• Title/Summary/Keyword: Electrical Substation System

Search Result 504, Processing Time 0.025 seconds

Analysis of the Load Transfer Capacity and Study of Conductor Sizes for Contingency Levels in Distribution Systems (상정사고별 배전측 부하분담 능력 분석과 도체 규격 검토)

  • 조남훈;전영재;한용희;한병성
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.7
    • /
    • pp.363-370
    • /
    • 2003
  • This paper presents the analysis of the load transfer capacity and study of conductor size for variable contingencies in distribution systems. The operation capacity of feeders was changed to improve operation efficiency in KEPCO, considerations for contingencies are still based on the previous capacity. In order to cope with the changes such as operation capacity, it is necessary to study whether the present "contingency support criteria" is reasonable or not, also to confirm the whether the present criteria should be improved or not. We analyze the load transfer capacity and conductor size on a distribution system for contingency levels such as the substation-level, bank-level, feeder-level, and zone-level.one-level.

The Study of characteristic comparison with inrush and fault current occurred in distribution system (배전계통에서 발생하는 돌입전류와 고장전류의 특성 비교연구)

  • 오용택;김진성
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.51-58
    • /
    • 2001
  • This paper gives a type and high-frequency waves analysis of in-rush current cab be flowed into distribution automatic machine to be installed in distribution line in order to use minimizing operation error of failure indicator to have been issue recent with obtaining high-frequency component that can be different from current. The in-rush and fault current data studied in this paper is to be surveyed actually in USA distribution system substation line of Bryan Power Company near Texas A. M University, to be occurred high impedance fault.

  • PDF

Analysis on Current Limiting Characteristics of a Hybrid SFCL with the First Half Cycle Limiting Operation Due to Resistance of Superconducting Element (초전도소자의 저항변화에 따른 반주기내 한류형 하이브리드 초전도 전류제한기의 전류제한 특성 분석)

  • Kim, Jin-Seok;Lim, Sung-Hun;Kim, Jae-Chul;Choi, Jong-Soo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.10
    • /
    • pp.1817-1822
    • /
    • 2011
  • The fault current has been increasing due to expansive substation facilities for meeting the increase of demand. To limit increasing fault current in a power system, among methods the superconducting fault current limiter (SFCL) has been considered to be adopted in the power grid. However, in case of adopting SFCL in the power system, most of SFCLs need to solve problems such as recovery, cost. With efforts to solve those problems, the novel fault current limiting device which is called hybrid SFCL is developed. To apply the hybrid SFCL, it has to be needed to analyze application possibility and itself operation characteristics. In this paper, the fault current limiting and operation characteristics of hybrid SFCL with first half cycle the limiting operation in case of various resistances of superconducting element were analyzed through experiment.

Ageing Diagnostics in Oil Transformer for Large Capacity due to Test methods (시험방법에 의한 대용량 유입변압기의 열화진단)

  • Sim, Yoon-Tae;Kim, Wang-Gon;Hong, Jin-Woong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.96-99
    • /
    • 2003
  • In this paper, ageing diagnostics in the large capacity oil transformer are investigated. Following items are investigated for the ageing diagnostic in transformer oils (leakage current of sensor, power consumption and temperature of transformer oil). All temperature data are gathered from daily report in the substation. The power consumption of transformer are gathered output report of APIS(Airport Power Information System). Especially, data of sensor leakage current are accumulated from the online diagnostic system for transformer oil. The temperature of transformer oils major change factor was ambient temperature and capacity of power load. The leakage current are change by oil temperature. The leakage current ware not more than 2 [nA] in summer,

  • PDF

Measurement of Resistance of Multi-Grounded System by Ground Current Measurement (접지전류 측정에 의한 다중 접지계통의 접지저항 측정)

  • 최종기;안용호;정길조;한병성;김경철
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.234-237
    • /
    • 2004
  • Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.

Analysis of Voltage Stability in Electric Railway Feeding System (전기철도 급전계통의 집전전압 안정도 해석)

  • Lee Chang-Mu;Lee Han-Min;Han Moon-Seob;Kim Joo-Rak;Jung Ho-Seong
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.1384-1389
    • /
    • 2004
  • The primary objective of this paper is to examine the capacity of electrical transmission in electric railway feeding system. Although supply capacity of railway substation are sufficient and there is no accident, due to the electrical transmission limit of feeding line the voltage breakdown may occur when large capacity of electric load at feeding line exist. So, using multi-port analysis model, we draw P-V curve due to the length of feeding line, load, location and power factor of electric locomotive. And through case study, compare measurement result and simulation result

  • PDF

On-line Insulation Diagnostic by PD Monitoring Field Practical of UHF Technique for On-line PD Monitoring (UHF 기술을 이용한 온라인 부분방전 모니터링)

  • Oh, Yong;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.176-180
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers is designed, which has been installed inside the oil tank of transformer in a substation by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

Economic Evaluation of Power Grid Interconnection between Offshore Wind Power Plants (해상풍력발전단지 간의 전력계통 연계에 관한 경제성 분석 연구)

  • Moon, Won-Sik;Jo, Ara;Kim, Jae-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.4
    • /
    • pp.339-344
    • /
    • 2014
  • An offshore wind power plant (WPP) is very expensive and different from an onshore wind power system in many ways. There has been a continuous increase in the capacity of the offshore WPPs. Therefore it is essential to analyze the feasibility and reliability of the offshore wind power to optimize their redundancy. Besides, it is very important to study a planning for grid interconnection of adjacent offshore WPPs. This paper proposes a economic evaluation method to interconnect with adjacent offshore substations in offshore wind power grid. Also, we suggest the probabilistic reliability method to calculate a probabilistic power output of the wind turbine and a cost of the expected energy not supplied that is used as the reliability index of the power system.

Measurement of Resistance of Multi-Grounded System by Ground Current Measurement (접지전류 측정에 의한 다중 접지계통의 접지저항 측정)

  • 최종기;안용호;정길조;한병성;김경철
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.4
    • /
    • pp.234-234
    • /
    • 2004
  • Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.

Coordinated Control of SVC and ULTC Considering Reactive Power Compensation Margin (무효전력 보상여유를 고려한 SVC와 ULTC의 협조제어)

  • Moon, Kyeong-Seob;Son, Kwang-Myoung;Lee, Tae-Gi;Lee, Song-Keun;Park, Jong-Keun
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.4
    • /
    • pp.351-357
    • /
    • 1999
  • This paper proposes the coordinated control of SVC and UTLC at the distribution substation to get larger operating margin of SVC for the voltage stability control by reactive power compensation. In the conventional method, ULTC doesn't respond to the variation of source voltage, so SVC has the entire responsibility for it. It could cause the lack of operating margin of SVC in some condition. It, however, is important to secure an operating margin for the dynamic stability control in emergancy. This paper proposes the coordinated control method that SVC controls the supply voltage and ULTC respond to the SVC compensation valve based on the relation between SVC compensation and ULTC tap position. The numerical simulation verifies that the proposed system could increase the operating margin of SVC compared with the conventional system.

  • PDF