배전계통 위치별 초전도전류제한기 적용효과 분석

  • Im, Seong-Hun;Hwang, Jong-Seon;Han, Byeong-Seong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.213-213
    • /
    • 2009
  • In this paper, we investigated the current limiting characteristics due to the application location of the superconducting fault current limiter (SFCL) such as the feeder, the bus, the secondary side of transformer in a power distribution system. In addition, the quench and the recovery characteristics of the SFCL installed in each location of the power distribution system were compared each other. Through the analysis, in case that the SFCL was applied into the feeder line, its current limiting and voltage-drop compensating characteristics were confirmed to be the more effective. On the other hand, the power burden of the SFCL was increased higher compared to the SFCL'S other application location.

  • PDF

Chaotic Neural Networks for Optimal Reconfiguration in Distribution Systems (카오스 신경망을 이용한 배전계통 최적 구성)

  • Rhee, Sang-Bong;Kim, Kyu-Ho;Lee, Yu-Jeong;You, Seok-Ku
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.279-281
    • /
    • 2001
  • This paper presents a chaotic neural networks to solve the distribution feeder reconfiguration problem for loss reduction. Feeder reconfiguration problem is the determination of switching option that minimizes the power losses for a particular set of loads in distribution systems. A chaotic neural networks is used to determine the switching combinations, select the status of the switches, and find the best combination of switches for minimum loss. The proposed method has been tested on 32 bus system, and the results indicate that it is able to determine the appropriate switching options for optimal configuration.

  • PDF

A Study on the Voltage/Var Control of Distribution System Using Kohonen Neural Network (코호넬 신경회로망을 이용한 배전시스템의 전압/무효전력 제어게 관한 연구)

  • Kim, Gwang-Won;Kim, Jong-Il
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.329-331
    • /
    • 1998
  • This paper presents a modified Learning Vector Quantization rule to control shunt capacitor banks and feeder voltage regulators in electric distribution systems with Kohonen Neural Network(KNN). The objective of the KNN is on-line decision of the optimal state of shunt capacitor banks and feeder voltage regulators which minimize $I^{2}R$ losses of the distribution system while maintaining all the bus voltages within the limits. The KNN is tested on a distribution system with 30 buses, 5 on-off switchable capacitor banks and a nine tap line voltage regulator.

  • PDF

Heuristic Approach to Service Restoration (경험 지식 기반 정전 복구)

  • Kim, Jong-Boo;Choi, Sang-Yule;An, Bi-O
    • Proceedings of the IEEK Conference
    • /
    • 2006.06a
    • /
    • pp.1019-1020
    • /
    • 2006
  • The proposed algorithm consists of two parts. One is to set up a decision tree to represent the various switching operations available. Another is to identify the most effective the set of switches using proposed search technique and a feeder load balance index. Test results on the KEPCO's 108 bus distribution system show that the performance is efficient and robust

  • PDF

An Adaptive Setting Method for the Overcurrent Relay of Distribution Feeders Considering the Interconnected Distributed Generations

  • Jang Sung-Il;Kim Kwang-Ho;Park Yong-Up;Choi Jung-Hwan;Kang Yong-Cheol;Kang Sang-Hee;Lee Seung-Jae;Oshida Hideharu;Park Jong-Keun
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.4
    • /
    • pp.357-365
    • /
    • 2005
  • This research investigates the influences of distributed generations (DG), which are interconnected to the bus by the dedicated lines, on the overcurrent relays (OCR) of the neighboring distribution feeders and also proposes a novel method to reduce the negative effects on the feeder protection. Due to the grid connected DG, the entire short-circuit capacity of the distribution networks increases, which may raise the current of the distribution feeder during normal operations as well as fault conditions. In particular, during the switching period for loop operation, the current level of the distribution feeder can be larger than the pickup value for the fault of the feeder's OCR, thereby causing the OCR to perform a mal-operation. This paper proposes the adaptive setting algorithm for the OCR of the distribution feeders having the neighboring dedicated feeders for the DG to prevent the mal-operations of the OCR under normal conditions. The proposed method changes the pickup value of the OCR by adapting the power output of the DG monitored at the relaying point in the distribution network. We tested the proposed method with the actual distribution network model of the Hoenggye substation at the Korea Electric Power Co., which is composed of five feeders supplying the power to network loads and two dedicated feeders for the wind turbine generators. The simulation results demonstrate that the proposed adaptive protection method could enhance the conventional OCR of the distribution feeders with the neighboring dedicated lines for the DG.

Study of Drawing Optimum Switch Automation Rate to Minimize Reliability Cost (신뢰도 비용 최소화를 위한 개폐기의 최적 자동화율 도출에 관한 연구)

  • Chai, Hui-seok;Kang, Byoung-wook;Kim, Jin-seok;Moon, Jong-fil;Kim, Jae-chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.64 no.4
    • /
    • pp.297-302
    • /
    • 2015
  • Replacing a manual switch installed in a feeder for a distribution system with an automatic one increases the reliability of the electric power system. This is because the automatic switch can shorten the duration of a fault the customer experiences by splitting the faulty section faster than the manual one does. However, improving the reliability of the distribution system may increase investment costs. Here, the investment costs include automatic switch cost, replacement work cost and labor cost. For this reason, importance should be attached to the proper balance between the increase of the investment costs and the improvement of the reliability of the distribution system. This article analyzed reliability index and economics when manual switches installed in a feeder (RBTS Bus2 model) was replaced by automatic ones. In addition, it attempted to draw the optimum rate of automation of manual switches by automatic ones using the GRG optimization method, considering the current economic requirements.

Power Quality Analysis of Sungsan Substation Bus Connected to Hangwon Wind Farm (행원풍력단지와 연계된 성산변전소 모선의 전기품질 분석)

  • Ahn, J.H.;Ko, S.M.;Na, K.Y.;Kim, S.H.;Kim, H.C.;Kim, Y.H.;Choi, B.C.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.146-148
    • /
    • 2005
  • The number of wind generation installations are growing substantially in Jeju, Korea. Many of these installations are significant in size and directly connected to the distribution system. In these distributed applications, it is not uncommon for the turbines to be connected near the end of a long rural distribution feeder from which end-users are served. Therefore, utility grid interconnection standards for interconnecting non-utility distributed generation systems are essential to both power system company and generation company. In this paper, it is investigated the power quality of Sungsan substation bus connected to Hangwon wind power generation farm.

  • PDF

Topological Locating of Power Quality Event Source

  • Won Dong-Jun;Moon Seung-Il
    • Journal of Electrical Engineering and Technology
    • /
    • v.1 no.2
    • /
    • pp.170-176
    • /
    • 2006
  • This paper proposes a topological locating algorithm to determine the location of the power quality event source. This algorithm makes use of the information on the topology of the monitored network and on the direction of PQ events. As a result, the bus incidence matrix is modified using monitor location and the direction matrix is constructed. With this information, the algorithm determines the suspected locations of the PQ events. To reduce suspicious areas, it utilizes event cause and related equipment. In case of line fault event, it calculates the distance from the monitor to the location of event source. The overall algorithm is applied to the IEEE test feeder and accurately identifies the event source location.

Development of Monitor Positioning Algorithm considering Power System Topology and Distributed Generation (분산전원과 토폴로지를 고려한 배전계통에서의 전기품질 모니터 위치 선정 기법)

  • Moon, Dae-Seong;Kim, Yun-Seong;Won, Dong-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1744-1751
    • /
    • 2008
  • This paper presents a monitor positioning algorithm to identify the power quality event source in the distribution system with distributed generations. This algorithm determines the appropriate number of monitors and their locations considering power system topology together with distributed generation. This paper summarizes the guidelines of monitor positioning into five principles and defines the weighting factors according to the principles. To evaluate the adequacy of monitor positioning results, ambiguity indices considering monitor location and system topology are proposed. The optimal number and locations of monitors are determined from optimization routine using the weighting factors and the monitor positioning results are evaluated in terms of ambiguity indices. The algorithm is applied to IEEE 13 bus test feeder and suggests the optimal number and locations of power quality monitors. The proposed approach can realize the expert's knowledge on monitor positioning into a sophisticated automatic computing algorithm.

Adaline-Based Control of Capacitor Supported DVR for Distribution System

  • Singh, Bhim;Jayaprakash, P.;Kothari, D.P.
    • Journal of Power Electronics
    • /
    • v.9 no.3
    • /
    • pp.386-395
    • /
    • 2009
  • In this paper, a new control algorithm for the dynamic voltage restorer (DVR) is proposed to regulate the load terminal voltage during various power quality problems that include sag, swell, harmonics and unbalance in the voltage at the point of common coupling (PCC). The proposed control strategy is an Adaline (Adaptive linear element) Artificial Neural Network (ANN) and is used to control a capacitor supported DVR for power quality improvement. A capacitor supported DVR does not need any active power during steady state because the voltage injected is in quadrature with the feeder current. The control of the DVR is implemented through derived reference load terminal voltages. The proposed control strategy is validated through extensive simulation studies using the MATLAB software with its Simulink and SimPower System (SPS) toolboxes. The DVR is found suitable to support its dc bus voltage through the control under various disturbances.