• Title/Summary/Keyword: Energized status

Search Result 2, Processing Time 0.017 seconds

A Study on Diagnosis of The Energized Status of 22.9kV Multigrounded Underground Power Cable (22.9kV 다중 접지 지중 전력 케이블의 가압 상태 진단에 관한 기초 연구)

  • Kim, Chang-Gyo;Hong, Jin-Su;Jeong, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.10
    • /
    • pp.699-703
    • /
    • 1999
  • An experimental study to identify the energized status of the 22.9kV underground power cable by the detection of vibration has been performed. We have derived that there exists vibration at double the line frequency in live cables by electromagnetic force. The relative amplitudes of the cable vibration according to the energized status of the cable were calculated by computer simulation. The cable vibration can also be picked up by accelerometer. A prototype was tested on the underground distribution system in Chonan substation, KEPCO. Comparison between simulation results and field test results was performed. The results showed that the energized status of the calble can be identified by measuring the vibration of the cable using accelerometer.

  • PDF

Identification of Energized status of Underground Power Cable (지중 전력 케이블 가압 상태 진단)

  • 김창교;홍진수;정영호
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.11a
    • /
    • pp.69-72
    • /
    • 1998
  • A study to identify the energized status of the 22.9kV underground power cable by the detection of vibration was reformed. We derived that there exists vibration at double the line frequency in live cables by electromagnetic force. The vibration can be picked up by accelerometer sensor. A prototype was tested on the underground distribution system in Chonan Station, KEPCO. The results are presented and suggest the applicability of the detecting device.

  • PDF