Development of Fault Detection Method for a Transformer Using Neural Network (신경회로망을 이용한 변압기 사고 검출 기법 개발)

  • 김일남;김남호
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.5
    • /
    • pp.43-50
    • /
    • 2003
  • This presents a fault detecting method for a power transformer based upon a neural network. To maintain a normal relay operating conditions, external winding faults of a power transformer and magnetic inrush have been tested under consideration of the EMTP/ATP software and internal faults of power transformer have been tested by the EMTP/BCTRAN software. The neural network has been evaluated by the proposed fault. Input variables of the neural network for the proposed model can be obtained from fundamental currents, restraining and operating currents. This algorithm uses back-propagation and the ratio of a restraining current and an operating current as relay input parameters. The ratio may enhance the fault detection since the restraining currents increase rapidly at external faults. The proposed detecting method has been applied to the practical relay systems for transformer protection. As a result, the proposed detecting method based on the neural network has been shown to have better characteristics.

A Study on the Algorithm for Fault Discrimination in Transmission Lines Using Neural Network and the Variation of Fault Currents (신경회로망과 고장전류의 변화를 이용한 고장판별 알고리즘에 관한 연구)

  • Yeo, Sang-Min;Kim, Chul-Hwan;Choi, Myeon-Song;Song, Oh-Young
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.366-368
    • /
    • 2000
  • When faults occur in transmission lines, the classification of faults is very important. If the fault is HIF(High Impedance Fault), it cannot be detected or removed by conventional overcurrent relays (OCRs), and results in fire hazards and causes damages in electrical equipment or personal threat. The fast discrimination of fault needs to effective protection and treatment and is important problem for power system protection. This paper proposes the fault detection and discrimination algorithm for LIFs(Low Impedance Faults) and HIFs(High Impedance Faults). This algorithm uses artificial neural networks and variation of 3-phase maximum currents per period while faults. A double lines-to-ground and line-to-line faults can be detected using Neural Network. Also, the other faults can be detected using the value of variation of maximum current. Test results show that the proposed algorithms discriminate LIFs and HIFs accurately within a half cycle.

  • PDF

A Study on the Evaluation of Distribution Reliability Considering Reliability Model for a Resistive-Type of Superconducting Fault Current Limiter (저항형 초전도한류기의 신뢰도 모델을 적용한 배전계통 신뢰도 평가에 관한 연구)

  • Kim, Sung-Yul;Kim, Wook-Won;Kim, Jin-O
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.3
    • /
    • pp.465-470
    • /
    • 2011
  • Recently fault currents are increasing in a network. It is caused by increase in electric demand and high penetration of distributed generation with renewable energy sources. Moreover, distribution network has become more and more complex as mesh network to improve the distribution system reliability and increase the flexibility and agility of network operation. Accordingly, the fault current will exceed capacity of circuit breakers soon and all the various rational solutions to solve this problem are taken into account. Under these circumstances, superconducting fault current limiter(SFCL) is a new alternative in the viewpoint of technical and economic aspects. This study presents operation processes for a resistive-type of SFCL, and it proposes reliability model for the SFCL. When a SFCL is installed into a network, the contribution of decreased fault currents to failure for distribution equipments can be quantified. As a result, it is expected that a SFCL makes the reliability of adjacent equipments on existing network improve and these changes are analyzed. We propose a methodology to evaluate the reliability in the distribution network where a SFCL is installed considering a reliability model for resistive-type of SFCL and reliability changes for adjacent equipments which are proposed in this paper.

Fault Detection for thyristors of Power Converter Module in Control Rod Control System (원자로 제어봉구동장치 제어시스템의 전력변환기 사이리스터 고장 검출)

  • Kim, Choon-Kyung;Cheon, Jong-Min;Lee, Jong-Moo;Jung, Soon-Hyun;Kwon, Soon-Man
    • Proceedings of the KIEE Conference
    • /
    • 2003.11c
    • /
    • pp.559-562
    • /
    • 2003
  • In this paper, we introduce a new method detecting thyristor faults of the power converter module in Control Rod Control System. When we control the currents in each coil of Control Rod Drive Mechanism by using the current control method, the current value can follow the current reference despite the faults like the missing phase or the diode acting. Comparing the fault current values with the normal current values, the bad transient characteristics of the abnormal current can make the operations of control rods incorrect. In this case, the information from the current trends cannot be enough to detect the fault occurrence in thyristors. Instead of the coil currents, the state of thyristors can be watched by measuring the coil voltages. In the existing system of Westinghouse type, the ripple detector takes charge of this task. But this detector has some shortcomings in the point of time for fault detection, we come to devise a new fault detection method solving the problems which belong to the ripple detector.

  • PDF

A Design of Power Management and Control System using Digital Protective Relay for Motor Protection, Fault Diagnosis and Control (모터 보호, 고장진단 및 제어를 위한 디지털 보호계전기 활용 전력감시제어 시스템 설계)

  • Lee, Sung-Hwan;Ahn, Ihn-Seok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.10
    • /
    • pp.516-523
    • /
    • 2000
  • In this paper, intelligent methods using digital protective relay in power supervisory control system is developed in order to protect power systems by means of timely fault detection and diagnosis during operation for induction motor which has various load environments and capacities in power systems. The spectrum pattern of input currents was used to monitor to state of induction motors, and by clustering the spectrum pattern of input currents, the newly occurrence of spectrums pattern caused by faults were detected. For diagnosis of the fault detected, the fuzzy fault tree was derived, and the fuzzy relation equation representing the relation between an induction motor fault and each fault type, was solved. The solution of the fuzzy relation equation shows the possibility of each fault's occurring. The results obtained are summarized as follows: 1) The test result on the basis of KEMC1120 and IEC60255, show that the operation time error of the digital motor protective relay is improved within ${\pm}5%$. 2) Using clustering algorithm by unsupervisory learning, an on-line fault detection method, not affected by the characteristics of loads and rates, was implemented, and the degree of dependency by experts during fault detection was reduced. 3) With the fuzzy fault tree, fault diagnosis process became systematic and expandable to the whole system, and the diagnosis for sub-systems can be made as an object-oriented module.

  • PDF

A Study on the Protection System for AT Feeding on the Electric Railway (전기철도 AT급전방식 보호시스템 최적구성 방안 연구)

  • 창상훈;이형수;홍재승;김정훈
    • Proceedings of the KSR Conference
    • /
    • 1999.11a
    • /
    • pp.344-351
    • /
    • 1999
  • The safe operation of electro railways is greatly dependant on its protective systems. The system so-called Fault Protection Wire(FW) is now widely adapted to protect in AT feeding systems. It is connected between the feeder and trolley circuit to return the fault current to autotransfonmers at substation. This paper computed the distribution of fault currents at FW in the system and also evaluated the safety from electric shock when ground fault or flashover occur in the feeding system. The results show FW is useful to protect power supply network from fault in electric railways

  • PDF

Grounding Characteristics Analysis of the Rod-Type Grounding Electrodes used for Electric Distribution Systems (배전계통에 사용되는 봉형 접지전극의 접지 특성 분석)

  • Kim, Kyung-Chul;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.49-56
    • /
    • 2011
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance.

Protection for DFIG using the d-q Equivalent Circuit (d-q 등가회로를 이용한 이중여자 유도발전기 보호)

  • Kang, Yong-Cheol;Lee, Ji-Hoon;Kang, Hae-Gweon;Jang, Sung-Il;Kim, Yong-Gyun;Park, Goon-Cherl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.12
    • /
    • pp.2173-2178
    • /
    • 2008
  • A doubly-fed induction generator(DFIG) system has been widely used in the modem wind turbines due to variable-speed operation, high efficiency and small converter size. It is well known that an inter-turn fault of a generator is very difficult to be detected. The DFIG system uses a wound rotor induction machine so that the magnetizing current of the generator can be fed from both the stator and the rotor. This paper proposes a protection algorithm for a DFIG using the d-q equivalent circuit in the time domain. In the case of a DFIG, the voltages and currents of the rotor side as well as the voltages and currents of the stator are available. The proposed algorithm estimates the instantaneous(i.e., converted into the stationary frame) induced voltages from the rotor and the stator sides. If the difference between the two estimated induced voltages exceeds the threshold, the proposed algorithm detects the inter-turn fault. The algorithm can detect a inter-turn fault of a winding. The performance of the proposed algorithm is validated using a PSCAD/EMTDC simulator under inter-turn fault conditions and normal operating conditions such as an external fault and the change of the wind speed.

The Analysis of Operation Characteristics of Flux-Lock Type High-Tc Superconducting Fault Currents Limiter (자속 구속형 고온초전도 전류제한기의 동작특성 분석)

  • Park Chung-Ryul;Lim Sung-hun;Park Hyoung-Min;Lee Jong-Hwa;Ko Seokcheol;Choi Hyo-Sang;Han Byoung-Sung;Hyun Ok-Bae;Chung Dong-Chul
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1130-1132
    • /
    • 2004
  • In this paper, we investigated the operational characteristics of the fault current limiting in the The flux-lock type high-Tc superconducting fault current limiter. The flux-lock type high-Tc superconducting fault current limiter was consisted of primary and secondary copper coils that flux was locked on iron core and YBCO thin film. The operational characteristic of a flux-lock type SFCL dependent on winding direction of coil 1 and coil 2, and the number of turns of coil 1 and coil 2, inductances of the coils, saturation in iron core, the properties of superconducting element etc. In this cases, we investigated the fault currents limiting characteristics of the flux-lock type SFCL when winding direction of coil 1 and coil 2 was subtractive polarity winding.

  • PDF

Switch Open Fault Diagnosis of Inverter Using Features of dq Currents (dq 전류의 특징을 이용한 인버터의 스위치 개방 고장진단)

  • Kwak, Nae-Joung;Hwang, Jae-Ho;Hong, Won-Pyo
    • Journal of the Institute of Electronics Engineers of Korea SC
    • /
    • v.48 no.1
    • /
    • pp.31-38
    • /
    • 2011
  • Faults of motor drive systems to be used for various industrial applications can cause serious problems. In this paper, a method to diagnose switch open fault of a voltage-fed PWM inverter is proposed. The proposed method normalizes dq current and fault-detection and first classification are performed by mean values of dq phase currents, second classification is performed by features such as the relation of dq phase currents, the ranges of those, the positions of those according to the results, and fault switch is diagnosed with the results. The proposed method performs the simulation for diagnosis of inverter switch open faults with MATLAB and identifies the feasibility of the proposed method. Because the proposed method is implemented by simple algorithms, the proposed algorithm can be embedded in general induction motor drive systems and be used.