• 제목/요약/키워드: Effective Impulse Impedance

검색결과 25건 처리시간 0.024초

Effective Impulse Impedances of Deeply Driven Grounding Electrodes

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong;Chang, Keun-Chul
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제4C권5호
    • /
    • pp.207-214
    • /
    • 2004
  • This paper presents the characteristics of transient and effective impulse impedances for deeply driven grounding electrodes used in soil with high resistivity or in downtown areas. The laboratory test associated with the time domain performance of grounding piles subjected to a lightning stroke current has been carried out using an actual-sized model grounding system. The ground impedances of the deeply driven ground rods and grounding pile under impulse currents showed inductive characteristics, and the effective impulse ground impedance owing to the inductive component is higher than the power frequency ground impedance. Both power frequency ground impedance and effective impulse ground impedance decrease upon increasing the length of the model grounding electrodes. Furthermore, the effective impulse ground impedances of the deeply driven grounding electrodes are significantly amplified in impulse currents with a rapid rise time. The reduction of the power frequency ground impedance is decisive to improve the impulse impedance characteristics of grounding systems.

가변주파수 및 임펄스 전류를 이용한 과도접지임피턴스 분석 (An Analysis Method for the Transient Ground Impedance Using Variable Frequency Current and Lightning Impulse)

  • 조성철;엄주홍;이태형
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2007년도 추계학술대회 논문집
    • /
    • pp.231-234
    • /
    • 2007
  • This paper presents an analysis method of transient ground impedance using the lightning impulse and variable frequency currents. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient impedance of the grounding system. There are some differences between the effective impulse ground impedance which was introduced some papers and the transient ground impedance. The transient ground impedance measured from the peak value of impulse voltage and the peak value of impulse current is more reliable than the effective impulse ground impedance.

  • PDF

가변주파수 및 임펄스 전류를 이용한 과도접지임피던스 분석 (An Analysis Method for the Transient Ground Impedance Using Variable Frequency and Lightning Impulse Current)

  • 엄주홍;조성철;이태형
    • 조명전기설비학회논문지
    • /
    • 제22권6호
    • /
    • pp.100-108
    • /
    • 2008
  • 접지전극의 형태, 크기, 재질 및 임펄스전류의 형상에 따라 변화하는 과도접지임피던스는 접지시스템의 성능에 중요한 영향을 미친다. 본 논문은 기존의 실효임펄스임피던스가 실제 과도접지임피던스를 얼마나 효과적으로 나타내고 있는가에 대한 분석과 보다 효과적인 과도접지임피던스 평가방법에 대하여 실험적인 결과를 제시하였다. 실험에 사용된 접지전극은 저항성분과 인덕턴스를 포함한 모의 접지전극과 1[m] 탄소접지봉, 9[m] 일반동봉 그리고 40[m] 매설지선이며, 가변주파수 전류와 임펄스전류에 의한 접지임피던스를 각각 측정하였다. 각각의 값을 비교 했을 때 기존의 실효임펄스임피던스의 값보다는 전압의 최대 값과 전류의 최대 값을 이용하여 과도접지임피던스를 구한 임피던스 값($Z_1$)이 등가주파수에 해당하는 가변주파수 전류에 의해 구해진 접지임피던스에 근접함을 확인하였다.

서지전류에 대한 과도접지임피던스의 특성 (Characteristics of Transient Grounding Impedance under Surge Currents)

  • 이덕희;박종순
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권11호
    • /
    • pp.717-723
    • /
    • 1999
  • The transient characteristics of grounding systems play a major role in the protection of power equipments, electronic circuits and info-communication facilities against surges which arise from lightning or ground faults. Electronic devices are very weak against lightning surges injected from grounding systems and can be damaged. The malfunction and damage of electronic circuits bring about bad operation performances, a lot of economical losses, and etc. Therefore, in order to obtain the effective protection measure of electronic devices from overvoltages and lightning surges, the analysis of the transient grounding impedances in essential. One of this work is to examine the transient behaviors of grounding impedances under steplike currents for various grounding systems. And the other of this work is to evaluate the transient behaviors of a grid with rods under impulse currents and to investigate the effect of grounding lead wire. Transient grounding impedances of a grid with rods under impulse current waves have been measured as a parameter of the length of the grounding leads. Z-t, Z-i and V-i curves of transient grounding impedance under impulse current waveforms have been measured and analyzed. It was found that the grounding impedance gives the inductive, resistive and capacitive aspects under steplike current. Transient grounding impedance characteristics were very different with shapes, geometries of ground electrodes. Also, they were dependent on the waveform and magnitude of impulse current.

  • PDF

접지전극의 형상에 따른 과도접지임피던스 (Transient Ground Impedances According to Shapes of Grounding Electrodes)

  • 이복희;이수봉;이태형;정현욱;정동철
    • 조명전기설비학회논문지
    • /
    • 제20권1호
    • /
    • pp.65-70
    • /
    • 2006
  • 본 논문은 임펄스전류에 따른 접지시스템의 과도 특성에 관한 것으로 임펄스 전류를 심매설 봉상 접지전극과 그리드 접지전극에 인가하였을 때 나타나는 과도접지임피던스를 조사하였다. 과도접지임피던스는 인가전류의 상승시간과 접지전극의 크기 및 형태에 강하게 의존하며, 접지전극의 인덕턴스는 짧은 시간 영역에서 접지시스템의 과도 접지임피던스에 크게 영향을 미치는 것으로 나타났다. 또한 심매설 봉상접지전극은 짧은 시간영역에서 과도접지임피던스를 줄이는데 효과적이었다.

임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선 (Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents)

  • 이수봉;이봉;이승주;전병욱;이복희
    • 조명전기설비학회논문지
    • /
    • 제22권10호
    • /
    • pp.62-68
    • /
    • 2008
  • 본 논문은 임펄스전류의 인가위치에 따른 심매설 봉상 접지전극의 과도접지임피던스와 규약접지임피던스 특성에 관하여 기술하였다. 과도접지임피던스는 심매설 접지전극의 길이 및 임펄스전류의 상승시간과 인가위치에 강하게 의존하며, 접지전극의 자체 인덕턴스는 짧은 시간 영역에서 점지시스템의 과도접지임피던스에 크게 영향을 미치는 것으로 나타났다. 심매설 봉상 접지전극의 자체 인덕턴스의 저감은 과도접지임피던스 특성의 개선에 결정적인 역할을 한다. 접지도선의 길이는 최대한 짧게 하여 접지전극의 상단에 접속하는 것이 효과적이다.

봉상 접지전극에시 전류유입위치에 따른 임펄스 접지임피던스의 특성 (Behaviors of Impulse Ground Impedances Associated with the Current Injection Point in a Ground Rod)

  • 이복희;정동철;이수봉
    • 조명전기설비학회논문지
    • /
    • 제19권1호
    • /
    • pp.94-100
    • /
    • 2005
  • 본 논문은 전류유입위치에 따른 봉상접지전극의 과도 및 실효임펄스임피던스의 특성에 관한 것으로 뇌격전류를 인가하여 실규모 접지봉에 대한 시간영역에서의 성능을 평가하였다. 임펄스전류가 가해진 봉상접지전극의 과도 접지임피던스는 접지저항보다 높게 나타났으며, 접지전극의 길이가 길어짐에 따라 접지저항과 실효임펄스접지임피던스는 감소되었다. 또한 실효임펄스접지임피던스는 짧은 시간범위에서는 급격하게 증가하였다. 접지저항의 저감은 접지시스템의 임펄스임피던스 특성의 개선에 결정적인 역할을 한다. 임펄스전류를 접지봉의 하단에 인가하였을 때 접지봉 전위의 파두부에 고주파의 진동 파형이 포함되고 실효임펄스임피던스는 다른 경우보다 높게 나타났다.

다른 형상의 접지전극에 접속된 심매설 접지전극의 실효임펄스임피던스 (Effective impulse impedances of a deep-driven ground rod combined with other grounding electrodes)

  • 이복희;장근철;이수봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.565-569
    • /
    • 2004
  • This paper deals with the characteristics of potential rise and effective impulse impedance of deep-driven ground rods that are used in high resistivity soil or in confined places such as downtown. Also the effects of the impulse and fault currents on the deep-driven ground rods combined with different type grounding electrodes like as mesh grids and counterpoises are described. The $8/20{\mu}s$ impulse current and other wave currents with different rise times are injected into the test ground rod and the effective impedances are examined. The most effective way to obtain the fine transient impedance behaviors of deep-driven ground rods is to reduce the inductive component of grounding electrode systems combined with other ground electrodes.

  • PDF

그리드접지와 심매설 접지전극의 과도임피던스 (Transient Impedance of the Ground Grid and Deeply-driven Ground Rod)

  • 이복희;이수봉;이태형;정현욱;정동철;길형준
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.240-243
    • /
    • 2005
  • This paper presents the transient behaviors of grounding system impedance against lighting impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current with various rise time were investigated. It was found that the transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system in the short time domain.

  • PDF

인하도선 길이에 따른 과도접지임피던스 특성 (Effects of Length of Down Conductor on Transient Ground Impedance)

  • 이복희;정동철;이수봉;이태형;정현욱;이규선;이승칠
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2235-2237
    • /
    • 2005
  • This paper presents the transient impedance behaviors of grounding systems to lightning impulse current. The potential rise and effective impulse ground impedance of the test grounding electrodes were measured as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the impulse current shapes and lengths of down conductor, and the inductance of reduce of grounding electrode inductance is an important factor to improve the transient ground impedance.

  • PDF