• Title/Summary/Keyword: Fault line

Search Result 1,138, Processing Time 0.06 seconds

Transferred Voltages on LV sides in Multigrounded Neutral during Line to Ground Fault (지락고장시 중성선 전위상승에 따른 저압기기 스트레스 전압)

  • Choi, Sun-Kyu;Park, Chang-Ho;Lee, Byung-Sung;Kim, Kyoung-Hun
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.2160-2161
    • /
    • 2011
  • IEC 61936의 저압기기 허용 상용주파 과전압에 대하여 선로의 지락고장시 고장전류의 분류 효과 및 등가회로를 이용하여 수학적 계산식을 도출하고 EMTP를 이용하여 모의를 수행하였다. 또한 시험선로를 이용하여 실증시험을 수행하여 실제 고장현상을 검토하였다. 현재 배전계통의 접지수준은 기준을 충분히 만족하고 있으므로 다양한 사례 연구를 통하여 접지기준의 개정을 검토할 필요가 있는 것으로 판단된다.

  • PDF

Surveillance System For Extra High Voltage Cable (초고압 CABLE 감시시스템 연구)

  • Hahn, K.M.;Lee, K.C.;Jeon, S.I.;Kim, C.S.
    • Proceedings of the KIEE Conference
    • /
    • 1992.07b
    • /
    • pp.789-793
    • /
    • 1992
  • For improving the power supply reliability and minimizing maintenance work of E.H.V. underground transmission line, new surveillance systems are strongly desired for use in the field of electric power transmission. For underground installation, high system reliability is required because E.H.V. cables, if an accident happen, can have a serious impact on social activities and human life. In answer to this requirement, applications of optical fiber transmission system have been widely developed in a variety of field. The main function of this system are cable fault location, oil leak detection, and surveillance of the cable circuit and tunnel condition.

  • PDF

A Study on the Cause of the Fault on Underground Distribution Line (지중배전선로 고장요인에 관한 연구)

  • Jung, Jong-Yon;Seon, Sang-Jin
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.302_303
    • /
    • 2009
  • 지중배전선로 고장발생현황을 분석한 결과 설비별로는 케이블 고장이 가장 많았고, 그 다음으로 개폐기, 접속재, 변압기 순으로 고장이 많이 발생하였다. 원인별로 보면 일반인 과실과 자연열화에 의한 고장이 대부분을 차지하였다. 지중고장 유형 중 가장 많은 케이블 외상 고장은 인적 과실에 의한 고장으로 이와 같은 인적 과실에 의한 고장이 전체 지중고장의 50% 이상을 차지하며 케이블 및 접속재 열화고장 등 관리소홀에 의한 고장은 전체 지중고장의 20% 이상을 차지하였다. 인적 과실 및 관리소홀에 의한 고장은 천재지변과는 달리 설비관리 노력으로 충분히 감소시킬 수 있다. 지중고장을 감소시키기 위한 구체적인 방안으로는 선로굴착개소 순시 및 입회 철저, 굴착개소 관련 DB의 정확도 유지, 설비열화 진단 및 보강, 설비진단 신기술 개발 및 도입, 접속개소 시공품질 향상 등이 필요할 것으로 판단된다.

  • PDF

A Study of distribution line Protective devices operation on the distributed generation system (양방향 분산전원 보호협조 운영방안 연구)

  • Lee, Sang-Ho;Seol, Il-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.145_146
    • /
    • 2009
  • 최근 한국전력의 일선 사업소에서 배전선로 계통운영 업무에 많은 어려움을 겪고 있다. 분산형전원의 보급이 확대되면서 단방향 고장전류로 처리하던 보호협조 및 배전자동화 업무에 문제점이 발생되면서 혼선이 생기고 있는 것이다. 현행 배전선로 보호협조 업무는 모두 방향성이 없는 형태로 OCR, OCGR과 Recloserfh 대변되는 배전용 차단기의 협조방안으로 운영되어 왔으며, 배전자동화의 경우에도 부하측 공장에 대해 고장표시기(Fault Indicator)를 발생시키는 로직을 활용하여 배전선로의 안정화에 크게 기여하여 왔다. 하지만 최근 급속도로 발전하는 신재생에너지 사업과 관련하여 배전선로와 연계된 분산전원이 점차로 많아지고 있으며, 따라서 이제는 양방향 분산전원를 고려한 보호협조가 적용되어야 할 상황이다. 이에 발맞추어 최근 여러각도에서의 분산전원 연계기술에 대한 많은 연구가 진행되고 있다. 본 논문에서는 현행 배전선로에서의 분산전원 연계시 나타나는 문제점과 그 대책에 대해 알아보고자 한다.

  • PDF

Preventive Control for Transient Security with Generation Rescheduling Based on Rotor Trajectory Index

  • Verma, Kusum;Niazi, K.R.
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.465-473
    • /
    • 2015
  • The increasing need to improve transient security assessment of existing or forecasted operating conditions of networks by power system operators is major concern of the power system security monitoring problem at the Energy Management Systems. This paper proposes a preventive control of transient stability with generation rescheduling based on rotor trajectory index obtained using time domain simulations. This index may help power engineers in making operational decision and to obtain a generation configuration with better transient security dispatch. The effectiveness of the proposed methodology is demonstrated on IEEE 39-bus New England system for a three phase fault at different loading conditions with single and multiple line outage cases.

A Fault Effect to Induced Voltage of Gas Pipeline in Transmission Systems (송전계통에서 고장에 따른 Gas Pipeline 유도전압 분석)

  • Kim, Hyun-Soo;Rhee, Sang-Bong;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1720-1725
    • /
    • 2008
  • Because of the continuous increasing of energy consumption, metallic pipelines are widely used to supply services to customers such as gas, oil, water, etc. Most common metallic pipelines are underground and are now frequently being installed in nearby electric power lines. In recent years, buried gas pipeline close to power lines can be subjected to hazardous induction effects, especially during single line to ground faults. because it can cause corrosion and it poses a threat to the safety of workers responsible for maintenance. Accordingly, it is necessary to take into consideration for analysis of induced voltage on gas pipelines in transmission lines. This paper analyzed the induced voltage on the gas pipelines due to the 154kV transmission lines in normal case and in different faulty case conditions using EMTP (Electro-Magnetic Transients Program).

Assessment of Rotor Winding Insulation Condition for Gas Turbine Generators (가스터빈 발전기 회전자 권선의 절연상태 평가)

  • Kim, Hee-Dong;Kim, Byeong-Rae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1818-1821
    • /
    • 2008
  • Several off-line diagnostic tests which include the insulation resistance(IR), polarization index(PI), low-voltage AC, and recurrent surge oscillograph(RSO) tests were performed to assess the condition of generator rotor windings. The low-voltage AC and the RSO tests were performed on the gas turbine generator rotor winding to detect shorted turns. Before intentionally applying artificial shorted faults, it was confirmed by the low voltage AC and the RSO tests that the winding was in sound condition. For simulated shorted rotor winding turns, the RSO test detected the fault in the winding. The RSO test was capable of identifying the number and pole location of the shorted turns for a number of simulated shorted coils.

Automatic Protection Schemes for Distribution System with Open and Closed-loop

  • Guan, Kang-Le;Lee, Seung-Jae;Choi, Myeon-Song
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.5
    • /
    • pp.969-974
    • /
    • 2013
  • Protection issues in distribution systems which are to be operated in open and closed-loop modes in a smart grid are studied and a generalized protection setting method is proposed to meet the new requirements. The developed setting method assumes a conventional over-current protection scheme for the system with reclosers and over-current relays. In a closed-loop mode, it identifies protective devices that have to be sacrificed in order to maximize protection coordination for bidirectional fault current flow. The proposed setting method has been tested on many systems with different complexity and is proved effective.

VPI-based Control Strategy for a Transformerless MMC-HVDC System Under Unbalanced Grid Conditions

  • Kim, Si-Hwan;Kim, June-Sung;Kim, Rae-Young;Cho, Jin-Tae;Kim, Seok-Woong
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.6
    • /
    • pp.2319-2328
    • /
    • 2018
  • This paper introduces a control method for a transformerless MMC-HVDC system. The proposed method can effectively control the grid currents of the MMC-HVDC system under unbalanced grid conditions such as a single line-to-ground fault. The proposed method controls the currents of the positive sequence component and the negative sequence component without separating algorithms. Therefore, complicated calculations for extracting the positive sequence and the negative sequence component are not required. In addition, a control method to regulate a zero sequence component current under unbalanced grid conditions in the transformerless MMC-HVDC system is also proposed. The validity of the proposed method is verified through PSCAD/EMTDC simulation.

Application of Neural Networks to Sensor Failure Detection, Identification, and Accommodation (신경망을 이용한 감지기의 고장발견, 확인 및 보완에 관한 연구)

  • An, Young-Hwan
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.16 no.2 s.95
    • /
    • pp.211-217
    • /
    • 1999
  • 감지기의 고장 발견, 확인, 보완은 복잡한 항공 시스템의 중요한 문제로 부각되어 왔으며, 그동안 칼만 필터를 이용한 기존 추정기술 혹은 온라인 학습 인공지능 알고리듬 등이 이 같은 문제를 해결하기 위해 제시되어 왔다. 본 연구에서는 여분의 감지기가 없는 항공제어계에 대해 온라인 학습 신경망을 이용한 감지기의 고장 발견, 확인, 그리고 보완에 관해 초점을 둔다. 이 내고장성 항공제어계는 주 신경조직망과 n개의 국소 신경조직망으로 이루어지는데, 포괄적인 감지기의 고장을 발견하는 능력을 가진다. 어떤 경우에서는 기존의 감지기 고장 발견 방법의 성능을 향상시키기 위해 수정된 감지방법이 소개되고 그 보완된 감지방법을 이용하여 기존의 방법과 성능비교가 이루어졌다.

  • PDF