of Water Mist on Burning Rates of Pool Fire", Journal of Fire Sciences, Vol. 22, No.4, pp. 305-323 https://doi.org/10.1177/0734904104041796
  3. 김호영, 오상엽, 정진택, 2004 , "분무수 분무특성 이 액체연료 Pool 화염의 소화에 미치는 영향", 대한기계학회논문집 B권, Vol. 28, No. 12, pp. 1591-1599.
  4. M. B. Kim, Y.J. Jang and J. K. Kim, 1996, "Burning Rate of a Pool Fir with Downward-directed Spray", Fire Safety Journal, 27, pp. 37 -48. https://doi.org/10.1016/S0379-7112(96)00024-0
  5. Y. S. Han, M. B. Kim and H. D. Shin, 1997, "Extinguishment by the Cooling Effect of the Fuel Surface with Pool Fires", Trans. of Korean Institute of Fire Science & Engineering, Vol. 11, No.4, pp. 15-23.
  6. M. B. Kim, Y. J. lang and M. O. Yoon, 1997, "Extinction Limit of a Pool Fire with a Water Mist", Fire Safety Journal, 28, pp. 295 - 306. https://doi.org/10.1016/S0379-7112(97)00011-8
  7. J. K. Hua, B. C. Khoo and H. Xue, 2002, "A Numerical Study of the Interaction of Water Spray with a Fire Plume", Fire Safety Journal, 37, pp. 631 -657. https://doi.org/10.1016/S0379-7112(02)00026-7
  8. 배강열 외 4 인, 2008 , "오리피스형 분사노즐에서 작동유체의 온도변화에 따른 K-factor에 관한 연구", 한국동력기계공학회지, 제 12권, 제 3호, pp. 12- 18.
  9. (주)윈, 2006 , "이동식 미분무수 소화시스템 개발", 소화방재청, 최종보고서.
  10. K. M. McGrattan, 2006, "Fire dynamics simulator (version 4) technical reference guide" , NIST Special Publication 1018
  11. 김성찬, 2003, "화염과 워터미스트의 상호작용에 관한 실험 및 수치 해석 연구", 중앙대학교 기계 공학과 박사학위논문, pp. 69-79.
  12. 정희택 외 4 인, 2006, "CFD기법을 이용한 선박 거주용 수계 소화시스템의 열.유동 성능특성 해석기법 개발" 경상대학교, 연구결과 보고서, pp. 30-31.