• Title/Summary/Keyword: Electric fire detection

Search Result 52, Processing Time 0.027 seconds

A study on the detection of poor contact and arcing fault using a fuzzy logic (퍼지논리를 적용한 전기적 접촉불량 및 아크 검출에 관한 연구)

  • Kim, Hyun-Woo;Kim, In-Tae
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2007.11a
    • /
    • pp.205-210
    • /
    • 2007
  • This study on the prevention of electric fire. Generally the electric fire is caused by break or disconnection of the power line, short circuit and poor contact, arcing fault ect. In these causes, this paper is studied on the detection of poor contact and arcing fault. The arcing fault is caused by poor contact mainly. The arcing fault can occurs a electric fire by interaction of flammable gas and materials and it can be caused of tracking and carbonization. These phenomenons is also caused of electric fire. Therefore this paper is studied on the detection of arcing fault and poor contact.

  • PDF

Detection of Current Signal and Thermal Characteristics of Electric Fan Operated in Various Situations (선풍기의 운전 상황별 발열특성 및 전류신호 검출)

  • Kim, Doo-Hyun;Lee, Heung-Su
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.3
    • /
    • pp.20-27
    • /
    • 2014
  • Cooling equipment is the frequent occurrence of fire despite the absence of the heating element. National fire statistics in 2013 show that a total of 263 fires occurred in the cooling equipment and the number of electric fan has 145 fire cases. This is accounted for 55.1% of the whole. Electric fan is the electrical appliance that the heat is generated on the winding wire and the iron core. If such characteristic is not controled properly, fire would break out at the electric fan. also there is a gap filled with an insulator between connection terminals of the capacitor in the electric fan. But in case that the gap on the capacitor is covered with some conductive material such as dust, there would be a fire as well caused by electrical heating locally. Although many studies related with those have been conducted, electric fan fire is continuously occurred. In this study, thermal characteristics and current signal in various conditions such as the heat generation of windings including iron cores of the motor and the dielectric breakdown of terminals on the capacitor connected to the motor were detected. In order to measure the maximum temperature, "third level" wind velocity button was pushed and the time selection switch to "continuation" was set. Analyzed data would be available for the fire safety of the electric fan.

Development of Parallel Arc Fault Detector Using Ripple Voltage (리플전압을 이용한 병렬아크 사고 감지기 개발)

  • Choi, Jung-Kyu;Kwak, Dong-Kurl
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.5
    • /
    • pp.453-456
    • /
    • 2016
  • The major causes of electrical fire in low-voltage distribution lines are classified into short-circuit fault, overload fault, electric leakage, and electric contact failure. The special principal factor of the fire is electric arc or spark accompanied with such electric faults. This paper studies the development of an electric fire prevention system with detection and alarm of that in case of parallel arc fault occurrence in low-voltage distribution lines. The proposed system is designed on algorithm sensing the instantaneous voltage drop of line voltage at arc fault occurrence. The proposed detector has characteristics of high-speed operation responsibility and superior system reliability from composition using a large number of semiconductor devices. A new sensing control method that shows the detection of parallel arc fault is sensed to ripple voltage drop through a diode bridge full-wave rectifier at electrical accident occurrence. Some experimental tests of the proposed system also confirm the practicality and validity of the analytical results.

A Study on Development of App-Based Electric Fire Prediction System (앱기반 전기화재 예측시스템 개발에 관한 연구)

  • Choi, Young-Kwan;Kim, Eung-Kwon
    • Journal of Internet Computing and Services
    • /
    • v.14 no.4
    • /
    • pp.85-90
    • /
    • 2013
  • Currently, the electric fire prediction system uses PIC(Peripheral Interface Controller) for controller microprocessor. PIC has a slower computing speed than DSP does, so its real-time computing ability is inadequate. So with the basic characteristics waveform during arc generation as the standard reference, the comparison to this reference is used to predict and alarm electric fire from arc. While such alarm can be detected and taken care of from a remote central server, that prediction error rate is high and remote control in mobile environment is not available. In this article, the arc detection of time domain and frequency domain and wavelet-based adaptation algorithm executing the adaptation algorithm in conversion domain were applied to develop an electric fire prediction system loaded with new real-time arc detection algorithm using DSP. Also, remote control was made available through iPhone environment-based app development which enabled remote monitoring for arc's electric signal and power quality, and its utility was verified.

Design and Implementation of a Multi-purpose Test Equipment with a Large Utilization Range for use in Electric Fire (전기화재 분야에서 다목적으로 시험장치의 활용범위를 증가시키기 위한 시험장치의 설계 및 구현)

  • Dongcheol Shin;Hyoungho Ko
    • Journal of Sensor Science and Technology
    • /
    • v.32 no.3
    • /
    • pp.180-186
    • /
    • 2023
  • Test devices can perform various functions, such as research on detection targets, sensors that detect detection targets, combined products containing sensors, and certification for the launch of combined products. However, the scope of use of test devices is limited because they perform only a single role or could only serve a particular purpose in the past. Therefore, studies on test devices that can perform various functions, such as research on detection targets, sensors that detect detection targets, combined products containing sensors, and certification for the release of combined products are necessary. Accordingly, this study proposes a test device that can increase the scope of use in the technical field of electric fires. In addition, we examine various outcomes of the proposed test device.

A Study on the Detection Technique of the Flame and Series arc by Poor Contact (접촉 불량에 의한 불꽃 및 직렬아크의 검출 기법에 관한 연구)

  • Woo, Kim Hyun;Hyun, Baek Dong
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.24-30
    • /
    • 2012
  • This study is on the method of the detection for flame and series arc which can be happened at poor contact point added a vibration in part of contact point of low voltage line. In general, the causes of electric fire are over current, short circuit, poor contact, ect. The over-current or short circuit among those causes is detected by measuring a instant current value, but poor contact is difficult to detect by measuring a excessive value of the voltage and current and a distortion of waveforms. And therefore, in this paper, it is studied on the optimal technique of the arc judgement using fuzzy logic and MDET (Multi Dimension Estimation Technique). And it carries out the simulation for arc detection and the experiment for controller and load test. In result, the controller and detection algoristhm, is classified with normal wave and abnormal arc wave without relation with each loads and so the controller can detect a series arc successfully.

Electrical Fire Detection System using Temperature and Current Detectors (열.전류 감지기를 이용한 전기화재감지시스템)

  • Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.22 no.3 s.81
    • /
    • pp.7-12
    • /
    • 2007
  • This paper presents the development of an electrical fire detection system using digital temperature and current detectors in order to sound for electrical fire in advance. As the demand for electricity is increasing and industrial facilities are getting more complex and larger in size, the losses of human life and property are on the increase by electrical fires. In order to prevent electrical fires, it is required to find out fire signatures, or electric signal of the overcurrent and overheating. Therefore, in this paper, developed is an electrical fire detection system based on the detection of signal for overcurrent and overheating to prevent electrical accidents in advance that happen in electrical wires. The developed system gives an alarm by computer monitor, speaker system and mobile phone before electrical fires occur and give severe damages to human beings and properties, and the system can be implemented and supplied for business and residental buildings at a low price. The usefulness and validity of the system, also, verified in this paper by case study and experiments.

Electric Fire Prediction by Detection of Spark Signals (스파크 신호검출에 의한 전기화재 예측)

  • 김일권;송재용;길경석;권장우
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2001.10a
    • /
    • pp.371-374
    • /
    • 2001
  • This paper describes a technique that can predict electric fires by detecting a spark signal generated from operation of electric facilities. An electric fire lead a loss of life as well as huge property, therefore it is very Important to predict an electric fire and eliminate the causes of it. Electrical spark which is ranked as majority causes of electric fires has a characterized frequency bandwidthdistinguishedfrompowerfrequenry. In the experiment, various spark signals are simulated in a condition such as short circuit, flashover and surface discharge. The results showed that the monitoring of spark signals can predict electric fires.

  • PDF

The Arc Fault Determination Method for the Electric Fire Prevention (전기화재 방지를 위한 아크고장 판단기법에 대한 연구)

  • Ko, Yun-Seok
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.3 no.4
    • /
    • pp.260-265
    • /
    • 2008
  • The arc-fault occurring in the customer system becomes the direct cause of electric fire. However, it is very difficult to identify the arc-fault using the existing fault detection mechanism because the magnitude of the fault current is very small. Accordingly, this paper analyzes the causes of arc fault and designs the basic detection mechanism of arc fault. And then, it proposes an signal processing-based arc-fault determination methodology which can enhance the of accuracy of the arc-fault determination by applying DFT/DWT to the voltage and current waveform. Finally, this paper showed the application methodology of the proposed signal processing based fault determination method by applying and analyzing DFT/DWT to an high voltage in-rush current waveform.

  • PDF

Analysis of Serial Arc with DC Current (DC 전류에 의한 직렬 아크 특성 분석)

  • Ban, Gi-Jong;Nam, Moon-Hyun;Kim, Lark-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1700-1701
    • /
    • 2007
  • DC Arc Fault Current is an electric discharge which is occurred in two opposite electrode. In this paper, DC arc detection device is designed for the display of DC arc fault current which is occurred in the local electric network with DC Power. This DC arc is one of the main causes of electric fire. Arc fault in electrical network has the characteristics of low current, high impedance and low frequency. DC Arc current detection device is designed for the display of arc fault current which has the modified arc characteristics.

  • PDF